background image

3690 N.W. 53rd Street, For t Lauderdale, FL 33309 U.S.A.

 (954) 739- 4300  •  Fax: (954) 484-3376  •  Web site: w w w.dynalco.com

© 2000 Dynalco Controls

1200F

DIP SWITCH SETTINGS

Switches 1 & 2 set the

full-scale frequency range

Switches 3 & 4 set the

overspeed relay logic

DIP

SW 1

DIP

SW 2

Full-Scale

Range

DIP

SW 3

DIP

SW 4

Re
Lo

OFF

OFF

=

0 – 11,200 Hz

ON

N/A

=

Ener

Ab

Setp

OFF

ON

=

0 – 5,000 Hz

OFF

N/A

=

De-En

Ab

Setp

ON

ON

=

0 – 1,000 Hz

N/A

ON

=

Latc

N/A

OFF

=

Doe

La

Installation and Calibration Instructions

SW-200B Speed Switch

1. Installation: Mount the SW-200B to a secure bracket off the engine. If

on-engine mounting is necessary, shock mounts are recommended.
Wire according to connection diagram on reverse. Shielded cable is
recommended. Shield should be brought to ground directly. The
SW-200B will work with most magnetic pickups provided the signal
amplitude is greater than 50 mVrms and less than 70 Vrms. Mount
pickup according to manufacturer’s instructions.

2. Calibration: Determine the setpoint frequencies from an RPM value

using the following formula:

 Frequency =

  RPM x No. of Teeth (Holes)

                60

A. Verify the current calibration: use a signal generator. Connect it to

the SW-200B magnetic pickup input.

B. Confirm the DIP switches are properly set for the frequency range and

overspeed relay logic desired. (See chart below.)

C. Set the signal generator output to at least 10% below the lowest setpoint.

Slowly increase the frequency. Using an ohmmeter across the relay
contacts, determine the frequency at which each relay changes state.

a. Change a setpoint: remove the appropriate access hole screw to reach

the setpoint's relay adjustment trim pot.

b. Set the signal generator to the frequency at which the relay should change

state. Connect it to the SW-200B magnetic pickup input.

c. Using a small, flat screwdriver, adjust the trim pot for the appropriate

relay until the relay changes state.

d. Decrease the frequency, then slowly increase it to verify that the relay

trips at the appropriate point. 

Replace the access hole screw.

SW-200B is a trademark of Dynalco Controls

DYNALCO CONTROLS RESERVES THE RIGHT TO CHANGE THESE SPECIFICATIONS WITHOUT NOTICE.

Отзывы: