Dwyer Instruments W.E. Anderson WE35 Series Скачать руководство пользователя страница 9

9

Electric Actuators Wiring Diagram: ACT-TD & ACT-MD

Wiring Diagrams for

TD01-A to TD06-A: 110 VAC, TD01-B to TD06-B: 220 VAC,

TD01-C to TD06-C: 24 VAC

Wiring Diagrams for

TD01-D to TD06-D: 24 VDC

Wiring Diagrams for

TD01-D to TD06-D: 24 VDC

Note: 

To speed up installation of the control wires to the ACT-MDXX modulating 

actuator, it is recommended to remove the control module from the actuator. The 

control module can be removed by removing the two mounting screws on the left 

and right of the control module. Install the control wires to the correct terminal points 

and then reinstall the control module.

Electric Actuator Maintenance

Once the actuator has been properly installed, it requires no maintenance. The gear 

train has been lubricated and in most cases will never be opened. 

Duty Cycle Definition

“Duty Cycle” means the starting frequency.

Formula: Running Time 

÷

 (Running Time + Rest Time) x 100% = duty cycle

 

> Rest Time = Running Time x (1 - duty cycle) 

÷

 duty cycle

For example: The running time is 15 seconds

  30% duty cycle     15 x [(1 - 30%) / 30%] = 35 

The rest time will be 35 seconds

  75% duty cycle    15 x [(1 - 75%) / 75%] = 5 

The rest time will be 5 seconds

If the duty cycle is higher, the rest time will be shortened, which means the starting 

frequency will be higher.

Thermal Overload

All actuators are equipped with thermal overload protection to guard the motor

against damage due to overheating.

Mechanical Overload

All actuators are designed to withstand stall conditions. It is not recommended to 

subject the unit to repeated stall conditions.

Explosion-Proof Electric Actuators

1.  DO NOT under any circumstances remove the cover of the 

actuator  while  in  a  hazardous  location.  Removal  of  the  cover 

while in a hazardous location could cause ignition of hazardous atmospheres.

2.   DO NOT under any circumstances use an explosion-proof electric actuator in a 

hazardous location that does not meet the specifications for which the actuator 

was designed.

3.    Always  verify  that  all  electrical  circuits  are  de-energized  before  opening  the 

actuator.

4.    Always  mount  and  cycle  test  the  actuator  on  the  valve  in  a  non-hazardous 

location.

5.    When removing the cover, care must be taken not to scratch, scar of deform the 

flame path of the cover and base of the actuator, since this will negate the NEMA 

rating of the enclosure.

6.    When replacing the cover, take care that the gasket is in place to assure proper 

clearance after the cover is secured. 

7.    All electrical connections must be in accordance with the specifications for which 

the unit is being used.

8.    Should the unit ever require maintenance, remove from the hazardous location 

before attempting to work on the unit. If the actuator is in a critical application, it 

is advisable to have a standby unit in stock.

WARNING

1

2

3

4

5

6

7

Y&G

GREY

PE

BROWN

WHITE

BLACK

RED

BLUE

OLS

CLS

C

M

PE

FULL-CLOSE SIGNAL

FULL-OPEN SIGNAL

COM

OPEN

K

L

CLOSE

N

+

-

1

2

3

4

5

6

7

Y&G

GREY

PE

BROWN

WHITE

BLACK

RED

OLS

CLS

M

PE

FULL-CLOSE SIGNAL

FULL-OPEN SIGNAL

COM

OPEN

CLOSE

+

-

D1

D2

BLACK

RED

BLUE

C

M

PE

L

N

PINK

PURPLE

ORANGE

RP

IK

OUTPUT SIGNAL

INPUT SIGNAL

POWER

+

-

+

-

SER

VO CONTROLLER

Содержание W.E. Anderson WE35 Series

Страница 1: ...s Body ball and stem Brass Seat seal and packing PTFE Temperature Limits 20 to 425 F 30 to 220 C Other Materials O ring NBR Handle stem nut ferrule SS Handle Sleeve Vinyl Body and cap Nickle plated ACTUATORS Pneumatic DA and SR Series Type DA series is a double acting and SR series is a spring return rack and pinion Normal Supply Pressure DA 40 to 115 psi 2 7 to 7 9 bar SR 80 psi 5 5 bar Maximum S...

Страница 2: ... ESR03 T2 WE35 FSR03 T2 WE35 GSR03 T2 WE35 HSR04 T2 WE35 CTD01 T2 A WE35 DTD01 T2 A WE35 ETD01 T2 A WE35 FTD01 T2 A WE35 GTD01 T2 A WE35 HTD02 T2 A WE35 CMD01 T2 A WE35 DMD01 T2 A WE35 EMD01 T2 A WE35 FMD01 T2 A WE35 GMD01 T2 A WE35 HMD01 T2 A MODEL CHART Model Size Ø A in mm L in mm W in mm H in mm Ø D1 in mm Ø D2 in mm ISO ØS in mm Ra in mm Rb in mm PORT M1 Torque in lb CV gal min WE35 CHD00 T1 ...

Страница 3: ...7 mm 4 101 mm 4 5 8 117 mm 10 1 2 268 mm 2 1 8 55 mm 8 1 2 216 mm 4 1 4 109 mm 4 7 8 124 mm 9 1 2 242 mm 2 1 4 58 mm 9 3 8 237 mm 4 3 4 122 mm 5 7 8 148 mm 10 7 8 275 mm 2 1 2 64 mm ELECTRIC ACTUATOR NPT 1 2 3 4 1 1 1 4 1 1 2 2 B C D E F 6 1 2 167 mm 5 1 4 133 mm 3 76 mm 6 1 8 154 mm 2 3 4 68 mm 10 1 8 257 mm 9 3 8 239 mm 3 3 8 86 mm 8 1 2 217 mm 5 126 mm 8 1 2 216 mm 9 3 8 239 mm 3 7 8 99 mm 8 1 ...

Страница 4: ...ody 4 Remove the pinion through the bottom of the actuator The actuator is now completely disassembled WARNING Be sure the actuator surfaces are free of debris and scratches before reassembling 1 Apply a light film of grease to all O rings and the pinion before replacing 2 Put the pinion 2 back through the actuator with the flats of the pinion shaft running parallel with the body 3 When reassembli...

Страница 5: ... ring O ring Guide ring Spring assembly O ring Left end cap Right end cap End cap bolt O ring Gasket Nut Adjusting bolt Extruded aluminum alloy Stainless steel Fluorine silicon rubber Nylon46 Stainless steel Nylon46 Nylon46 Fluorine silicon rubber Nylon46 Stainless steel Stainless steel PPPP 30 GF PPPP 30 GF PPPP 30 GF Casting aluminum alloy Nylon46 Fluorine silicon rubber Fluorine carbon composit...

Страница 6: ...ng pad if it is ISO5211 compliant 8 Cycle the unit several times and check the open and closed positions of the valve Cams are pre adjusted at the factory due to the variety of valve designs and types however slight adjustments might be required 9 Replace cover and tighten screws To Set The Open Position 1 Cycle the valve to the open position by applying power to terminals The top cam and switch c...

Страница 7: ...HREE CLOSES THE VALVE CW ROTATION TERMINALS 4 5 ARE FOR LIGHT INDICATION WIRING DIAGRAM ILLUSTRATES THE ACTUATOR IN THE OPEN POSITION GROUND SCREW OPTIONAL BRAKE LIGHTS FOR REMOTE POSITION INDICATION OPTIONAL EQUIPMENT FIELD WIRING Wiring Diagrams for TI01 D to TI06 D 24 VDC DC MOTOR CA M CA M SW 1 SW 2 DC VOLTAGE SPDT SWITCH SHOWN FOR ILLUSTRATION ONLY REVERSING RELAY SUPPLIED BY CUSTOMER FIELD W...

Страница 8: ...W IS FAIL IN LAST POSITION UPON LOSS OF SIGNAL SW 3 CLOSE SW 4 OPEN AUXILIARY SWITCHES OPTIONAL OPTIONAL EQUIPMENT FIELD WIRING Wiring Diagrams for MI01 D to MI06 D 24 VDC J1 J2 4 20mA POSITIONER PSC MOTOR CAPACITOR SW 1 CLOSE SW 2 OPEN BRAKE OPTIONAL 1PH 60HZ POWER SUPPLY 4 20mA CONTROL SIGNAL 0 10VDC or 0 5VDC CONTROL SIGNAL REMOVE JP2 JP3 JP4 1K OHM FEEDBACK POTENTIOMETER FIELD WIRING N HOT NOT...

Страница 9: ...itions It is not recommended to subject the unit to repeated stall conditions Explosion Proof Electric Actuators 1 DO NOT under any circumstances remove the cover of the actuator while in a hazardous location Removal of the cover while in a hazardous location could cause ignition of hazardous atmospheres 2 DO NOT under any circumstances use an explosion proof electric actuator in a hazardous locat...

Страница 10: ...25 0 4 100 24 VDC 2 5 s 25 0 4 100 TI02 and MI01 MI02 Voltage Cycle Time Two Position Cycle Time Modulating Duty Cycle Two Position Duty Cycle Modulating Full Load AMP Draw Torque in lb 110 VAC 5 s 10 s 25 75 0 38 200 220 VAC 5 s 10 s 25 75 0 18 200 24 VAC 5 s 5 s 25 75 0 7 200 24 VDC 5 s 5 s 25 75 0 7 200 TI03 and MI03 Voltage Cycle Time Two Position Cycle Time Modulating Duty Cycle Two Position ...

Страница 11: ...______________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ ___________________...

Страница 12: ..._______________________________________________________________________________________________________________________________ __________________________________________________________________________________________________________________________________________ _____________________________________________________________________________________________________________________________________...

Отзывы: