background image

INSTRUCTION MANUAL 

BExCBL2-L2D-P 
Combined Beacon/ Beacon

 

ATEx/IECEx & UKEx Gas & Dust

 

 

European Safety Systems Ltd.

   Impress House, Mansell Road, Acton, London W3 7QH

www.e2s.com

 

Tel: +44 (0)208 743 8880

Document No. D210-00-721-IS

 

Issue 5

 

12-09-2022

Sheet 1 of 6

 

 

BExCBGL2-L2D-P

 

1.  Product Table 

 

Unit Type Code 

Nominal 

Input 

Voltage 

Chamber 

Beacon 

Nominal 

Input Current

 

Cover Beacon 

Nominal 

Input Current

Max I/P Voltage  

BExCBGL2-L2DPDC024  

24Vdc 

240mA

240mA

28V 

BExCBGL2-L2DPAC115  

115Vac 

85mA

85mA

126V 

BExCBGL2-L2DPAC230  

230Vac 

48mA

48mA

253V 

The table shows the input current taken by the various units. 
Nominal current at nominal voltage. 
 
 
 
 
Table 1: Electrical Ratings. 

 
 

It is important that a suitable power supply is used to run the equipment. The power supply selected must have the necessary capacity 
to provide the input current to all of the units. 

 

The above table shows the input current taken by the various units and shows the maximum voltage at which they can be operated: 

 

The input current will vary according to the voltage input level and flash rates selected. 

 

2.  Warnings 

  

 

  DO NOT OPEN WHEN AN EXPLOSIVE ATMOSPHERE IS PRESENT 

  DO NOT OPEN WHEN ENERGIZED 

  POTENTIAL ELECTROSTATIC CHARGING HAZARD – CLEAN ONLY WITH A  DAMP CLOTH 

  COVER BOLTS CLASS A4-80 

  USE HEAT RESISTING CABLES AND CABLE GLANDS (RATED 110°C) AT AMB. TEMPERATURES OVER 

40°C 

 
 
 
 
 
 
 
 
 
 
 
 
 

Содержание 1-21-142

Страница 1: ...nt taken by the various units Nominal current at nominal voltage Table 1 Electrical Ratings It is important that a suitable power supply is used to run the equipment The power supply selected must hav...

Страница 2: ...cur in normal operation and if it does it will only exist for a short time Gas Groupings Group IIA Propane Group IIB Ethylene Group IIC Hydrogen Acetylene Temperature Classification for Gas Applicatio...

Страница 3: ...to ensure that the unit cannot move in service Fig 1 Fixing Location for Combined Beacon Beacon 7 Access to the Flameproof Enclosure To access the Ex d chamber remove the four M6 hexagon socket head...

Страница 4: ...using the internal earth terminal ensure that the stainless steel M4 flat washer is between the incoming earth wire and the enclosure Internal earthing connections should be made to the Internal Eart...

Страница 5: ...mum resistance value of 3k3 and a minimum power rating of 0 5 watts or a minimum resistance value of 500 and a minimum power rating of 2 watts The resistor must be connected directly across the ve and...

Страница 6: ...Repair Maintenance repair and overhaul of the equipment should only be carried out by suitably qualified personnel in accordance with the current relevant standards EN60079 19 IEC60079 19 Explosive at...

Страница 7: ...MIN MINIMUM VALUES R1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Fl...

Страница 8: ...TS 1 1 Single Stage Configuration Simultaneous Operation Config 1a Line Monitoring Stage 1 only Negative switching Stage 1 Flash Pattern Apply Power to Stage 1 ve Stage 1 ve Stage 2 Flash Pattern Appl...

Страница 9: ...ality Assurance Notification ModuleD SIRA 05 ATEX M342 Provisions fulfilledby theequipment II 2G Ex db IIB T6 to T4 Gb II 2D Ex tb IIIC T65 C to T130 CDb IP6X Dust Protectionto EN60079 0 EN60079 31 St...

Страница 10: ...r Date andPlace of Issue London 23 12 2020 EU Declaration of Conformity On behalf of European SafetySystems Ltd I declarethat on the date the equipment accompanied by this declaration is placed onthem...

Страница 11: ...Chester CH4 9JN UK Quality Assurance Notification Module D CSAE 22UKQAN0046 Provisions fulfilled by the equipment II 2G Ex db IIB T6 T4 Gb II 2D Ex tb IIIC T65 C T130 Db IP6X Dust Protection to EN6007...

Страница 12: ...and Place of Issue London 12 09 2022 UKCA Declaration of Conformity On behalf of European Safety Systems Ltd I declare that on the date the equipment accompanied by this declaration is placed on the m...

Отзывы: