tECHniCAL dAtA
(Modification rights reserved)
InformatIon
+43 7235 605 0 / [email protected]
Langwiesen 7 • A-4209 Engerwitzdorf
Tel: +43 7235 605-0 • Fax: +43 7235 605-8
[email protected] • www.epluse.com
LG Linz Fn 165761 t • UID-Nr. ATU44043101
Place of Jurisdiction: A-4020 Linz • DVR0962759
BA_EE150_e // v1.0 // Technische Änderungen vorbehalten
The EE150 is ready to use and does not require any configuration by the user. The factory setup of EE150 corresponds to the type num-
ber ordered. For ordering guide please see data sheet at
www.epluse.com/EE150
.
If needed, the user can change the factory setup by using the optional
E+E Product Configuration
Adapter (EE-PCA) and the E+E
Product Configuration Software (EE-PCS). With these
one can set the output scaling, and perform one or two point adjustment for
humidity and temperature.
For product data sheet EE-PCA please see
www.epluse.com
.
The E+E Product Configuration Software (EE-PCS) is free and can be downloaded from
www.epluse.com/configurator
.
SEtUP And AdJUStmEnt
USA
FCC notice:
This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are
designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate ra-
dio frequency energy and, if not installed and used in accordance with the installation manual, may cause harmful interference to radio communications.
However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or
television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or
more of the following measures:
-
Reorient or relocate the receiving antenna.
-
Increase the separation between the equipment and receiver.
-
Connect the equipment into an outlet on a circuit different from that to which thereceiver is connected.
-
Consult the dealer or an experienced radio/TV technician for help.
CANADIAN
ICES-003 Issue 5:
CAN ICES-3 B / NMB-3 B
Measured values
Relative Humidity
Working range
10...90% RH
Accuracy at 20°C
±3% RH (30...70%RH), otherwise ±5% RH
Temperature dependency
typ. ±0.05% RH/°C
Temperature
Working range
-5...55°C
(23...131°F)
T-Accuracy at 20°C
±0.3°C
Outputs
Analog output
0-10 V
R
L
≥ 10k Ohm
(0...100% RH; T: see ordering guide)
4-20 mA (2-wire)
R
L
≤ 500 Ohm
Passive T-sensor
2-wire
see ordering guide
Wires resistance (terminal - sensor)
typ. 0.5 Ohm
General
Power supply (Class III)
for 0 - 10 V
15 - 35V DC or 24V AC ±20%
for 4 - 20 mA
10V + R
L
x 20 mA < U
V
< 35V DC
Current consumption
with DC power supply typ. 5mA
with AC power supply typ. 13mA
eff
Connection
Screw terminals, max. 1.5 mm
2
Housing material
Polycarbonate, UL94V-0 approved
Protection class
IP65/NEMA 4
Cable gland
M16 x 1.5
Sensor protection
PTFE filter, non-removable
Electromagnetic compatibility
EN61326-1 EN61326-2-3 Industrial environment
FCC Part 15 Class B ICES-003 Issue 5 Class B
Working conditions
-5...55°C
(23...131°F)
0...95% RH (non-condensing)
Storage conditions
-25...60°C
(-13...140°F)
20...80% RH