User Manual MOP301 Digital Moisture in Oil Immersion Probe

8  Technical Data

Measurands

 

Water activity (aw) / Water content (x)

 

Measuring range 

 

0...1 aw 

 

 

 

0...100 000 ppm; actual range depends on the oil type, for non- 

 

 

 

mineral transformer oil, specific solubility parameters are needed 

  

 

(ppm output is valid in the range 0...100 °C

 (32...212 °F)

)

 

Response time t

90

, typ. 

 

10 min. in still oil 

 

@ 20 °C (68 °F)

 

Accuracy

1)

 

 

Including hysteresis, non-linearity and repeatability

 

 

0...40 °C 

(32...104 °F) 

(0...0.9 aw) 

±0.02 aw 

  

(0.9...1 aw)

 

±0.025 aw 

 

-40...120 °C 

(-40...356 °F)

  (0...1 aw) 

±0.03 aw

 

Resolution 

 

0.0001 aw

 

Temperature (T)

 

Measuring range 

 

-40...120 °C 

(-40...248 °F)

 

Accuracy

1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Resolution  

 

0.01 °C

Output

 

Digital interface  

 

RS485 (MOP301 = 1 unit load) 

 

Protocol 

 

Modbus RTU 

 Factory settings 

 

9 600 Baud, parity even, 1 stop bit, Modbus address 70 

 

Supported baud rates 

 

9 600, 19 200, 38 400, 57 600, 76 800 and 115 200 

 

Data types for measured values   

FLOAT32 and INT16 registers

General

 

Power supply class III 

 (EU) / class 2 (NA) 

8 - 35 V DC

2)

 

Power consumption, typ. 

 

40 mW (without termination resistor)

 

Electrical connection

  

M12x1, 4 poles

 

Protection rating  

 

IP66 / NEMA 4X

 

Pressure rating 

 

20 bar 

(290 psi)

 

Probe material 

 

Stainless steel 1.4404

 

Cable jacket

3)

 

 

HFS 125XL, black, oil and fuel resistant

 

Temperature working range 

 

Sensing e filter cap: -40...125 °C 

(-40...257 °F)

 

 

 

 

Probe: -40...120 °C 

(-40...248 °F)

 

 

 

 

Cable: -40...120 °C 

(-40...248 °F)

 

 

 

 

M12 connector: -25...90 °C 

(-13...194 °F)

 

Storage conditions 

 

-40...80 °C 

(-40...176 °F)

 

 

 

 

0...95 %RH, non-condensing

 

Electromagnetic compatibility 

 

EN 61326-1  EN 61326-2-3 

ICES-003 ClassA 

   

 

 

 

Industrial Environment  FCC Part15 ClassA

 

Shock and vibration 

 

Tested acc. to EN 60068-2-6 and EN 60068-2-27

 

Configuration and adjustment 

 

PCS10 Product Configuration Software (free download) and 

 

 

 

configuration adapter

 

1) Valid in fluids. 

 

  Traceable to international standards, administrated by NIST, PTB, BEV...  

 

  The accuracy statement includes the uncertainty of the factory calibration with an enhancement factor k=2 (2-times standard deviation). The accuracy  

 

  was calculated in accordance with EA-4/02 and with regard to GUM (Guide to the Expression of Uncertainty in Measurement). 

 

2) USA & Canada class 2 supply required, max. supply voltage 30 V DC.

 

3) Please mind the mounting and installing instructions included in the user manual.

-40 -20

0

20 40 60 80 100 120 140 160 180

0

0.1

0.2

0.3

0.4

0.5

0.6

T [°C]

T [°C]

40 20

0

40

20

80

60

120

100

0.15

0.45

0.1

0.2

0.3

0.4

0.5

0

∆T [°C]

T [°C]

∆T [°C]

T [°C]

Содержание Modbus MOP301

Страница 1: ...BA_MOP301 v1 0 Modification rights reserved User Manual MOP301 Digital Moisture in Oil Immersion Probe up to 120 C 248 F ...

Страница 2: ... equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmful interference when the equipment is operated in a commercial environment This equipment generates uses and can radiate radio frequency energy and if not installed and used in accordance with the in...

Страница 3: ... 1 Installation of the Probe Directly in the Process 8 4 2 Probe Installation with Ball Valve 9 4 3 Sampling Cell with Shut off Function 10 5 Setup and Adjustment 11 5 1 PCS10 Product Configuration Software 11 5 2 Modbus Setup 12 5 3 Modbus Register Map 13 5 4 Freely Configurable Custom Modbus Map 13 5 5 Device Status Indication 14 5 6 Modbus RTU Examples 15 6 Maintenance and Service 17 6 1 Cleani...

Страница 4: ...r to reach optimal performance of the device 1 2 Safety Instructions 1 2 1 General Safety Instructions Avoid any unnecessary mechanical stress and inappropriate use When replacing the filter cap make sure not to touch the sensing elements The device must be operated with the filter cap on at all times For sensor cleaning and filter cap replacement please see Cleaning Instructions at www epluse com...

Страница 5: ...understood this user manual and must follow the instructions contained within All process and electrical connections shall be thoroughly checked by authorized staff before putting the device into operation Do not install or start up a device supposed to be faulty Make sure that such devices are not accidentally used by marking them clearly as faulty A faulty device may only be investigated and pos...

Страница 6: ...il The MOP301 is typically deployed in monitoring of lubrication hydraulic and insulation oils as well as diesel fuel in equipment and machinery The oil to be monitored may be mineral synthetic or biodegradable Installation is simplified by various mounting options which are supported by E E accessories The MOP301 provides the measured data at its digital RS485 interface via Modbus RTU protocol Th...

Страница 7: ...10 pressure tight up to 20 bar 290 psi 3 3 Electrical Connection Important note The manufacturer cannot be held responsible for personal injuries or damage to property as a result of incorrect handling installation wiring power supply and maintenance of the device The relations of electrical potential between a bus system and an MOP301 probe are characterized by the following properties The bus co...

Страница 8: ...at precautions are taken to prevent the sensor from shooting out The internal ducting to the electronics is suitable for up to 20 bar 290 psi The respective feedthrough determines the actual working pressure 20 bar 290 psi As a rule non cross section constricting and cross section constricting cut in screw connections may be used cross section constricting screw connections are only permitted in t...

Страница 9: ... The temperature during probe installation may deviate by max 40 C 72 F from the regular temperature during normal operation Probe installation steps see Fig 6 Install the probe into the ball valve while the ball valve is closed Open the ball valve Slide the probe through the ball valve to the desired immersion depth Depending on the process pressure additional tools may be necessary for pushing t...

Страница 10: ...on works like the method described in chapter 4 1 Installation of the Probe Directly in the Process however without the need of stop valves in the upstream and downstream of the measurement point Technical data of the sampling cell1 Pipe thread Rp Whitworth thread according to EN 10226 old DIN 2999 Senor port thread G 1 2 ISO Operating pressure 40 bar at max 80 C 580 psi at max 176 F Temperature r...

Страница 11: ...hapter 5 1 below 5 1 PCS10 Product Configuration Software The PCS10 provides a convenient graphical user interface to the MOP301 To use the software for performing adjustments and changes in settings please proceed as follows 1 Download the PCS10 Product Configuration Software from www epluse com pcs10 and install it on the PC 2 Connect the MOP301 to the PC using the Modbus configuration adapter 3...

Страница 12: ...its can be set via 1 PCS10 Product Configuration Software and the Modbus configuration adapter HA011018 The PCS10 can be downloaded free of charge from www epluse com pcs10 2 Modbus protocol in the register 1 0x00 and 2 0x01 See Application Note Modbus AN0103 available at www epluse com mop301 The serial number as ASCII code is located in read only registers 1 8 0x00 0x07 16 bits per address The f...

Страница 13: ...and B 1663 30005 and 7 3705 decimal 46 10 00 64 00 04 08 E9 9A C4 CF DB 23 40 EB CA 19 If two parameters are to be uploaded it is recommended to write them with a single command Tab 5 MOP301 FLOAT32 measured data registers INT16 read register Parameter Unit Scale3 Register number1 Dec Register address2 Hex Read register function code 0x03 0x04 Water activity aw 1000 4068 0xFE3 Water content x ppm ...

Страница 14: ...t to NaN according to IEEE754 for data type FLOAT32 or to 0x8000 INT16 It is possible to read out all status and error information via Modbus register 602 0x259 Errors are displayed in bit coded form If an event is present the corresponding bit is set to 1 Measured values outside the measureing range are limited with the corresponding limit value Error Bits Description Recommended action Bit 0 Err...

Страница 15: ...E754 refer to the example at the end of this chapter Read register from custom modbus map address 0x0BB8 0x0BB9 unconfigured Request Hex Modbus address Function code Starting address Hi Starting address Lo Qty of registers Hi Qty of registers Lo CRC 46 03 0B B8 00 02 49 7D Response Hex Modbus address Function code Byte count Register 1 value Hi Register 1 value Lo Register 2 value Hi Register 2 va...

Страница 16: ...de Byte count Register 1 value Hi Register 1 value Lo Register 2 value Hi Register 2 value Lo Register 3 value Hi 46 03 0C 0B C9 41 DB BD Register 3 value Lo Register 4 value Hi Register 4 value Lo Register 5 value HI Register 5 value Lo Register 6 value Hi Register 6 value Lo CRC 7B 3E AD FF FF FF FF B7 9A Decoding of floating point values Floating point values are stored according IEEE754 The by...

Страница 17: ...he accuracy of a measurement device The device under test specimen is compared with the reference and the deviations are documented in a calibration certificate During the calibration the specimen is not changed or improved in any way Adjustment improves the measurement accuracy of a device The specimen is compared with the reference and brought in line with it An adjustment can be followed by a c...

Страница 18: ...PCS10 Modbus configuration adapter HA011018 Stainless steel filter cap for flow 1 m s HA010110 Stainless steel filter cap for flow 1 m s HA010111 Protection cap for M12 socket HA010781 Protection cap for M12 plug HA010782 T wcoupler M12 M12 HA030204 Ball valve G 1 2 ISO HA050101 Ball valve 1 2 NPT HA050104 Sampling cell with shut off function PN40 DN25 HA050109 ...

Страница 19: ...n rating IP66 NEMA 4X Pressure rating 20 bar 290 psi Probe material Stainless steel 1 4404 Cable jacket3 HFS 125XL black oil and fuel resistant Temperature working range Sensing element filter cap 40 125 C 40 257 F Probe 40 120 C 40 248 F Cable 40 120 C 40 248 F M12 connector 25 90 C 13 194 F Storage conditions 40 80 C 40 176 F 0 95 RH non condensing Electromagnetic compatibility EN 61326 1 EN 613...

Страница 20: ...epluse fr E E Elektronik Germany Obere Zeil 2 61440 Oberursel Tel 49 6171 69411 0 E mail info epluse de E E Elektronik India 801 Sakhi Vihar Road 400072 Mumbai Tel 91 990 440 5400 E mail info in epluse com E E Elektronik Italy Via Alghero 17 19 20128 Milano MI Tel 39 02 2707 86 36 E mail info epluse it E E Elektronik Korea Suite 2001 Heungdeok IT Valley Towerdong 13 Heungdeok 1 ro Giheung gu 16954...

Отзывы: