number  of  beacons on  the  line  and  the  length  of  the  cable 
runs.  The  cable  size  selected  must  have  the  necessary 

capacity  to  provide  the  input  current  to  all  of  the  beacons 
connected to the line.  

 
SAFETY  WARNING:  If  the  BExBG21D  beacon  is  used  at 

high  ambient  temperatures,  i.e.  over  +40ºC,  then  the  cable 
entry temperature may 70ºC and therefore suitable 
heat  resisting  cables  must  be  used,  with  a  rated  service 

temperature of at least 110ºC. 
 

 

10) 

Earthing

 

 

Both AC and DC beacon units must be connected to a good 

quality  earth.  The  units  are  provided  with  internal  and 
external  earthing  terminals  which  are  both  located  on  the 

terminal chamber section of the unit (see figures 2 and 3).  
 

When  using  the  internal  earth  terminal  ensure  that  the 
stainless steel M4 flat washer is between the incoming earth 
wire and the enclosure. 

 
When using the external earth terminal a cable crimp lug 

must be used.  The cable lug should be located between the 
two M5 stainless steel flat washers. The M5 stainless steel 

spring washer must be fixed between the outer flat washer 
and the M5 stainless steel nut to ensure that the cable lug is 
secured against loosening and twisting.  

 
The  internal  earth  bonding  wire  ensures  that  a  good quality 

earth is maintained between the flameproof chamber casting 
and the flameproof cover casting. 

 

 

 
 

 

11) 

Cable Glands

 

 

The  BExBG21D beacon  has dual  cable  gland entries  which 

have  an  M20  x1.5  entry  thread  as  standard.  Only  cable 
glands  approved  for  Ex  ‘d’  applications can  be  used,  which 

must  be suitable  for  the  type  of  cable  being  used  and  also 
meet  the  requirements  of  the  Ex  ‘d’  flameproof  installation 

standard EN60079-14:2008 / IEC60079-14:2007. 
 
When  only  one  cable  entry  is  used  the  other  one  must  be 

closed with an Ex ‘d’ flameproof blanking plug, which must be 
suitably approved for the installation requirements. 

 

For combustible dust applications, the cable entry device and 
blanking  elements  shall  be  in  type  of  explosion  protection 

increased  safety  "e"  or  flameproof  enclosure  "d"  and  shall 
have an IP 6X rating according to EN60529:1992 

 
SAFETY  WARNING:  If  the  BExBG21D  beacon  is  used  at 

high  ambient  temperatures,  i.e.  over  +40ºC,  then  the  cable 
entry temperature may 70ºC  
and  therefore  suitable  heat  resisting  cable  glands  must  be 

used, with a rated service temperature of at least 110ºC. 
 

 

12) 

 Cable Connections 

 

The cable connections are made into the terminal blocks on 

the  electronic  pcb  assembly  located  in  the  flameproof 
enclosure.  See  section  7  of  this  manual  for  access  to  the 

flameproof enclosure.  A four-way  terminal  block  is provided 
on the AC beacons, with feeds both boards, therefore there 

are two live terminals and two neutral terminals so that both 
input  and  output  wiring  can  be  terminated  if more  than  one 
beacon  is  being  wired  to  a  single  supply.  On  the  DC  units 

there  is  a  three-way  terminal  on  each of  the boards  making 
up the electronics assembly. The terminal blocks are wired in 

parallel  with  each  terminal  having  a  +ve  terminal  a  -ve 
terminal  and  an  S2  second  stage  terminal.  Therefore  both 

input  and  output  wiring  can  be  terminated  if more  than  one 
beacon is being wired to a single supply 
 

 
 

 

 
 

 
 

 

2 off M20  
Cable Entries 

Internal Earth Terminal 

Figure 3 

Internal Bonding 

Wire Terminal 

BExBG21D  Beacon Cover Internal View 

Figure 4 

  Supply 
Terminals 

BExBG21D DC  21 Joule Beacon 

Flash Pattern 
Pin Header 

BExBG21D AC   21 Joule Beacon 

Figure 5 

  Supply 
Terminals 

Flash Pattern 
Pin Header 

  Supply 
Terminals 

Содержание BExBG21D

Страница 1: ...AT RESISTING CABLES AND CABLE GLANDS Rated 110ºC AT AMB TEMPERATURES OVER 40ºC Year of Construction i e 10 1DB72000001 Serial No 3 Type Approval Standards The beacon has EC Type Examination and IECEx certificates issued by KEMA and has been approved to the following standards EN60079 0 2006 IEC60079 0 2004 Ed4 General Requirements EN60079 1 2007 IEC60079 1 2007 Ed6 Flameproof Enclosure d EN61241 0...

Страница 2: ...er To achieve this remove the four M6 hexagon socket head screws see figure 2 and withdraw the flameproof cover taking extreme care not to damage the flameproof joints in the process Note the four M6 screws are Class A4 80 stainless steel and only screws of this category can be used on these beacons It is therefore important that these screws and their spring washers are kept in a safe place durin...

Страница 3: ... approved for Ex d applications can be used which must be suitable for the type of cable being used and also meet the requirements of the Ex d flameproof installation standard EN60079 14 2008 IEC60079 14 2007 When only one cable entry is used the other one must be closed with an Ex d flameproof blanking plug which must be suitably approved for the installation requirements For combustible dust app...

Страница 4: ...three different flash patterns as listed below The flash patterns are set internally by the selection of pin headers On the DC beacons the flash pattern set can be changed externally to produce a second stage by connecting terminal S2 to ve supply line The AC beacons do not have a second stage DC Beacons Stage 2 Single Flash 1Hz Both tubes flashing together AF Alternate Flash 2Hz Tubes flashing al...

Отзывы: