For communication between the master and the slave modules, the EOL slave modules must
be connected to ground. The shielding on the speaker cable, a free wire in the speaker cable,
or any other available ground point – such as the safety ground of the power supply system –
can be used for this purpose. The resistance between an output line of the DPA and the
ground must be at least 800 kOhms. The capacity between an output line of the DPA and the
ground must not be greater than 200 nF.
EOL
Slave
DPA
EOL
Master
Shield / Wire / Ground
Figure 6.11: EOL circuit diagram
EOL monitoring function setup
Connect the EOL slave modules to the end of the speaker line. Set the desired address at the
DIP switches.
DIP switch SW2
DIP switch SW1
4
3
2
1
4
3
2
1
OFF OFF OFF OFF OFF 0 (not connected)
Module address
OFF OFF OFF OFF ON
1
OFF OFF OFF ON
OFF 2
OFF OFF OFF ON
ON
3
OFF OFF OFF OFF OFF 4
OFF OFF ON
OFF ON
5
OFF OFF ON
ON
OFF 6
OFF OFF ON
ON
ON
7
OFF ON
ON
OFF OFF 8
OFF ON
OFF OFF ON
9
OFF ON
OFF ON
OFF 10
OFF ON
OFF ON
ON
11
OFF ON
ON
OFF OFF 12
OFF ON
ON
OFF ON
13
OFF ON
ON
ON
OFF 14
OFF ON
ON
ON
ON
15
ON
OFF OFF OFF OFF 16
ON
OFF OFF OFF ON
17
:
:
:
:
:
:
ON
ON
ON
ON
OFF 30
24
en | Safety information
PROMATRIX 8000 POWER AMPLIFIER
19-Aug-13 | 03 | F01U217494
User manual