AR402 Administration
11
2.7 Power
Supply
•
DC Voltage, 12...24V
Minimum 1A and complying with Limited Power Source
according to IEC/EN 60950-1
•
Power consumption max 5W
•
CSA or UL listing is recommended
2.8 Environment
Conditions
•
Temperature range 14° to 122º F
•
Indoor and Outdoor
•
Protection class IP65
2.9
Dimensions and Weight
•
4,5 in x 2,5 in x 2 in (H x W x D)
•
Approx. 0.4 lb
2.10 Cable Specifications
•
RS485
Shielded twisted pair cable (4000 feet max)
Examples:
1. 2x2 strands litz wire AWG24 (0.4 kcmil)
2. J-Y(ST)Y 2x2x0,6
3. CAT 5 ... 7 STP (Shielded Twisted Pair)
•
Wiegand
Non-twisted shielded cable (500 feet max)
Examples:
1. 10 pair shielded wire AWG22 (0.64 kcmil)
For shorter distances or using higher supply voltage:
2. 8 pair AWG24 (0.4 kcmil)