European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH           [email protected]              Tel: +44 (0)208 743 8880 

                                                                                                                                                             www.e-2-s.com             Fax: +44 (0)208 740 4200 
Document No.  IS 2491-P       Issue C          18-03-10                   Sheet 4 of 4                                                                                                             (4)

 

Stage Headers Set for –ve Switching 

 

S2

S3

Stop

-ve

+ve

 

 

Stage Headers Set for +ve Switching

 

S2

S3

Stop

-ve

+ve

 

 

Stop Terminal

 

 
The  user  can  remotely  activate  and  deactivate  the 

BExH120D Hootronic DC sounder by switching a connection 
from  the  “Stop”  terminal  to  the  –ve  or  +ve  supply  lines, 

depending on which switching mode is being used +ve or –ve 
(see  above)  whilst  the  unit  is  powered.  To  achieve  the  “tail 

off” sound at switch off the unit must remain powered. 
 
 

AC Units Second and Third Stage Sound Selection 
 

To  select  the  second  and  third  stage  sounds  on  the 
BExH120D Hootronic AC sounder the Common (C) terminal 

on the four way terminal block on the pcb is connected to the 
S2 terminal for the second stage sound and the S3 terminal 

for the third stage sound. 
 

Stop Terminal

 

 
The  user  can  remotely  activate  and  deactivate  the 

BExH120D Hootronic AC sounder by switching a connection 
between the “Stop” terminal to the “C” terminal whilst the unit 

is  powered.  To  achieve  the “tail  off” sound  at  switch  off  the 
unit must remain powered. 

 

 

16) 

 Volume Control

 

 

The  BExH120D  Hootronic sounder  has  a  volume  control  to 
adjust  the  output  level.  To  set  the  required  output  level, 

adjust  the  potentiometer  on  the  pcb.  For  maximum  output 
level  the  potentiometer  should  be  set  to  the  fully  clockwise 

position. 
 
 

17) 

 End of Line Monitoring (DC Units)

 

 

On BExH120D Hootronic DC units, dc reverse line monitoring 
can  be  used  if  required.  The  DC  unit  has  a  blocking  diode 

fitted  in  their  supply  input  lines.  An  end  of  line  monitoring 
diode or an end of line monitoring resistor can be connected 

across the +ve and –ve terminals. If an end of line resistor is 
used it must have a minimum resistance value of 3k3 ohms 
and a minimum wattage of 0.5 watts or a minimum resistance 

value of 500 ohms and a min. wattage of 2 watts. 
 

 
 

 
 

 
 
 

 
 

 
 

 

Sound Selection Table 
 

Stage 

1

 

Discription 

Stage 

Stage 

Header 

 

Sound 1 

 

Industrial Hooter 

 

Sound 3 

 

Sound 5 

 

1 2 3

 

 

Sound 2 

 

High Frequency 

Mechanical Siren 

 

Sound 1 

 

Sound 5 

1 2 3

 

 

Sound 3 

 

Medium Frequency 

Mechanical Siren 

 

Sound 1 

 

Sound 5 

1 2 3

 

 

Sound 4 

 

Electro Mechanical 

Buzzer 

 

Sound 2 

 

Sound 5 

1 2 3

 

 

Sound 5 

 

 

Mechanical Bell 

 

Sound 1 

 

Sound 2 

1 2 3

 

 