Humidity and Temperature Sensor for High Humidity and Chemically Polluted Conditions | 19
WARNING
The metal enclosure must be grounded during operation. National regulations for installation must be observed!
Switch Load
Max. switch load
250.V.AC./.6.A
28.V.DC./.6.A
Min. switch load
12.V./.100.mA
Tab. 1
Maximum and minimum switch loads
WARNING
No overcurrent and short circuit protection. Both relays shall be connected to either high oder low voltage.
3.5.5.
Integrated Power Supply 100 - 240 V AC (Option AM3)
This.module.allows.the.HTS801.to.be.powered.with.100.-.240.V.AC.(50/60.Hz),.2.VA.
Polycarbonate enclosure
Stainless steel enclosure
Fig. 21 Power supply module (option AM3)
WARNING
The AM3 option includes a 1.25 A fuse on the 100 - 240 V side. This fuse must not be replaced by the user,
only by the E+E after sales service.
The protection of the supply cable against excess current and short-circuit must be designated to a wire
cross section of 0.8 mm
2
(AWG 18) (6 A fuse).
The metal enclosure must be grounded during operation.
All national regulations for installation shall be observed!