background image

                                        

INSTRUCTION MANUAL 

Metal Housed Alarm Tone and Voice 

Annunciation Sounder/Sounder Beacon Range. 

 

European Safety Systems Ltd.

  

Impress House, Mansell Road, Acton, London W3 7QH    

 

 

[email protected]

     Tel: +44 (0)208 743 8880 

                                                                                                                                                        

www.e2s.com

    Fax: +44 (0)208 740 4200 

Document No. D172-00-051-IS_Issue_B    16-11-22 
 

Sheet 1 of 9 

1)  Introduction 

The  Appello  tone  and  speech  annunciation 
sounder has three different styles in DC. 

 

D105AX 

Sounder 

 

DL105AXX  Sounder Beacon (Xenon) 

 

DL105AXH  Sounder Beacon (LED) 
 

These  Sounder  units  share  a  common  set  of 
functions:- 

 

4  stages,  each  stage  can  record  up  to  30 
seconds of CD quality audio. 

 

Facility to record via an on board microphone 
or a line in input. 

 

The  recorded  message  can  be  played  back 
proceeded  either  with  or  without  the  choice 
of one of forty five tones. 
 

The Beacon functions are either:- 

 

Xenon Strobe: 

o

 

1Hz flash rate 

o

 

1.5Hz flash rate 

o

 

Double strike flash pattern 

 

LED: 

o

 

Steady 

o

 

2Hz flash rate 

2)  Operating and Marking 

 
All 

units 

have 

the 

following 

operating 

requirements and limitations. 
 

Sounder only outputs 

Unit Type No.       Voltage   Range          Current 
D105AX  

24Vdc    10-30Vdc      256mA  

 

 

Max Current 256mA @ 30Vdc 

 
DL105AXX & DL105AXH sounder beacon units - 
Add selected sounder & beacon currents to 
calculate total current required. 
  
 

 

Beacon only outputs 

Unit Type No.       Voltage   Range          Current 
Xenon Beacon   12Vdc    10-14Vdc      500mA 
 

 

24Vdc    20-28Vdc      250mA 

 
LED Beacon 

24Vdc    10-30Vdc      157mA  

 

 

Max Current 166mA @ 30Vdc 

 
 
Operating Temp:  -25 to +55

IP Rating: 

Type 4 / 4X / 3R / 13 , IP66 

 

Marking:  

 

 

 

 
 
 
 
 

3)  Installation & Wiring Requirements

 

 

D105AX 

 

 
DL105AXX & DL105AXH

 

 

 
Always de-energize unit before removing cover. 
The installation of the units must be in accordance 
with  any  local  codes  that  may  apply  and  should 
only  be  carried  out  by  a  competent  trained 
electrical engineer. 
The power terminals on the control unit are clearly 
marked and will accept up to 1.5mm

2

 cable.

 

 
 

 

 

 

DC Terminals  
On main PCB. 

 

 

 

++ = Positive 

 

 

 

- -  = Negative 

 
 

The  DL105AXX  &  DL105AXH  units  will  have  the 
beacon  already  prewired  to  the  unit  so  no  extra 
wiring is required. 
 
 
 
 
 

Содержание D105AX

Страница 1: ...Steady o 2Hz flash rate 2 Operating and Marking All units have the following operating requirements and limitations Sounder only outputs Unit Type No Voltage Range Current D105AX 24Vdc 10 30Vdc 256mA...

Страница 2: ...nnector the unit will need to be supplied with power DC units can be powered when completing recording and set up See section 7 Appello Setup Guide overleaf for Set up instructions and functions 6 Ton...

Страница 3: ...llo unit can be set up to either play an attention seeking tone and then a recorded message or just play the recorded message The user can o Record on each of the 4 stages using either the Line In or...

Страница 4: ...tch 3 Off Alarm Stage 4 3 Stage selection switch 4 Line In selected On board Microphone selected 5 Program Record Erase Mode ON Playback Record Erase Mode OFF 6 Message Tone Playback Message only Play...

Страница 5: ...ons 2 4 to ON For Stage 4 Set Switch S2 position 4 to ON To record from Line in instead of the on board microphone follow above step 1 but set Switch S2 position 4 to OFF 2 Switch on power or Press re...

Страница 6: ...B 16 11 22 Sheet 6 of 9 Quick Ref Erase Single stage Mode Stage 1 illustrated 1 For Stage 1 Set Switch S2 positions 2 3 7 to ON Alternatively for For Stage 2 Set Switch S2 positions 3 7 to ON For Stag...

Страница 7: ...0 051 IS_Issue_B 16 11 22 Sheet 7 of 9 Quick Ref Mass Erase Mode Erases All Stages 1 Set Switch S2 position 7 to ON 2 Set jumper J4 ME to ON position centre and right pin connected 3 Switch on power o...

Страница 8: ...umper J5 S M on Master unit to master position on Set jumper J5 S M on Slave unit to slave position off Position of S2 switch does not affect synch operation 3 Switch on power onto the Master unit fir...

Страница 9: ...e 19 1 4KHz 1 6KHz 1s 1 6KHz 1 4KHz 0 5s NFC48 265 Tone 2 Tone 5 Tone 29 Tone 20 660Hz Continuous Tone 2 Tone 5 Tone 29 Tone 21 554Hz 440Hz 1Hz Alternating Tone 2 Tone 5 Tone 29 Tone 22 544Hz 0 875 se...

Отзывы: