3: Operating Procedures
28
Calibrating the pulse frequency range
The
Calculated Pulse Value
field is automatically calculated as:
This value is often required to be programmed into the device that is receiving the pulses to enable it to calculate
the correct flow rate – for example, when connecting the pulse output to an energy meter.
1.
With the instrument operating in the
FLOW
READING
mode, press the
Pulse
function key
to access the
PULSE OUTPUT
screen.
2.
Select
Max Pulse Freq (Hz)
and enter the
required value.
3.
Select
Flow at Max Freq
and enter the
required value (gal/min).
4.
Select
Exit
and press the
ENTER
key to return
to the
FLOW READING
screen
PULSE OUTPUT
DD-MM-YY HH:MM:SS
A1 Pulse Frequency is ON
Qxx.xx%
Flow units : gal
Output : Frequency
Vol per pulse : 10.00
Pulse width (ms) : 10
Max Pulse Freq (Hz) : 10.00
Flow at Max Freq : 200.00
Calculated Pulse Value: 20.0
Exit
Calculated Pulse Value
Flow at Max Freq
Max Pulse Freq (Hz)
--------------------------------------------------
=