Document No. IS 2424-P     Issue B     17-04-02                                  Sheet 2 of 4 

loudspeakers  should  only  be  fixed  to  services  that  can  carry 
the weight of the unit. 
 
The  loudspeakers  should  be  securely  bolted  to  a  suitable 
surface using the 7mm diameter boltholes in the stainless steel 
U shaped mounting bracket (see figure 1). The angle can then 
be adjusted in the direction that the sound is primarily required 
to  cover.  This  can  be  achieved  by  loosening  the  two  large 
bracket  screws in  the  side of  the unit,  which  allow  adjustment 
in steps of 18

°

. On completion of the installation the two large 

bracket adjustment screws on the side of the unit must be fully 
tightened  to  ensure  that  the  loudspeaker  cannot  move  in 
service. 

 

 

7) 

Safety Warning (Electrostatic Hazard)

 

 

The acoustic horn section is made of ABS Plastic, therefore to 
avoid  a  possible  ELECTROSTACTIC CHARGE  the  unit  must 
only be cleaned with a damp cloth. 

 

8) 

Access to the Flameproof Enclosure

 

 

Access  to  the  flameproof  enclosure  will  not  normally  be 
necessary  as  the  cables enter  the  unit  in  the  Ex  ‘e’  Increased 
Safety  Termination  enclosure.  Access  will  only  be  required  if 
you  need  to  fit  an  end  on  line  monitoring  component  (see 
section  15  of  this  manual).  To  gain  access  to  the flameproof 
enclosure,  remove  the  four  M6  hexagon  socket  head  screws 
(see  figure  2)  and  withdraw  the  terminal  chamber  taking  
extreme  care  not  to  damage  the  flameproof  joints  in  the  
process.  
 
Note  the  four 

M6  screws  are  Class  A4-80  stainless  steel 

and  only  screws  of  this  category  can  be  used  on  these 
sounders. 

It is therefore important that these screws and their 

spring washers are kept in a safe place during installation. 
 
On  completion  of  the  fitting  of  the  monitoring  component  the 
flameproof  joints  should  be  inspected  to  ensure  that  they  are 
clean and that they have not been damaged during installation. 
Also  check  that  the  earth  bonding  wire  between  the  two  
casting sections is secure and that the ‘O’ ring seal is in place. 
W hen  replacing  the terminal chamber  section  casting,  ensure 
that  it  is  square  with  the  flameproof  chamber  casting  before 
inserting.  Carefully  push the section  in  place  allowing  time for 
the  air  to  be  expelled.  Only  after  the  section  is  fully  in  place 
should the four M6 Stainless Steel A4-80 cover bolts and their 
spring washers be  inserted  and  tightened  down.  If  the  section 
jams  while  it  is  being  inserted,  carefully  remove  it  and  try 

again.  Never  use  the  M6  cover  bolts  to  force  the  cover  into 
position. 
 

 

9) 

Access  to  the  Increased  Safety  Terminal 
Chamber 

 

To  connect  the  cables  to  the  loudspeaker  it  is  necessary  to 
remove  the  terminal  cover  to  gain  access  to  the  termination 
chamber. To achieve this remove the four M4 hexagon socket 
head  screws  (see  figure  2).  The  four  M4  screws  and  their 

spring  washers  are  grade  A4  stainless  steel  and  they  should 
be kept in a safe place during installation. Before replacing the 
terminal cover ensure that the earth bonding wire between the 
two  castings  is  secure  and  that  the  ‘O’  ring  seal  is  in  place. 
Insert  the  four  M4  hexagon  screws  and  their  spring  washers 
and tighten them down.

 

 

10) 

  Power Amplifier Selection 

 

It  is  important  that  the  loudspeakers  are  connected  to power 
amplifiers  that  have  outputs  that  are  compatible  to  the  type of 
loudspeaker  being  used.  Loudspeakers  with  a  100V  line 
matching  transformer  fitted  must  be  connected  to  a  power 
amplifier with a 100V line output. Low impedance 8 ohm or 16 
ohm  loudspeakers  must  be  connected  to  amplifiers  with  a 
suitable low impedance output.  
 
 
 
 
 

Figure 1 

Flameproof  
Chamber

 

Terminal  
Cover

 

S/S Mounting 
Bracket

 

Figure 2 

Flameproof Chamber 
4 off M6 Cover Screws 
  

External Earth  
Terminal

 

Figure 3 

Internal Bonding 
Wire Terminal 

Increased Safety 
Chamber 
4 off M4 Cover Screws 
  

Terminal  
Chamber

 

1

2

3

4

5

6

7

8

9

1 0

11

12

2 off M20 
Cable Entries 

Internal Earth Terminal 

Plastic Acoustic Horn 
 