User Manual EE850 Duct Sensor

3.5.4  Modbus Setup

Item

Factory settings

Selectable values (via EE-PCS)

Baud rate

9 600

9 600, 19 200, 38 400, 57 600, 76 800, 115 200

Data bits

8

8

Parity

Even

None, odd, even

Stop bits

1

1, 2

Slave address

67

1...247

Tab. 1 

Digital interface default settings

The recommended settings for multiple devices in a Modbus RTU network are 9600, 8, even, 1.

The EE850 represents 1/10 unit load on an RS485 network.

Device address, baud rate, parity and stop bits can be set via:

1.  EE-PCS Product Configuration Software and the Modbus configuration adapter HA011066. 

The EE-PCS can be downloaded free of charge from 

www.epluse.com/configurator

2.  Modbus protocol in the register 60001 (0x00) and 60002 (0x01).  

See Modbus Application Note AN0103 (available on 

www.epluse.com/EE850

)

The serial number as ASCII code is located in the register addresses 0x00...0x07 (16 bits per address).

The firmware version is located in the register address 0x08 (bits 15...8 = major release; bits 7...0 = 

minor release). The beforementioned registers can be read out with function code 0x03 or 0x04.

The measured data is saved as 32 bit floating point values (data type FLOAT) and as 16 bit signed 

integer values (data type INTEGER).

FLOAT 32 bit

Parameter

Unit

Register number

1)

 [DEC]

Register address

2)

 [HEX]

Read register: function code 0x03 

Temperature T

° C

1003

0x3EA

° F

1005

0x3EC

Relative Humidity

%

1021

0x3FC

CO

2

 (average)

ppm

1061

0x424

CO

2

 (raw)

ppm

1063

0x426

Water vapour partial pressure

mbar

1101

0x44C

psi

1103

0x44E

Dew point temperature

°C

1105

0x450

°F

1107

0x452

Absolute humidity

g/m

3

1113

0x458

gr/ft

3

1115

0x45A

Mixing ratio

g/kg

1121

0x460

gr/lb

1123

0x462

Specific enthalpy

kJ/kg

1125

0x464

ft lb/lb

1127

0x466

BTU/lb

1129

0x468

Frost point temperature

°C

1131

0x46A

°F

1133

0x46C

1) Register number starts from 1

2) Register address starts from 0

Содержание EE850

Страница 1: ...BA_EE850 v1 5 Modification rights reserved User Manual EE850 Duct Sensor for CO2 Humidity and Temperature...

Страница 2: ...equipment has been tested and found to comply with the limits for a Class A digital device pursuant to part 15 of the FCC Rules These limits are designed to provide reasonable protection against harmf...

Страница 3: ...3 Installation Start up and Operation 5 1 3 Environmental Aspects 5 2 Scope of Supply 5 3 Product Description 6 3 1 General 6 3 2 Installation 6 3 3 Electrical Connection 7 3 4 Setup and Adjustment 7...

Страница 4: ...ructions 1 2 1 General Safety Instructions Avoid any unnecessary mechanical stress and inappropriate use The device shall not be exposed to extreme thermal stress Installation electrical connection ma...

Страница 5: ...into operation and maintenance may be performed by qualified personnel only Such staff must be authorized by the operator of the facility to carry out the mentioned activities The qualified staff mus...

Страница 6: ...n the EE850 cover Depending on the EE850 version the response time specified is only valid for direction marked with the blue arrow with respect to the cable gland position Air flow in the opposite di...

Страница 7: ...are EE PCS One can change the CO2 output signal the scaling of the outputs and perform CO2 RH and T adjustment calibration Please note The EE850 may not be connected to any additional power supply whe...

Страница 8: ...e scaling of the output can be changed by using USB Configuration Adapter HA011066 and Product Configuration Software EE PCS Example The initial scaling of the outputs is The output scale after the ch...

Страница 9: ...address has to be set via PCS Modbus Slave device factory setting EE850 67 permitted values 1 247 BACnet Master device factory setting EE850 67 permitted values 0 127 Example Slave address is set via...

Страница 10: ...code is located in the register addresses 0x00 0x07 16 bits per address The firmware version is located in the register address 0x08 bits 15 8 major release bits 7 0 minor release The beforementioned...

Страница 11: ...Slave ID Modbus address 3 1 0x00 Modbus protocol settings4 2 0x01 1 Register number starts from 1 2 Protocol address starts from 0 3 If the ID is set via DIP switch the response will be NAK 4 For Modb...

Страница 12: ...re Working range 20 60 C 4 140 F Accuracy at 20 C 68 F 0 3 C 0 54 F Response time t63 50 s Relative Humidity Working range 0 95 RH Accuracy at 20 C 68 F 3 RH 20 80 RH Response time t63 10 s Outputs An...

Страница 13: ...lin 69130 Ecully Tel 33 4 74 72 35 82 E mail info epluse fr E E Elektronik Germany Sch ne Aussicht 8 C 61348 Bad Homburg Tel 49 6172 13881 0 E mail info epluse de E E Elektronik Italy Via Alghero 17 1...

Отзывы: