Minimum sash height/ -width

The details apply to a 

non-rotational installation of the drive!

(Window inwards opening)

Standard chain:

Minimum size (mm) = Stroke (mm) x 3.9

Maximum stroke bottom-hung vent: 1000 mm

Maximum stroke side-hung vent: 800 mm

Side bow chain:

Minimum size (mm) = Stroke (mm) x 1,6

Maximum stroke bottom-hung vent: 800 mm

Maximum stroke side-hung vent: 350 mm

x

x

99.827.07 1.0/02/17

CDC-0252-5-ACB

8/20

CDC-0252-5-ACB

 

Visual inspection: 

Only one master drive is allowed.

The master always has the last address of all the 

drives; this can be found on a sticker attached to 

the drive. Slaves are numbered downwards from 

the master, so that in a group of three drives, for 

example, the master is no. 3, with a slave 2 and 

slave 1 drive. Please note that this only applies in 

the ex-factory configuration. As soon as the drives 

are reconfigured with SCS, the ex-factory 

addressing no longer applies.

The CDC-0252-5-ACB must be set as master.

Wiring:

Is the drive or drive group wired properly?

See connection plans.

Diagnostics with SCS software:

The SCS software and a BSY+ interface is 

required for further troubleshooting or 

configuration.

Troubleshooting

English

Electrical devices, accessories, batteries and packa-

ging  should  be  sorted  for  environmental-friendly 

recycling.  Do  not  dispose  electrical  devices  and 

batteries into household waste!

Only for EC countries:

According the European Guideline 2012/19/EU for 

waste  electrical  and  electronic  equipment  and  its 

implementation into national right, electrcal devices 

that are no longer usable must be collected separa-

tely and disposed of in an environmentally correct 

manner.

Disposal

Declaration of Conformity

We  declare  under  our  sole  responsibility  that  the 

product  described  under  “Technical  Data”  is  in 

conformity with the following directives:
2014/30/EU, 2014/35/EU
Technical file at:

D+H Mechatronic AG, D-22949 Ammersbek
Dirk Dingfelder 

Maik Schmees

Member of the Board 

Authorized signatory, Technical Director

21.02.2017

Maintenance and cleaning

Maintenance work is only allowed when the device is in 

a de-energized condition! Inspection and maintenance 

has to be carried out according to D+H maintenance 

notes.  Only  original  D+H  spare  parts  may  be  used. 

Repair is to be carried out exclusively by D+H.

Wipe away debris or contamination with a dry, soft 

cloth.

Do not use cleaning agents or solvents.

Guarantee

You will get 2 years guarantee for all D+H products 

from date of verified handing over of the system up to 

maximal  3  years  after  date  of  delivery,  when 

mounting and starting has been carried out by an 

authorized D+H-distributor.

D+H guarantee is expired, with connection of D+H 

components with external systems or with mixing of 

D+H products with parts of other manufacturers.

30 mm 

35 mm 

A

545 mm

242 mm

303 mm

670 mm

625 mm

367 mm

322 mm

303 mm

303 mm

775 mm

472 mm

303 mm

CDC-0252-0350-5-ACB

CDC-0252-0600-5-ACB

CDC-0252-0500-5-ACB

CDC-0252-0800-5-ACB

A

B

C

Dimensions

B

C

= =

- The drive set is fully configured ex factory.The 

drives must be reconfigured using SCS in the 

event of changes to the ex-factory configuration 

(e.g. when removing a drive from existing set or 

integrating a new drive).

- Mount the drives whilst under zero stress. With 

that, an even load distribution is provided by all 

the drive chains.

- At vertical active pulling application (e.g. for a 

skylight) the forces must be rearranged by 

software SCS.

- If after mounting, the distance X is greater than 23 

mm, null balance with software SCS is neccesary. 

Closure Ranges will shift in relation to new zero 

point.

Mounting information

≥ 23 mm ? 

X

ACB bus interface

ACB is used for secure communication between the 

drive  and  compatible  D+H  control  systems.  It 

enables  activation,  diagnostics  and  configuration 

with perfect position, directly from the control panel. 

In  this  process,  all  status  messages,  such  as  the 

OPEN  and  CLOSED  signals,  opening  stroke  and 

drive errors, are transmitted to the control panel.

BSY+ synchronised electronics:

A  synchronous  group  can  contain  up  to  8  drives, 

which communicate via bus. Each drive has its own 

address, configurable with SCS.

The last drive of a synchronous group is the master, 

which  controls  the  other  drives,  the  slaves. 

Differences in forces between the drives of a group 

are  balanced  by  means  of  intelligent  force  and 

position  control.  In  the  event  that  a  drive 

malfunctions, all the drives are automatically cut off.

Functional description

Содержание D+H CDC-0252-5-ACB Series

Страница 1: ...CDC 0252 5 ACB instructions Please order bracket sets separately ...

Страница 2: ...ctions for future reference Features ACB Advanced Communication Bus bus interface with ModBus protocol for the connection to compatible D H control panels or direct integration into building management systems for example BSY electronics for reliable and accurate synchronous operation of up to 2 drives Individually programmable via software SCS Outstanding quiet performance thanks to acoustic deco...

Страница 3: ...mm 150 N 23 mm 250 N 15 mm 250 N 250 N Type CDC 0252 0350 5 ACB CDC 0252 0500 5 ACB CDC 0252 0600 5 ACB CDC 0252 0800 5 ACB Power supply Nominal force Input power 230 V AC 10 15 50 Hz 250 N 33 W 45 VA 2x Set 64 W 90 VA Nominal stroke length 350 mm 2 500 mm 2 600 mm 2 800mm 2 Running speed ventilation SHEV high speed function O1 O2 O3 C3 C2 C1 6 7 mm s 9 4 mm s 6 7 mm s 6 7 mm s 5 mm s 9 4 mm s 5 m...

Страница 4: ...gured using SCS in the event of changes to the ex factory configuration e g when removing a drive from existing set or integrating a new drive Mount the drives whilst under zero stress With that an even load distribution is provided by all the drive chains At vertical active pulling application e g for a skylight the forces must be rearranged by software SCS If after mounting the distance X is gre...

Страница 5: ...signatory Technical Director 21 02 2017 Maintenance and cleaning Maintenance work is only allowed when the device is in a de energized condition Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used RepairistobecarriedoutexclusivelybyD H Wipe away debris or contamination with a dry soft cloth Donotusecleaningagentsorsolvents G...

Страница 6: ...L BK L BU N Optional signalling cable Mot a 24V WH BN Mot b GND OG ACB a YE BSY a GN BSY b GY ACB b High Speed High Speed Master 1 Connection Do not reverse L N Connect PE Junction box SHEV fast running Normal mode 1 drive GN green YE yellow BU blue BN brown BK black WH white PK pink GY grey ...

Страница 7: ...52 1 ACB ON 24 V DC Slave 1 Master 2 High Speed High Speed Connection Do not reverse L N Connect PE Junction box WH Mot a 24V BN Mot b GND OG ACB a YE BSY a GN BSY b GY ACB b SHEV fast running Normal mode 2 drives looped through GN green YE yellow BU blue BN brown BK black WH white PK pink GY grey ...

Страница 8: ...reen YE yellow BU blue BN brown BK black WH white PK pink GY grey Option DS BN Mot b OG ACB a HS GY ACB b GN BSY b YE BSY a WH Mot a Standard BN Mot b OG ACB a HS GY ACB b GN BSY b YE BSY a WH Mot a 6x 0 5 mm Ø 7 1 0 5 mm 6x 0 5 mm Ø 7 1 0 5 mm BN GND Mot b OG ACB a GY ACB b GN BSY b YE BSY a WH 24V Mot a CDC 0252 5 ACB CDC 0252 1 ACB ON Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Es...

Отзывы: