INSTRUCTION MANUAL
Metal Housed Alarm Tone and Voice
Annunciation Sounder/Sounder Beacon Range.
European Safety Systems Ltd.
Impress House, Mansell Road, Acton, London W3 7QH
Document No. D172-00-051-IS_Issue_B 16-11-22
Sheet 1 of 9
1) Introduction
The Appello tone and speech annunciation
sounder has three different styles in DC.
•
D105AX
Sounder
•
DL105AXX Sounder Beacon (Xenon)
•
DL105AXH Sounder Beacon (LED)
These Sounder units share a common set of
functions:-
•
4 stages, each stage can record up to 30
seconds of CD quality audio.
•
Facility to record via an on board microphone
or a line in input.
•
The recorded message can be played back
proceeded either with or without the choice
of one of forty five tones.
The Beacon functions are either:-
•
Xenon Strobe:
o
1Hz flash rate
o
1.5Hz flash rate
o
Double strike flash pattern
•
LED:
o
Steady
o
2Hz flash rate
2) Operating and Marking
All
units
have
the
following
operating
requirements and limitations.
Sounder only outputs
Unit Type No. Voltage Range Current
D105AX
24Vdc 10-30Vdc 256mA
Max Current 256mA @ 30Vdc
DL105AXX & DL105AXH sounder beacon units -
Add selected sounder & beacon currents to
calculate total current required.
Beacon only outputs
Unit Type No. Voltage Range Current
Xenon Beacon 12Vdc 10-14Vdc 500mA
24Vdc 20-28Vdc 250mA
LED Beacon
24Vdc 10-30Vdc 157mA
Max Current 166mA @ 30Vdc
Operating Temp: -25 to +55
C
IP Rating:
Type 4 / 4X / 3R / 13 , IP66
Marking:
3) Installation & Wiring Requirements
D105AX
DL105AXX & DL105AXH
Always de-energize unit before removing cover.
The installation of the units must be in accordance
with any local codes that may apply and should
only be carried out by a competent trained
electrical engineer.
The power terminals on the control unit are clearly
marked and will accept up to 1.5mm
2
cable.
DC Terminals
On main PCB.
++ = Positive
- - = Negative
The DL105AXX & DL105AXH units will have the
beacon already prewired to the unit so no extra
wiring is required.