Settings
36
© 2019 DynaGen Technologies Inc
TOUGH Series Manual
Name
Range
Default
Settings
Description
Setpoints > High
Fail (High Failure)
Disabled, 50 ~
300°F (10 ~
148.9
0
C)
220 F
Reading at which a "High Engine Temp" failure occurs. Only applies if
Sensor Type has been set to a sender. Only monitored in the RUN
mode.
Note: All temperature settings are entered in terms of Fahrenheit.
4.4.2
Oil Pressure
Use the following settings' configurations to allow the controller to read and interpret data from the oil pressure sensor or
switch.
Name
Range
Default
Description
Signal
Source
Port A
Port B
Port C
Port D
J1939 Bus*
Port B
The sensor input pin where the oil pressure switch or sender is attached.
*Oil pressure is obtained from the engine controller (ECM) using the
CANbus communication port and J1939 protocol.
Sensor Type DAT 100P/R240*
VDO 150P/R180*
(custom sender)**
Close = Warning
+
Open = Warning
+
Close = Failure
+
Open = Failure
+
DAT
100P/R240
(Steart
279B-F)
Select the sender that is connected to the Signal Source above. If using
a switch select the action that should occur when the switch is active.
*These are preprogrammed into the controller and cannot be changed.
- DAT 100P/R240 supports the Stewart - Warner 279B-F and Datcon
2505-00 sender tables.
- VDO 150P/R180 supports the VDO 360-004 oil pressure sender.
DAT 100P/R240 and VDO 150P/R180 can not be used on port A. To use
on port A store as a custom sender table using the RapidCore
Configuration software.
**A custom table created using the RapidCore Configuration Software.
The text (custom sender) will be replaced with the custom text you
choose when creating the sender.
+
The switch must close to ground.
Trim Offset
-50.0 ~ 50.0 PSI (-
344.7 ~ 344.7kPa)
0 PSI
Calibrate a sensor by using the offset to correct errors. Only applies if
Sensor Type has been set to a sender.
Setpoints ->
Bypass Time
0 ~ 90 seconds
30 s
Amount of time to bypass warnings and failures after engine has started.
Setpoints ->
Low Warning
Disabled, 0.1 ~ 99.0
psi (0.7 ~ 682.6kPa)
20.0 PSI
Reading at which a "Low Oil Pressure" warning occurs. Only applies if
Sensor Type has been set to a sender.
Setpoints ->
Low Failure
Disabled, 0.1 ~ 99.0
psi (0.7 ~ 682.6kPa)
15.0 PSI
Reading at which a "Low Oil Pressure" failure occurs. Only applies if
Sensor Type has been set to a sender.
Note: All pressure settings are entered in terms of psi.
4.4.3
Fuel Level
Use the following settings' configurations to allow the controller to read and interpret data from the fuel level sensor.
Name
Range
Default
Description
Signal Source
Disable
Port A
Port B
Port C
Port D
Disable
The sensor input pin where the fuel level switch or sender is attached.
Sensor Type
DAT R/33-
240*
VDO R/0-
180*
(custom
sender)**
Close = Failure
Select the sender that is connected to the Signal Source above. If using a
switch select the action that should occur when the switch is active.
*These are preprogrammed into the controller and cannot be changed.
- DAT R33-240 supports a Dacon fuel level sensor of the range 33 Ohms to
180 Ohms
Содержание Tough Series
Страница 4: ...3 2019 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2019 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2019 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2019 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2019 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 19: ...Installation 18 2019 DynaGen Technologies Inc TOUGH Series Manual ...