Document No. IS 2427-P   Issue B       17-04-02                                     Sheet 2 of 4 

The  Sontels  should  be  securely  bolted  to  a  suitable  surface 
using  the  7mm  diameter  boltholes  in  the  stainless  steel  U 
shaped mounting bracket (see figure 1). The angle can then be 
adjusted in the direction that the sound is primarily required to 
cover. This can be achieved by loosening the two large bracket 
screws in the side of the unit, which  allow adjustment in steps 
of 18

°

.  On completion  of  the installation  the  two  large  bracket 

adjustment  screws  on  the  side  of  the  unit  must  be  fully 
tightened to ensure that the unit cannot move in service. 

 

 

7) 

Safety Warning (Electrostatic Hazard)

 

 

The acoustic horn section is made of ABS Plastic, therefore to 
avoid  a  possible  ELECTROSTACTIC CHARGE  the  unit  must 
only be cleaned with a damp cloth. 

 

8) 

Access to the Flameproof Enclosure

 

 

In  order  to  connect  the  electrical  supply  cable  and  the 
telephone line cable to the Sontel it is necessary to remove the 
flameproof cover to gain access to the flameproof chamber. To 
achieve this remove the four M6 hexagon socket head screws 
(see  figure  2)  and  withdraw  the  flameproof  cover  taking  
extreme  care  not  to  damage  the  flameproof  joints  in  the  
process.  
 
Note  the  four 

M6  screws  are  Class  A4-80  stainless  steel 

and  only  screws  of  this  category  can  be  used  on  these 
Sontels. 

It  is  therefore  important  that  these  screws  and  their 

spring washers are kept in a safe place during installation. 

 

On  completion  of  the  cable  wiring  installation  the  flameproof 
joints  should  be  inspected  to  ensure  that  they  are  clean  and  
that  they  have  not  been  damaged  during  installation.  Also 
check  that  the  earth  bonding  wire  between  the  two  casting 
sections  is  secure  and  the  ‘O’  ring  seal  is  in  place.  W hen 
replacing  the flameproof cover casting ensure  that  it  is  square 
with the flameproof chamber casting before inserting. Carefully 
push the cover in place allowing time for the air to be expelled. 
Only  after  the  cover  is  fully  in  place  should  the  four  M6 
Stainless  Steel  A4-80  cover  bolts  and  their  spring  washer  be 
inserted and tightened down. If the cover jams while it is being 
inserted, carefully remove it and try again. Never use the cover 
bolts to force the cover into position. 
 

9) 

Power Supply Selection 

 

It  is  important  that  a suitable power  supply  is  used to  run  the  
Sontels.  
 
The  following  table  shows  the  input  current  taken  by  the  
various units:- 

 

Unit Type 

Input  

 

Input 

 

Max. 

 

 

Voltage   

Current   

I/P Volts

 

 
 
BExTS110D 

230V AC   

56mA 

 

264V 

BExTS110D 

110V AC   

93mA 

 

121V 

BExTS110D 

115V AC   

110mA 

 

126V 

 

The  input  current  will  vary  according  to  the  voltage input  level 
and  the  frequency  of  the  tone  selected.  The  current  levels 
shown  above  are  for  the  440Hz  Continuous  tone  @  nominal 
input  voltage.  The  units  have  a  switching  voltage  regulator 
circuit  and  therefore  the  input  current  level  will  decrease 
slightly  as  the  input  voltage  in  increased  and  will  increase 
slightly as the input voltage is reduced.  
 
The  above  table  also  shows  the  maximum  voltages  at  which 
the sounders can be operated. 
 

10) 

 Cable Selection 

 

W hen selecting the cable size  consideration  must  be  given  to 
the  input  current  that  each  unit  draws  (see  table  above),  and 
the length of the cable runs.  
 
SAFETY  WARNING:  If  the  high  output  BExTS110D  units  are 
used  at  high  ambient  temperatures,  i.e.  over  +40ºC,  then  the 
cable  entry  temperature  may  exceed  +70ºC  and  therefore 
suitable  heat  resisting  cables  must  be  used,  with  a  rated 
service temperature of at least 95ºC. 
 

11) 

  Earthing

 

 

The  Sontel  units  must  be  connected  to  a  good  quality  earth. 
The  units  are  provided  with  internal  and  external  earthing  
terminals  which  are  both  located  on  the  terminal  chamber 
section of the unit (see figures 2 and 3).  

Figure 1 

Plastic Acoustic Horn 
 
Please see Safety Warning 
in Section 7 of this manual 

Flameproof  
Chamber

 

Flameproof  
Cover

 

S/S Mounting 
Bracket

 

Figure 2 

4 off M6 Cover Screws 

External Earth  
Terminal

 

Содержание BExTS110D

Страница 1: ...ertificate issued by KEMA and have been approved to the following standards EN 50014 1992 prA1 General Requirements EN 50018 1994 prA1 Flameproof Enclosure d 4 Installation Requirements The Sontels must be installed in accordance with the latest issues of the relevant parts of the BS EN 60079 specifications or the equivalent IEC specifications Selection Installation and maintenance of electrical a...

Страница 2: ...he O ring seal is in place W hen replacing the flameproof cover casting ensure that it is square with the flameproof chamber casting before inserting Carefully push the cover in place allowing time for the air to be expelled Only after the cover is fully in place should the four M6 Stainless Steel A4 80 cover bolts and their spring washer be inserted and tightened down If the cover jams while it i...

Страница 3: ... board has two terminal blocks one for the mains supply input voltage and one for the telephone signal input cable see figure 4 The mains input cable should enter the enclosure via one of the M20 cable entries and be connected to the supply terminals L and N and the telephone signal cable should enter the enclosure via the other M20 entry and be connected to the telephone terminal A single wire wi...

Страница 4: ...400 2900Hzat 2Hz 1 0 0 1 0 11 Intermittent 1000Hz at 0 5Hz General alarm 0 1 0 1 0 12 Alternating 800 1000Hz at 0 875Hz 1 1 0 1 0 13 Intermittent 2400Hz at 1Hz 0 0 1 1 0 14 Intermittent 800Hz 0 25s on 1s off 1 0 1 1 0 15 Continuous at 800Hz 0 1 1 1 0 16 Intermittent 660Hz 150mS on 150mS off 1 1 1 1 0 17 Alternating 544Hz 100mS 440Hz 400mS 0 0 0 0 1 18 Intermittent 660Hz 1 8s on 1 8s off 1 0 0 0 1 ...

Отзывы: