5
C. Remove rust, scale and paint from the flow meter mounting
location. Clean to bare metal. Plastic pipes do not require
preparation.
D. Apply a thin, even layer of silicone grease to the two
transducer faces. Ensure that air bubbles are not present
over the two brown plastic sound-guides. Place the electronic
portion of the flow meter onto the prepared area of pipe,
making sure that the flow direction arrow is pointing in the
direction of flow. Place the clamp portion opposite the flow
meter and secure with the enclosed screws. Only moderate
torque is required on the screws—DO NOT OVER TIGHTEN
and DO NOT ROTATE the flow meter on the pipe once the
screws have been tightened.
E. Connect 11-30 Vdc to the power terminals within the TFXL
transmitter. Ensure that the power supply is capable of
sourcing a minimum of 0.25 Amps. Observe polarity.
F. Connect either the 4-20mA, pulse output or both outputs to
the data acquisition or monitoring system as required.
G. Apply power.
H. If the pipe is full of liquid, a flow rate reading will appear. If
the pipe is empty or partially empty, a ERROR 0010 will be
shown on the display. The error will clear when flow resumes
and the pipe fills up with water.
I. Configuration changes and advanced troubleshooting can be
accomplished using the UltraLink software utility, a PC
computer and a PC interface cable.