B4850 ESS Unit User Manual
12
3.1.1 Environmental requirements
Working temperature: -20
℃
~ +55
℃
•
Charging temperature range is 0
℃
~+55
℃
,
•
Discharging temperature range is -20
℃
~+55
℃
Storage temperature: -10
℃
~ +35
℃
Relative humidity: 5% ~ 85%RH
Elevation: no more than 4000m
Operating environment: Indoor installation, sites avoid the sun and no wind, no
conductive dust and corrosive gas.
And the following conditions are met:
•
Installation location should be away from the sea to avoid brine and high humidity
environment.
•
The ground for product arrangement shall be flat and level
•
There is no flammable explosive materials near to the installation site.
•
The optimal ambient temperature is 15
℃
~ 30
℃
•
Keep away from dust and messy zones
3.1.2 Tools and data
Hardware tool
Tools and meters that may be used are shown in table 3-1.
Table 3-1 Tool instrument
Name
Screwdriver
(
Slotted
、
Phillips
)
Multimeter
Torque wrench
Clamp current meter
Diagonal pliers
Insulation tape
Pointed nose pliers
Temperature meter
Pliers to hold the wire
Anti-static bracelet
Stripping pliers
Cable tie
Electric drill
Tape measure
3.1.3 Technical preparation
Electrical interface check
Devices that can be connected directly to the battery can be user equipment, power
supplies, or other power supplies.
⚫
Confirm whether the user's PV power generation equipment, power supply or other
power supply equipment has a DC output interface, and measure whether the DC
power output voltage meets the voltage range requirements in Table 2-2.
⚫
Confirm that the maximum discharge current capability of the DC power interface of
the user's photovoltaic power generation equipment, power supply or other power
supply equipment should be greater than the maximum charging current of the
products used in Table 2-2
.
If the maximum discharge capacity of the DC power interface of the user's
photovoltaic power generation equipment is less than the maximum charging
current of the products used in Table 2-2, the DC power interface of the user's
photovoltaic power generation equipment shall have a current limiting function to
ensure the normal operation of the user’s equipment.