PowerRack HV4 User Manual
18
3.2.3 Electrical installation
Before connecting the power cables, use multimeter to measure cable continuity,
short circuit, confirm positive and negative, and accurately mark the cable labels.
Measuring methods
:
Power cable check: select the buzzer mode of multimeter and detect the both
ends of the same color cable. If the buzzer calls, it means the cable is in good
condition
.
Short circuit judgment: choose multimeter resistor file, probe the same end of
positive and negative pole, if the resistor shows infinity, means that the cable
is available.
After visual testing of power line connection, the positive and negative poles of
the battery shall be connected respectively to the positive and negative poles
of the opposite terminal
.
It is better to add a circuit breaker between the inverter and the battery system.
Figure3-6
Power cable-
negative
Power cable-
positive
Module cable-
negative
Module cable-
positive
Communication
cable-to inverter
Communication
parallel cable
Inverter
Serial cable
Circuit
breaker