Solar Panel

LOCATION

The solar panel should oriented as much as possible toward 
the midday sun. Locate where there is no significant shading 
of the solar panel. The Solar Charge Controller and Sealed 
Lead Acid (SLA) battery should be located in close physical 
and thermal proximity. Both must be shaded from direct 
sunlight to minimize temperature differences between them 
which will greatly diminish the battery service life. Also insulate 
the bottom of the battery if heat could be absorbed from the 
surface (concrete, metal etc.) on which the battery is resting. 
Also take measures to prevent accumulation of moisture (rain, 
snow, ice, flooding) between the battery terminals which could 
discharge the battery.

If the battery and Solar Charge Controller are housed in an 
enclosure, the outside must be white or shiny metallic to mini-
mize solar heat build up inside that is seriously detrimental 
to the service life of the battery. Even light colors (such as the 
standard ANSI 61 Gray) can elevate the interior of the enclosure 
by 40F (22C.) If other colors are used, the enclosure must be 
shaded from direct sunlight or painted glossy white. In addition, 
because even sealed batteries could vent if the Solar Charge 
Controller fails, for safety reasons the enclosure should be 
vented, particularly if it contains other electrical equipment.

290 mA (typical at design operating point)
17 V (typical at design operating point)
14.2”
8.5”
4 pounds (solar panel and mounting bracket)
Bracket, band clamps and mounting hardware for 1-1/2 or 2 inch vertical pipe
-40˚ F to +158˚ F (-40˚ C to +70˚ C)

High efficiency series PWM regulator with temperature compensation and built-in lightning protection

Electrical   Current
 

 Voltage

Dimensions   Height
 

 Width

 

 Weight

Mounting
Operating Temperature Range
Change Controller

SPECIFICATIONS*

*Specifications subject to change 

For powering Dwyer Instruments Inc. mechanical meters 
along with display electronics, use a 12V Sealed Lead Acid 
(SLA) deep-cycle battery with a minimum capacity of 22 Amp-
hours. This should provide a conservative 40 day backup with 
maximum  battery  service  life.  Marine/RV  grade  deep-cycle 
batteries or automotive batteries may be used but must be 
upsized in Amp-hour capacity by two times and four times 
respectively to achieve the same battery service life in most 
applications.

For powering Dwyer Instruments Inc. low power (<50mA) 
magnetic flow meters use only deep-cycle SLA batteries (not 
marine/RV orautomotive grade batteries) with a minimum ca-

pacity of 33 Amp-hours. In climates where meters are operat-
ing in full pipe mode much of the time with extended periods 
of cloudy days, operating continuously through the year, or in 
latitudes above 50 degrees, the required battery Amp-hour 
capacity should be reviewed before selection. To learn more, 
consult the Appendix in our solar power application note 
found at www.dwyer-inst.com.

In summary, the minimum recommended battery capacity, as 
described above, will be adequate in most climates and ap-
plications. However, under marginal conditions, a larger ca-
pacity battery may provide superior reliability, better battery 
service life and lower life-cycle costs. 

BATTERY SELECTION

TM

Содержание SPK

Страница 1: ...tandard with a charge controller and corrossion resistant mounting hardware The SPK can also be used to provide up to a 40 day back up power supply for periods of darkness FEATURES Includes 5 watt solar panel mounting hardware and 12V solar charge controller Reliable maintenance free operation Powers Dwyer Instruments Inc flow meters Requires a 22 33 Amp hour Sealed Lead Acid battery APPLICATIONS ...

Страница 2: ...lamps and mounting hardware for 1 1 2 or 2 inch vertical pipe 40 F to 158 F 40 C to 70 C High efficiency series PWM regulator with temperature compensation and built in lightning protection Electrical Current Voltage Dimensions Height Width Weight Mounting Operating Temperature Range Change Controller SPECIFICATIONS Specifications subject to change For powering Dwyer Instruments Inc mechanical met...

Страница 3: ... 20 bolts nuts flat and lock washers to attach the angle bracket to the pipe mount C channel Then attach the entire assembly to the pipe using the two band clamps as shown Turn the panel to face true not magnetic south in the northern hemisphere or north in the southern hemisphere before tightening the clamps securely Connect the solar charge controller flow meter and battery as shown in the wirin...

Страница 4: ... Actual maintenance replacement inter val will depend on local conditions and criticality of data MAINTENANCE WIRING DIAGRAM Dwyer Instruments Inc 102 Indiana Highway 212 Michigan City IN 46360 USA P 219 879 8868 F 219 872 9057 1 800 872 9141 www dwyer inst com WARRANTY RETURN Refer to Terms and Conditions of Sale in our cata log or on our website Contact customer service to receive a Returns Good...

Отзывы: