WARNING
The metal enclosure must be grounded during operation. National regulations for installation must be observed!
Switch Load
Max. switch load
250 V AC / 6 A
28 V DC / 6 A
Min. switch load
12 V / 100 mA
Tab. 4
Max. and min. switch loads
WARNING
No overcurrent and short circuit protection. Both relays shall be connected to either high or low voltage.
PLEASE NOTE
When error indication mode is selected, various errors will trigger the alarm output. An alarm output in this
operation mode is used for error indication only.
5.2 Integrated Power Supply 100 - 240 V AC (Option AM3)
This module allows the EE360 to be powered with 100 - 240 V AC (50/60 Hz), 2 VA.
Enclosure
Polycarbonate
Stainless steel
Fig. 14 Power supply module (option AM3)
Pin assignment of the plug connection (see chapter 4.2.1 Electrical Connection and Wiring)
WARNING
The AM3 option includes a 1.25 A fuse on the 100 - 240 V side. This fuse may not be replaced by the user,
only by the E+E after sales service.
The protection of the supply cable against excess current and short-circuit must be designated to a wire
cross section of 0.8 mm2 (AWG 18) (6A fuse).
The metal enclosure must be grounded during operation.
All national regulations for installation shall be observed!