There are two other conditions for which the LED will be out besides the drive being set for zero 
speed or running wide open above the regulating range. These are whenever the “E” relay is 
deenergized (the drive is stopped), or due to a wiring error, ground or some malfunction of the 
controller itself.  
 

Max Speed/volts R21, Alternate Methods 

a.

 

To set maximum rated speed with a tach or stroboscope: turn the Run Speed potentiometer 
R5 to 100% (full CW) Allow the drive to accelerate to full speed, turn the Max Speed/Volts pot 
CW until the rated speed indicated is the same as the speed listed on the nameplate of the 
mechanical unit.  

b.

 

To set approximate maximum speed with a voltmeter, connect a voltmeter (60 Vac scale 
across terminals G1 and G2. Turn the Run Speed pot R5 to 100% (Full CW) Allow the drive to 
accelerate to full speed. With the drive at full speed, turn the Max Speed/Volts pot CW until 
the meter reading ceases to rise. Back off the adjustment (CCW) until the meter reading just 
begins to drop. This is the point of maximum speed.  

c.

 

To set a maximum speed that is less than rated maximum speed  requires the use of a 
tachometer or stroboscope indicator. This cannot be accomplished with the LED status 
monitor. Turn the Run Speed potentiometer to 100% (Full CW). Allow the drive to accelerate 
to full speed, slowly increase Max Speed/Volts potentiometer setting CW until the desired 
speed is indicated.  

5.

 

Since there may be some interaction between the Zero Adjust and the Max Speed/Volts, 
particularly if the minimum speed is other than zero, repeat steps 3 and 4 until the desired speeds 
are obtained for both the zero and max positions of the Run Speed pot.  

6.

 

Time Constant (TC) Adjust R26

- The TC adjust is used to set current feedback by using coil 

voltage and a variable RC combination to simulate the different coil time constants of various size 
drives. A trimpot illustration is provided to facilitate the setting of this control. Sufficient range 
has been provided for drive size from fractional through 20 hp for the 4000 controller and up to 
125 hp for the 4050 controller. Set you TC control appropriately for your individual drive size as 
shown in Preliminary Adjustments.  
 
Setting are not critical and so may be ‘tuned” for each drive. High inertia applications can benefit 
from a higher than normal setting.  

7.

 

Current Feedback R20*-

 Normal operation will not require use f this potentiometer. Certain 

applications are best met with a negative current feedback response which is slower in settling 
and less likely to overshoot at low rpms. There are some low inertia, light load, linear acceleration 
applications that may also benefit from improved low-end  linearity with current feedback 
damping. If you have one of these applications, remove jumper J1 from the Normal position and 
place it in the increased position. Adjust Current Feedback R20 as required to obtain desired drive 
response.  

*See Basic 4000/4050 manual for a more detailed description of this adjustment.   

Содержание 15-533-1015

Страница 1: ...ug wiring connection adjustment procedure and recommended spare parts list for these specific assemblies are contained in this Instruction Sheet Any differences between these two controllers are clearly noted Use Instruction Manual IM 130006 83XX with this Instruction Sheet for complete installation operation and maintenance instructions Caution Above ground electrical potentials scan be hazardous...

Страница 2: ...liminary Adjustments 7 Operator Controls 7 Main PCB 15 530 5 or 15 530 6 7 Trimpot Illustration 8 Torque Limit 8 Adjustment Procedure 9 Zero Adjust R19 with LED monitor 9 Zero Adjust R19 Alternate Method 9 Max Speed Volts R21 9 Max Speed Volts R21 with LED monitor 9 Max Speed volts R21 Alternate Methods 10 Time Constant TC Adjust R26 10 Current Feedback R20 10 Accel Rate R18 11 Velocity Damping R2...

Страница 3: ...3 Connection diagram for Standard Enclosure 4000 Controller ED 58215 ...

Страница 4: ...4 Schematic Diagram for 4000 Controller ...

Страница 5: ...5 Connection Diagram for 4000 Panel Mount and 4050 Controllers ED 56815 ...

Страница 6: ...6 Schematic Diagram for 4050 Controller Torque Limit Modification PCB 15 444 2 ...

Страница 7: ...mit the torque available to a machine in order to prevent damage to the machine itself or its process The Torque Limit modification provides and override feedback signal which indirectly limits the induction motor torque current to a preset maximum value This limit can be used to prevent the motor breakover torque from being reached during a condition such as drive output shaft lock up or the peri...

Страница 8: ... 182 0 184 186 214 14 18 112 132 140 180 15 216 254 256 280 21 160 210 30 320 360 440 25 24 180 225 250 280 320 360 440 100 Typical product number stamped on mechanical unit nameplate 1 A1 100214 0053 specific mechanical model is AC 214 2 B2 100210 0008 specific mechanical model is AS 21 Trimpot Illustration 3 Torque Limit Mod PCB 15 444 2 a Set the Torque Limit Damping potentiometer R18 at 50 CW ...

Страница 9: ...haft just begins to turn Then back off on the control until the output shaft just stops turning Stop and start the controller a few times to be sure the drive shaft does not rotate b For a minimum speed greater than zero the LED cannot be used Turn the Zero Adjust potentiometer CW until the desired speed is attained For an accurate setting use a tachometer or stroboscope 4 Max Speed Volts R21 This...

Страница 10: ...peed is indicated 5 Since there may be some interaction between the Zero Adjust and the Max Speed Volts particularly if the minimum speed is other than zero repeat steps 3 and 4 until the desired speeds are obtained for both the zero and max positions of the Run Speed pot 6 Time Constant TC Adjust R26 The TC adjust is used to set current feedback by using coil voltage and a variable RC combination...

Страница 11: ...crease turn CW slightly until the speed becomes stable See basic 4000 4050 manual for a more destined description of this adjustment 10 HI Damping R20 This pot is located on the Torque Limit modification board It is used for applications such as stamping presses where the load inertia is greater than 5 to 10 times the drive inertia In these cases turn the Velocity Damping pot R22 on the main board...

Страница 12: ...rent xfmr output voltage at full load VR Current xfmr output voltage at reduced load IF Motor current at full load IR Motor current at reduced load e Disconnect the leads to terminals 1 and 2 on 15 444 2 Modification board and connect a variac f Adjust the variac for VF and adjust the Torque Limit pot until the output speed of the drive just begins to decrease Increasing the output of the variac s...

Страница 13: ...sure 1 15 530 5 Main PCB Refer to PCB parts list above 1 15 444 0002 Torque Limit PCB assembly 4 36 298 0010 Circuit board support Model 4050 Controllers 15 530 0006 Main PCB Assembly 1 27 123 0001 Mini Jumper J1 2 32 028 0100 Fuse 10 Amp 250 V FU1 2 1 53 398 0001 Relay 4pdt plug in E 15 539 0015 Panel Mount 1 15 530 0006 Main PCB Refer to PCB parts list above 1 15 444 0005 Torque Limit PCB assemb...

Страница 14: ...14 Drive Source International Dynamatic 7900 Durand Ave Bldg 3 Sturtevant WI 53177 800 548 2169 sales dynamatic com www Dynamatic com ...

Отзывы: