Dwyer Instruments PROXIMITY VRLS-01 Скачать руководство пользователя страница 3

Output Indication

1.  Before  wiring,  please  select  the  appropriate  input  power  supply  (L+/N-)  20-250
VAC/VDC, 50/60Hz.
When operating in either FSH mode, the output will function as follows:
A. The signal indicator lamp will light up if the level switch detects no material or the
bin is empty. The NO and COM contacts of the relay will be conducting. 
B. The signal indicator lamp will turn off if the level switch detects material. The NC
and COM contacts of the relay will be conducting. 

When operating in either FSL mode, the output will function as follows:
A. The signal indicator lamp will light up if the level switch detects material. The NC
and COM contacts of the relay will be conducting. 
B. The signal indicator lamp will turn off if the level switch detects material. The NC
and COM contacts of the relay will be conducting. 

CHECK OPERATION-VERIFY SWITCH OPERATION

Sensitivity Calibration

In  order  to  adjust  the  sensitivity  of  the  switch,  the  following  procedure  should  be
followed:
1. If level switch has already been installed, confirm sensitivity before materials are
added.
2. By default, the output mode of the switch is set to FSH. This can be adjusted as
needed for each particular application. 
3. Based on the particular application, the sensitivity can be adjusted by rotating the
SENSITIVITY knob to an appropriate selectable sensitivity setting. 

Typically, the sensitivity knob is set as follows:

- SENSITIVITY L: 

Low Sensitivity

- SENSITIVITY H:

High Sensitivity

L: 

Suitable  for  detecting  a  medium  that  has  a  large  volume  or  density  such  as  a

plastic material.

H:

Suitable for detecting a medium that has a smaller volume or density such as rice

bran. 

Installation

When installing VRLS, the following should be noted.

Top Mounting

-Avoid installing directly under substance inlet to prevent damage to the probe.
-Angle of mounting should be taken into consideration during installation to prevent
false alarm.

Side Mounting

-It is highly recommended to use a shield to protect the vibrating probe level switch.
The cover should be parallel to the probe and of the same length.
-Incline the device at approximately 20 degrees when installing.
Keep conduit facing downward to prevent moisture from getting inside the housing
while in operation.
-All wiring should employ 18 AWG cable. 

MAINTENANCE/REPAIR

Upon  final  installation  of  the  Model  VRLS  no  routine  maintenance  is  required. The
Model VRLS is not field serviceable and should be returned if repair is needed. Field
repair should not be attempted and may void warranty.

WARRANTY/RETURN

Refer to “Terms and Conditions of Sales” in our catalog and on our website. Contact
customer service to receive a Return Goods Authorization number before shipping the
product back for repair. Be sure to include a brief description of the problem plus any
additional application notes.

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A. 

Fax: 219/872-9057

e-mail: [email protected]

©Copyright 2014 Dwyer Instruments, Inc.

Printed in U.S.A. 

9

/14

FR# R6-444060-00 Rev. 5

Figure 3 - Failure-Mode Switch

Figure 4 - Diagram of Relay Output

Figure 5 - Side Mounting Installation