DIMENSIONS MM (INCH)

MOUNTING

DRILLING IN THE WALL OF THE DUCT FOR INSTALLING THE MOUNTING FLANGE

Air flow

>16 

(0.63")

60 

(2.4")

The arrow engraved on the sensing head of EE660 indicates the direction of the air stream during factory adjustment. When  

installing the EE660 probe, make sure that the arrow matches exactly the flow direction.

Air flow

CORRECT

INCORRECT

The mounting flange allows for precise setting of the EE660 immersion depth in a duct. The entire sensing head must be in the air 

flow to be measured.

6 (0.24)

60 (2.36)

Ø > 16 (0.63)

80.6 (3.17)

19

(0.75)

101 (3.98)

155 (6.1)

15

(0.59)

155 (6.1)

46 

(1.81)

Cable gland 

M16x1.5

FOR CONDUIT

INSTALLATION

Cable gland 

M16x1.5

90 (3.54)

~105 or 205 

(~4.13 or 8.07)

Ø > 13 (0.51)

GASKET

15 

(0.59)

Type T2

duct mount

mounting flange

Type T3

remote probe

Immersion depth = 30 % - 50 % 

of the duct diameter

duct diameter

CORRECT

INCORRECT

Air flow

Содержание EE660

Страница 1: ...probe and mainly onto the sensing head Observe the humidity working range 5 95 RH non condensing Avoid installation in corrosive environment as this may lead to sensor destruction CONNECTING DIAGRAM A...

Страница 2: ...ply voltage within the specified range see technical data at any time and at all devices in the bus This is particularly relevant when using long and thin cables which can cause high voltage drop plea...

Страница 3: ...ter number starts from 0 3 For Modbus protocol setting please see Application Note Modbus www epluse com MODBUS RTU EXAMPLE Example of MODBUS RTU command for reading the temperature float value T 26 6...

Страница 4: ...typ 1 sec at constant temperature Output Analogue 0 10 V and 4 20 mA 0 1 m s 0 1 5 m s 0 2 m s 1 1 mA IL 1 mA RL 450 linear 3 wires Digital interface RS485 with max 32 devices on one bus Protocol Modb...

Страница 5: ...ction Air flow CORRECT INCORRECT The mounting flange allows for precise setting of the EE660 immersion depth in a duct The entire sensing head must be in the air flow to be measured 6 0 24 60 2 36 16...

Страница 6: ...h flow rate Positioning the probe at a location with a laminar to turbulent flow Turbulent flows are caused by pipe bends branches behind flaps flans air heaters air coolers or cross sectional changes...

Страница 7: ...ted in later versions The described products can be improved and changed at any time without prior notice Copyright E E Elektronik Ges m b H All rights reserved EMC note USA FCC This equipment has bee...

Отзывы: