User Manual ControlPlex

®

EM12D-TIO Intelligent Supply Module

Содержание ControlPlex EM12D-TIO

Страница 1: ...User Manual ControlPlex EM12D TIO Intelligent Supply Module...

Страница 2: ...e X81 12 5 Operating modes and signalling 13 5 1 Operating mode system start 13 5 2 Operating mode critical failure 13 5 3 Operating mode non critical failure 13 5 4 Operating mode independent operati...

Страница 3: ...ation data of the EM12D TIO intelligent supply module Index 200 31 9 2 2 Diagnostic information of the EM12D TIO intelligent supply module Index 300 32 9 2 3 Parameters of channel for 16 channels 33 9...

Страница 4: ...ostic messages dynamic info channel for 32 channels 47 9 3 6 1 Error memory for 32 channels 47 9 3 6 2 Reason for trip for 32 channels 48 9 3 6 3 Reason for trip for 32 channels 48 9 3 7 Action comman...

Страница 5: ...5...

Страница 6: ...Qualified personnel This user manual must exclusively be used by qualified personnel who are able based on their training and experience to realise arising problems when handling the product and to av...

Страница 7: ...for a reliable production process in this plant sector Part of the information is the permanent transmission of status indication regarding each channel of the individual circuit protector In additio...

Страница 8: ...ing display and analysis of the individual measuring values as well as diagnosis and control of the individual channels of the electronic circuit protectors This enables the user to have unrestricted...

Страница 9: ...ply voltage outside the indicated operating range can cause malfunctions or destruction of the device fig 2 EM12D TIO fig 3 Status indication and terminals EM12D TIO EM12D TIO xxx L C Q L X81 OV DC24V...

Страница 10: ...o IO link master 3 supply voltage IO link L 3 3 2 Connector socket for the IO link Master connector socket X81 This connector socket serves for connecting the EM12D TIO intelligent supply module with...

Страница 11: ...nal Push in PT 10 0 5 mm2 10 mm2 wire stripping length 18 mm IO link connection X81 COM 4 Mounting and installation 4 1 Mounting of the system The preferred mounting position of the EM12D TIO is horiz...

Страница 12: ...voltage both via the supply terminals LINE and 0 V and via X81 COM The voltages are decoupled reciprocally 4 2 2 Connection to EM12D TIO intelligent supply module X81 Use of the terminals for applica...

Страница 13: ...e is a connection between the EM12D TIO and the superordinate IO link master and there is no critical failure the operating mode independent operation will be quitted Should the connection between the...

Страница 14: ...k OFF channel ON by momentary switch and OFF by IO link orange OFF channel ON by momentary switch and IO link green ON selected threshold value exceeded blinking green orange ON overload detected oran...

Страница 15: ...ystem conditions After plugging in a circuit protector it will automatically be identified and parameterised if parameters are available for the slot in question During this procedure the cyclical dat...

Страница 16: ...REX12D Tx1 1 channel circuit protectors or REX12D Tx2 2 channel or even a combination of both 7 2 2 Models for the operation of 16 channels Up to 16 channels can be connected to the supply module This...

Страница 17: ...ion of the present load current 7 4 Software versions of EM12D In the context of functional or portfolio extensions the firmware used in the supply module is extended or adjusted Downward compatibilit...

Страница 18: ...bit 1 channel 2 bit 2 channel 3 bit 3 channel 4 bit 4 channel 5 bit 5 channel 6 bit 6 channel 7 bit 7 channel 8 bit 8 channel 9 bit 9 channel 10 bit10 channel 11 bit 11 channel 12 bit 12 channel 13 b...

Страница 19: ...LowByte Word 0xFFFF bit 0 channel 1 bit 1 channel 2 bit 2 channel 3 bit 3 channel 4 bit 4 channel 5 bit 5 channel 6 bit 6 channel 7 bit 7 channel 8 bit 8 channel 9 bit 9 channel 10 bit10 channel 11 bi...

Страница 20: ...tem width information Overall Status 26 byte 0xFF bit 0 low voltage bit 1 permanently ON for diagnostic purposes bit 2 EL Bus error from index I bit 3 reserve bit 4 reserve bit 5 reserve bit 6 reserve...

Страница 21: ...nel 11 bit 11 channel 12 bit 12 channel 13 bit 13 channel 14 bit 14 channel 15 bit 15 channel 16 switch channel ON OFF Channel 1 to 32 on off 2 HighByte 3 LowByte Word 0xFFFF bit 0 channel 1 bit 1 cha...

Страница 22: ...te Dword 0xFFFFFFFF bit 0 channel 1 bit 1 channel 2 bit 2 channel 3 bit 3 channel 4 bit 4 channel 5 bit 5 channel 6 bit 6 channel 7 bit 7 channel 8 bit 8 channel 9 bit 9 channel 10 bit10 channel 11 bi...

Страница 23: ...nnel 26 bit 26 channel 27 bit 27 channel 28 bit 28 channel 29 bit 29 channel 30 bit 30 channel 31 bit 31 channel 32 short circuit Channel Shortcircuit 8 HHByte 2 HByte 10 LByte 11 LLByte Dword 0xFFFFF...

Страница 24: ...channel 26 bit 26 channel 27 bit 27 channel 28 bit 28 channel 29 bit 29 channel 30 bit 30 channel 31 bit 31 channel 32 hardware lock Device Locked Off 16 HHByte 17 HByte 18 LByte 19 LLByte Dword 0xFF...

Страница 25: ...e Value 2512 100 25 12 Volt fig 15 Reading data with 32 channels parameters byte type range description acknowledge channel Channel 1 to 32 Reset 0 HHByte 1 HByte 2 LByte 3 LLByte Dword 0xFFFFFFFF bit...

Страница 26: ...bit 8 channel 9 bit 9 channel 10 bit10 channel 11 bit 11 channel 12 bit 12 channel 13 bit 13 channel 14 bit 14 channel 15 bit 15 channel 16 bit 16 channel 17 bit 17 channel 18 bit 18 channel 19 bit 1...

Страница 27: ...e per channel 501 516 1F5 204 1 16 3 R extended diagnostic information channel 601 616 259 268 1 16 1 W action commands channel 701 716 2BD 2CC 1 16 10 R ELBus device information 801 816 312 321 1 16...

Страница 28: ...no of the EM12D TIO intelligent supply module 9 1 2 3 Hardware version index 22 The string holds information on the hardware version of the EM12D TIO intelligent supply module 9 1 2 4 Software version...

Страница 29: ...ng process communication channel Please also see IOL Interface Spec 10002 Version 1 1 2 of 13 07 2013 9 1 2 9 Process Data Output The device supports reader access to the IO link Process Data Output I...

Страница 30: ...e bit means that the channel cannot be switched on or off via the control unit This means that voltage is applied to the output of the channel when the supply voltage is switched on provided the chann...

Страница 31: ...of the circuit protectors are switched off and the EM12D TIO changes into the operating mode Independent operation freeze 1 all load outputs channels of the circuit protectors remain in their current...

Страница 32: ...4 bit 3 bit 2 bit 1 bit 0 description 128 64 32 16 8 4 2 1 TN_SysNoConfig 0 1 TN_SysConfigMismatch 0 1 0 1 0 1 TN_SysQueueFull 0 1 0 1 0 1 TN_ELBusDown 0 1 byte 1 bit 15 bit 14 bit 13 bit 12 bit 11 b...

Страница 33: ...r 16 channels The parameter in byte 2 determines at how many percent of the rated current the channel will signal limit value exceeded This parameter allows read write transactions value range 50 100...

Страница 34: ...he safe range 1 0 0 1 0 0 1 1 reserve 1 0 0 1 0 1 0 0 device tripped a reset command has to be sent 1 0 0 1 0 1 0 1 no error 0 0 0 0 0 0 0 0 circuit protector is not parameter ised 1 0 0 1 0 1 1 1 int...

Страница 35: ...lds the internal error memory of the circuit protector value range 0 255 data length 1 byte unsigned character fig 26 Load voltage channel fig 27 Diagnosis channel error memory byte 1 LOW bit 7 bit 6...

Страница 36: ...yte 2 bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 description 128 64 32 16 8 4 2 1 value 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 byte 3 bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 description 128 64 3...

Страница 37: ...1 word unsigned integer fig 31 Device information channel circuit breaker p n fig 32 Device information channel hardware version byte 9 bit 7 bit 6 bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 description 128...

Страница 38: ...bit 5 bit 4 bit 3 bit 2 bit 1 bit 0 description 128 64 32 16 8 4 2 1 value 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 byte 6 HIGH bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8 description 32768 16384 819...

Страница 39: ...ne decimal place for simplification it is shown identically with the voltage with 2 decimal places Example measuring value operating voltage 710 real measuring value 7 10 Ampere byte 4 HIGH bit 27 bit...

Страница 40: ...ge 2512 real measuring value 25 12 Volt The maximum voltage is made available as a standardised 16 bit value with a resolution of 10 mV Example measuring value operating voltage 2512 real measuring va...

Страница 41: ...ata model for 32 channels 9 3 1 Configuration data of the EM12D TIO intelligent supply module 9 3 1 1 Internal cycle time index 198 2 When reading index 198 one byte is returned The internal cycle tim...

Страница 42: ...nnel 13 0 1 PLCLock channel 14 0 1 PLCLock channel 15 0 1 PLCLock channel 16 0 1 1 available from revision D Setting the bit means that the channel cannot be switched on or off via the control unit Th...

Страница 43: ...s of the circuit protectors are switched off and the EM12D TIO changes into the operating mode Independent operation freeze 1 all load outputs channels of the circuit protectors remain in their curren...

Страница 44: ...4 bit 3 bit 2 bit 1 bit 0 description 128 64 32 16 8 4 2 1 TN_SysNoConfig 0 1 TN_SysConfigMismatch 0 1 0 1 0 1 TN_SysQueueFull 0 1 0 1 0 1 TN_ELBusDown 0 1 byte 1 bit 15 bit 14 bit 13 bit 12 bit 11 b...

Страница 45: ...r 32 channels The parameter in byte 2 determines at how many percent of the rated current the channel will signal limit value exceeded This parameter allows read write transactions value range 50 100...

Страница 46: ...the safe range 1 0 0 1 0 0 1 1 reserve 1 0 0 1 0 1 0 0 device tripped a reset command has to be sent 1 0 0 1 0 1 0 1 no error 0 0 0 0 0 0 0 0 circuit protector is not parameterised 1 0 0 1 0 1 1 1 int...

Страница 47: ...description 128 64 32 16 8 4 2 1 value 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 byte 2 HIGH bit 15 bit 14 bit 13 bit 12 bit 11 bit 10 bit 9 bit 8 description 32768 16384 8192 4096 2048 1024 512 256 value 0 1...

Страница 48: ...reason for trip available 0 0 0 0 0 0 0 0 0 short circuit 1 0 0 0 0 0 0 0 1 overload 2 0 0 0 0 0 0 1 0 internal failure 4 0 0 0 0 0 1 0 0 fig 50 Diagnosis channel trip counter fig 51 Diagnosis channe...

Страница 49: ...value statistics 119 1 0 1 1 1 0 1 1 1 fig 52 Action commands channel 1 available from revision D 9 3 8 Device information channel for 32 channels When reading the index 701 732 ten bytes each are re...

Страница 50: ...it 10 bit 9 bit 8 description 32768 16384 8192 4096 2048 1024 512 256 value 0 1 0 0 0 0 1 0 1 0 1 0 1 fig 55 Device information channel Software version 1 available from revision D 9 3 8 2 Hardware ve...

Страница 51: ...24 512 256 value 0 1 0 1 0 1 0 1 byte 2 bit 15 bit 14 bit 13 bit 12 description 32768 16384 8192 4096 value 0 1 0 1 0 1 0 1 byte 3 bit 19 bit 18 bit 17 bit 16 description 524288 262144 131072 65536 va...

Страница 52: ...0 real measuring value 7 10 Ampere The maximum current is made available as standardised 16 bit value with a resolution of 10 mA resolution of the channel is one decimal place for simplification it is...

Страница 53: ...unsigned integer The minimum voltage is made available as a standardised 16 bit value with a resolution of 10 mV Example measuring value operating voltage 2512 real measuring value 25 12 Volt byte 7...

Страница 54: ...48 1024 512 256 value 0 1 0 1 0 1 0 1 0 1 0 1 0 1 0 1 fig 62 Mean value voltage channel 1 available from revision D 9 3 9 5 Maximum voltage for 32 channels 1 Byte 3 byte 4 contain the highest measured...

Страница 55: ...55...

Страница 56: ...Fig 24 Device parameters channel limit value load current 33 Fig 25 Diagnostic information channel 34 Fig 26 Load voltage channel 35 Fig 27 Diagnosis channel error memory 35 Fig 28 Diagnosis channel t...

Страница 57: ...53 Device information channel type 49 Fig 54 Device information channel hardware version 50 Fig 55 Device information channel software version 50 Fig 56 Device information channel Serial number 51 Fi...

Страница 58: ...58 Notes...

Страница 59: ...59 Notes...

Страница 60: ...GERMANY Phone 49 9187 10 0 Fax 49 9187 10 397 E mail info e t a de www e t a de Bedienungsanleitung Instruction manual B_EM12D TIO_REX12D_020620 Bestell Nr Ref number Y 312 28701 Index e Issue 06 202...