Installation
18
© 2017 DynaGen Technologies Inc
TOUGH Series Manual
2.6.6
Current Transformers
When wiring current transformers into the system you must follow these considerations:
1.
The maximum amperage allowed on the secondary is 5A. A 5:X ratio CT should be used where X is the maximum
primary amperage rating (e.g. 200A).
2.
The CT power rating should be a minimum of 1VA.
3.
The current transformer of each phase must be facing the same direction. See below.
4.
The CT Common connection must be connected to the black wire on each current transformer.
5.
The wires from the current transformers to the controller should be as short as possible.
6.
The CT wires should be run in a separate conduit from the AC voltage wires.
NOTE
: If readings are unstable with the configuration shown below, attempt connecting the CT Common's black wire
to the negative terminal of the battery. Ensure the connecting wire is as short as possible.
Содержание TG410
Страница 4: ...3 2017 DynaGen Technologies Inc TOUGH Series Manual User Guide ...
Страница 11: ...Installation 10 2017 DynaGen Technologies Inc TOUGH Series Manual 2 3 Wiring Harnesses ...
Страница 12: ...Installation 11 2017 DynaGen Technologies Inc TOUGH Series Manual 2 4 Typical Wiring Diagram ...
Страница 13: ...Installation 12 2017 DynaGen Technologies Inc TOUGH Series Manual 2 5 Typical Wiring Diagram with RelayPak ...
Страница 17: ...Installation 16 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 20: ...Installation 19 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 22: ...Installation 21 2017 DynaGen Technologies Inc TOUGH Series Manual ...
Страница 40: ...Settings 39 2017 DynaGen Technologies Inc TOUGH Series Manual ...