1.0
Message Display Readings
Message Display / Cycle Counter
DYNACO USA, INC,
2
The Leader in Door Safety & Design
1. Follow table to translate display readings on initial power up. See table 1.0-1
Display Reading
Translation
Ready
###
Drive Error
Rev - Edge
Tripped
Opening
Expired
Closed
Expired
SET
LIMITS
ENCODER
COM_LOSS
Means its ready to go and the
number below is the cycle counter
Means the Variable Frequency Drive
went into error
Means the reversing edge is staying
or was activated
Means the open run timer has
expired
Means the closed run timer has
expired
Means to set limits do to loss of
limits or new install
Means that the DY4000 lost encoder
feedback
Operate door
Check drive display for error code
(refer:N/A)
Check pneumatic switch for proper
operation / Normal if activated
Reset unit (via up jog reset) / check
open run timer setting (refer: Pg7)
Reset unit (via up jog reset) / check
closed run timer setting (refer: Pg7)
Set Limits (refer: Pgs 3-6)
Check if encoder connected and
wired correctly (refer: N/A)
Table 1.0-1: Display Chart
2. DY4000 has a two line display. See figure 1.0-2
MESSAGE DISPLAY / COUNTER
READY
562
FIRST LINE DISPLAYS
DIFFERENT MESSAGES OF
OPERATION
SECOND LINE DISPLAYS
CYCLE COUNTER / TIMER
SETTINGS
Figure 1.0-2: DY4000 display
Note:
Most error codes can be reset using the
JOG UP/RESET
button
Action Taken