E2S A100 Series Скачать руководство пользователя страница 4

 

 

 

 

E2S Warning Signals Impress House, Mansell Road, Acton, London W3 7QH    Sheet  4 of 5                                  e2s.com                          D218-00-001-IS Issue 4 10/06/2024  

2821 

S36282 

 

 

Approved Tones for EN54-3 Applications: 

 

•(Alternating Tone) 800/1000Hz @ 2Hz Alternating Tone 44 

•(Rising Tone) 500/1200Hz @ 0.26Hz (3.3s on, 0.5s off) Tone 8 

•(Fainting Tone) 1200/500Hz @ 1Hz Tone 2 

•(Continuous Tone) 800Hz Tone 21 

•(Pulsed Tone) 660Hz (150mS on, 150mS off) Tone 31 

•(Alternating Tone) 544Hz(100mS)/440Hz (400mS) Tone 5 

 

 

21 

Order Code: A100DC024 

Voltage Range: 18-60Vdc 

Nominal Voltage: 24Vdc / 48Vdc 

Max Current: 125mA @ 60Vdc  

DOP: DP-2821-CPR-0107 

UKCA Cert: 0843-CPR-1005 

EU Cert: 2821-CPR-0107 

A100DC024 @ 1m 

 

Horizontal Sound Output Max Voltage 

(60 Vdc) LAFmax,T dB(A) 

Horizontal Sound Output 

Min Voltage (18 Vdc) LAFmax,T dB(A) 

Angle 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 

31 

Tone 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 31 

Tone 5 

15° 

98 

99.9 

99 

95.7 

94.8 

95.4 

94.7 

96.8 

95.9 

93 

91.9 

92.7 

45° 

97.8 

100.1 

99 

97.6 

94.7 

96.6 

95 

97 

96 

94.8 

92.1 

94 

75° 

101.5 

102.9 

102.4 

101.4 

98.3 

100.4 

98.7 

100.2 

99.5 

98.8 

94.9 

97.9 

105° 

101.4 

102.8 

102.5 

101.4 

98.1 

100.4 

98.6 

100.2 

99.5 

98.8 

94.9 

97.9 

135° 

97.4 

100 

98.9 

97.2 

94.9 

96.4 

94.6 

96.9 

95.9 

94.5 

92.2 

93.8 

165° 

97.5 

99.6 

98.9 

95.8 

94.7 

95.4 

94.3 

96.4 

95.8 

93 

91.8 

92.8 

 

Vertical Sound Output Max Voltage 

(60 Vdc) LAFmax,T dB(A) 

Vertical Sound Output Min Voltage 

(18 Vdc) LAFmax,T dB(A) 

Angle 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 

31 

Tone 

Tone 

44 

Tone 

Tone 

Tone 

21 

Tone 31 

Tone 5 

15° 

96.3 

99.8 

99 

95.5 

94.1 

95.3 

93.1 

96.7 

96 

92.8 

91.2 

92.6 

45° 

97.6 

99.9 

98.8 

97.4 

94.5 

96.3 

94.8 

96.8 

95.7 

94.6 

91.9 

93.8 

75° 

101.3 

103 

102.5 

101.4 

98.1 

100.5 

98.5 

100.1 

99.5 

98.7 

95 

97.8 

105° 

101.3 

102.8 

102.4 

101.3 

98.2 

100.5 

98.5 

100.1 

99.5 

98.7 

95 

97.7 

135° 

97.4 

99.9 

98.8 

97.6 

94.5 

96.3 

94.6 

96.8 

95.8 

94.8 

91.9 

93.7 

165° 

96.7 

100 

99 

95.5 

93.9 

95.4 

93.6 

96.9 

96 

92.7 

91.1 

92.7 

Construction Product Regulation 

• 

A100DC024 is compliant to EN54-3:2001+A1+A2 

• 

Alarm devices – Sounder for use in fire detection and fire alarm systems installed in and 
around buildings  

• 

Type 3R / 13, IP66, Independently tested to EN60529:1991, (IP33C Compliant to EN54-3) 

• 

Type B Product, For Indoor & Outdoor use 

• 

Observe Precautions for handling electrostatic devices 

• 

-

25°C to +55°C compliant to EN54-3 

• 

Cable Glands must be suitably sealed and meet minimum IP33 for EN54-3 applications 

• 

Storage Temperature: -40°C to +70°C 

• 

Maintenance – None 

• 

Mounting - Units can be mounted using the 2-off ø6mm holes in the mounting lugs or 
through the back of the housing using the supplied gasket seal. 

21 

0843 

Содержание A100 Series

Страница 1: ...on einem Elektriker gem den neuesten Vorschriften und Bestimmungen durchgef hrt werden Attenzione L installazione deve essere eseguita da un elettricista in conformit con i codici e le normative pi re...

Страница 2: ...se Mansell Road Acton London W3 7QH Sheet 2 of 5 e2s com D218 00 001 IS Issue 4 10 06 2024 See D218 06 001 S2 S3 S2 S1 S2 S1 E E S3 S2 N L Default S2 Tone 1 Default S1 Tone 44 ON 1 OFF 0 AC DC See D22...

Страница 3: ...nals Impress House Mansell Road Acton London W3 7QH Sheet 3 of 5 e2s com D218 00 001 IS Issue 4 10 06 2024 INSTRUCTION SERVICE MANUAL A100 AlertAlarm Sounder 2x 1Nm 20mm 98 3 86in 60 3 2 37in 35 9 1 4...

Страница 4: ...5 92 2 93 8 165 97 5 99 6 98 9 95 8 94 7 95 4 94 3 96 4 95 8 93 91 8 92 8 Vertical Sound Output Max Voltage 60 Vdc LAFmax T dB A Vertical Sound Output Min Voltage 18 Vdc LAFmax T dB A Angle Tone 44 To...

Страница 5: ...08 which has been assessed and is considered suitable for use in low demand safety function 1 Random Hardware Failures and Systematic Failures and route 2H 2 As an unvoted item i e hardware fault tole...

Страница 6: ......

Страница 7: ...1 0 1 0 0 0 0 1 1 0 0 0 1 1 1 0 0 0 0 0 0 1 0 0 1 0 0 1 0 0 0 1 0 1 0 0 1 1 0 1 0 0 0 0 1 1 0 0 1 0 1 1 0 0 0 1 1 1 0 0 1 1 1 1 0 0 0 0 0 0 1 0 1 0 0 0 1 0 0 1 0 0 1 0 1 1 0 0 1 0 0 0 1 0 1 0 1 0 1 0...

Страница 8: ...A105N D105 DC SOUNDER WIRING DIAGRAMS INTRODUCTION NTS 1 1 OPTIONAL LINE MONITORING RESISTOR CUSTOMER SUPPLIED 14V MAX SYSTEM 120 MIN 2W MIN OR 1K MIN 0 5W MIN 28V MAX SYSTEM 470 MIN 2W MIN OR 2 4K M...

Страница 9: ......

Страница 10: ...Page left Intentionally blank...

Страница 11: ...Page left Intentionally blank...

Страница 12: ...Page left Intentionally blank...

Отзывы: