Safety notes

Safety extra low voltage 24 V DC!

Do not connect directly to the mains supply!

-   Connection must be carried out by a certified

   electrical technician

-   Danger of crushing hands and fingers!

-   Keep people away from the operating area of the

   drive

-   Keep children away from the control

-   Observe pressure load diagram of the chain

-   Use only in dry rooms

-   Suitable for indoor mounting only. Use rain

   detector in locations if there is a risk of rain

-   Use unmodified original D+H parts only

-   Observe mounting instructions of bracket set!

Observe enclosed red safety note!

Intended use

- Chain drive for electric opening and closing of

  windows and flaps in the facade and roof area

- Operating voltage 24 V DC

- Useable for smoke ventilation as well as daily 

natural ventilation

- Suitable for indoor mounting only

99.826.94 1.2/02/17

CDC-0252-1-ACB

6/20

CDC-0252-1-ACB

 

English

Features

- ACB (Advanced Communication Bus) bus 

interface with ModBus protocol for the connection 

to compatible D+H control panels or direct 

integration into building management systems, 

for example

- BSY+ electronics for reliable and accurate 

synchronous operation of up to 8 drives

- Individually programmable via software SCS

- Outstanding quiet performance thanks to 

acoustic decoupling of the drive components and 

reduced motor speed in ventilation mode

- SHEV-high speed function (fast-running feature 

in case of an alarm)

- Protection system for the main closing edge

- Rated voltage and Bus-signals loopable for max. 

3 drives

- Connection possible from both sides

- The force can be increased at the factory up to 

400 N (nominal current 1 A) in the seal area

- Relief of pressure on window gasket after closing

- Direct connection of additional closing edge 

protection at the drive possible (SKS option)

Technical Data

* Programmable with software SCS   ** + approx. 20 % switch-off reserve (temporary)

C3*

250 mm

250 N

Opening and Closing Ranges

O1*

C1*

C2*

O2*

O3*

23 mm

150 N

77 mm

150 N

23 mm

250 N

15 mm

250 N

250 N

Type

CDC-0252-0350-1-ACB CDC-0252-0500-1-ACB CDC-0252-0600-1-ACB CDC-0252-0800-1-ACB

Power supply
Nominal force

24 V DC / ± 15 %

250 N**

Nominal current

0,6 A

0,8 A

1,0 A

Nominal stroke length*

350 mm ± 2 %

500 mm ± 2 %

600 mm ± 2 %

800mm ± 2 %

Running speed: ventilation (SHEV high-speed function)*

O1, O2
O3
C3
C2, C1

6,7 mm/s (9,4 mm/s)
6,7 mm/s (6,7 mm/s)

5 mm/s (9,4 mm/s)

5 mm/s (5 mm/s)

6,7 mm/s (13,6 mm/s)

6,7 mm/s (6,7 mm/s)

6,7 mm/s (13,6 mm/s)

5 mm/s (5 mm/s)

6,7 mm/s (15,0 mm/s)

6,7 mm/s (6,7 mm/s)

6,7 mm/s (15,0 mm/s)

5 mm/s (5 mm/s)

Nominal locking force
Service life
Duty cycle
Housing
Ingress protection
Temp. range
Fire stability
Ambient humidity
Emission sound pressure level
Additional functions*

approx. 1500 N

>10.000 double strokes

30 % S6 (EN 60034-1)

Aluminium powdercoated (~ RAL 9006)

IP 32

-5 ... +75 °C

30 min / 300 °C

≤ 90 %, not condensing

LpA = 35 dB(A)

Closing edge protection = activated (3 repetitions of stroke);

Locking relief  = activated (retraction lift max. 0,2 mm)

WARNING

Read all safety warnings, instructions, illustrations 

and specifications provided with this product.

Failure to follow all instructions listed below may 

result in electric shock, fire and/or serious injury.

Save all warnings and instructions for future 

reference.

Observe maximum pressure load of the chain!

Maximum pressure load of chain is not automatically 

identical with maximum pressure force of the drive!

Standard

-SBD / -SBU

100

200

300

400

500

600

700

800

250

300

350

400

200
150
100

50

0

Pressure load (N)

Stroke (mm)

250

50

Pressure load diagram

Main closing edge

Beside closing edge

Beside

closing edge

Closing edge protection

In  the  "CLOSE"  direction  the  drive  has  an  active 

protection for the main closing edge. If there is an 

overload in the closing ranges C3 and C2, the drive 

runs "OPEN" for 10 seconds, then "CLOSE" again. If 

closing is not possible after three attempts, the drive 

remains in this position.

In  addition,  the  drive  is  equipped  with  passive 

protection. The closing speed in closing range C2 

and C1 is reduced to 5 mm/s.

Significantly greater forces can be

exerted at the secondary closing

edges. Danger of crushing hands and

fingers!

Chain type

The mounting instructions for the bracket

set must be observed before mounting.

Always observe and comply with the

information in the mounting instructions.

Attention with side bow chains SBD and SBU 

-SBD

Standard chain

-SBU

Side bow chain

Side bow chain

Scope of supply

Drive unit with 2.5 m silicone cable.

Depending on the type of window, different bracket 

sets are available separately.

Содержание CDC-0252-1-ACB Series

Страница 1: ...CDC 0252 1 ACB instructions Standard version R Mirrored version option L Please order bracket sets separately ...

Страница 2: ... reduced motor speed in ventilation mode SHEV high speed function fast running feature in case of an alarm Protection system for the main closing edge Rated voltage and Bus signals loopable for max 3 drives Connection possible from both sides The force can be increased at the factory up to 400 N nominal current 1 A in the seal area Relief of pressure on window gasket after closing Direct connectio...

Страница 3: ...ng Ingress protection Temp range Fire stability Ambient humidity Emission sound pressure level Additional functions approx 1500 N 10 000 double strokes 30 S6 EN 60034 1 Aluminium powdercoated RAL 9006 IP 32 5 75 C 30 min 300 C 90 not condensing LpA 35 dB A Closing edge protection activated 3 repetitions of stroke Locking relief activated retraction lift max 0 2 mm Main closing edge Beside closing ...

Страница 4: ...guration with perfect position directly from the control panel In this process all status messages such as the OPEN and CLOSED signals opening stroke and drive errors are transmitted to the control panel BSY synchronised electronics A synchronous group can contain up to 8 drives which communicate via bus Each drive has its own address configurable with SCS The last drive of a synchronous group is ...

Страница 5: ...signatory Technical Director 11 08 2016 Maintenance and cleaning Maintenance work is only allowed when the device is in a de energized condition Inspection and maintenance has to be carried out according to D H maintenance notes Only original D H spare parts may be used RepairistobecarriedoutexclusivelybyD H Wipe away debris or contamination with a dry soft cloth Donotusecleaningagentsorsolvents G...

Страница 6: ...Speed High Speed High Speed Mot a Mot b 1 2 3 4 5 L 6 N 7 Z A E X a b LT Group MOT BK BK OG 2x47kW End mod ul Term inal mod ule Mod ule term inal EM 47 K WH BN OG YE GN GY Mot a Mot b ACB a HS BSY a BSY b ACB b CDC 0252 1 Junction box Master 2 2 up to max 3 drives looped through WH BN OG YE GN GY Mot a Mot b ACB a HS BSY a BSY b ACB b CDC 0252 1 Slave 1 Mot b BN Mot a WH 24 V DC 24 V DC Monitoring...

Страница 7: ...b BSY b ACB b ACB b CDC 0252 1 CDC 0252 1 Junction box Master 2 Slave 1 High Speed High Speed High Speed WH white BN brown OG orange YE yellow GN green PK pink GY grey Monitoring Not in case of GVL E K M Protect wire against short circuit In case of connection to D H SHEV control panels with E HS line monitoring Cable according to D H table for layout of cables See instructions for use of control ...

Страница 8: ...tion SKS BN Mot b OG SKS GY SKS GN BSY b YE BSY a WH Mot a BN Mot b OG ACB a HS GY ACB b GN BSY b YE BSY a WH Mot a Motor side Chain side Type plate WH white BN brown OG orange YE yellow GN green PK pink GY grey Dyer Environmental Controls Ltd Unit 10 Lawnhurst Trading Estate Cheadle Heath Stockport SK3 0SD Tel 44 0 161 491 4840 E Mail enquiry dyerenvironmental co uk www dyerenvironmental co uk ...

Отзывы: