Dwyer Instruments OSC-200 Скачать руководство пользователя страница 3

The walk test is used to quickly ensure correct system
wiring, proper functioning of the output, and proper
location of the sensor.

Apply power to the unit and allow 25 seconds for the

sensor to warm up. The LED will blink (long blink followed
by short) during warm up.

The LED will blink rapidly if the sensor is improperly wired.

When the LED stops blinking, the sensor has had

adequate time to warm up and is now in standby mode
(Standby mode is discussed in more detail in the
Operation Mode Section.)

Walk across the detection zone. The LED will stay lit

and the output will be activated during occupancy
detection.  Adjust accordingly.

ON/OFF DELAY SETTINGS

To adjust the On/Off Delay time intervals or adjust sensor
for  “Walk Test”

1. Remove the cover from the sensor.
2. Refer back to Figure 3 to locate the On/Off Delay pins

and jumpers on the circuit board.

3. Gently remove the jumpers and reinsert into the 

desired pins according to the table below.

4. Replace cover and screw.

NOTICE

ON
OFF

A (Walk Test)
0 Sec.
10 Sec.

B
10 Sec.
1 Min.

C
30 Sec.
5 Min.

D
1 Min.
10 Min.

E
5 Min.
20 Min.

F
10 Min.
30 Min.

OPERATION MODES

The OSC-200 Omnidirectional Occupancy Sensor utilizes
several operation modes to eliminate false readings and
conserve energy.

A.

STANDBY

DETECTION

B.

RELAY ON

DELAY

C. 1-MINUITE

WAITING

NO 

DETECTION

DETECTION

D.

RELAY OFF

DELAY

(RELAY OUTPUT)

Figure 4

Standby Mode

Before any movement is being sensed, the sensor is in
standby mode.  

When the sensor detects occupancy, the LED light turns
on and the sensor switches to Relay On Delay Mode.

Relay On Delay Mode

This adjustable mode allows the user to choose the time
delay before the unit reports that a space is occupied.  

The Relay On Delay Mode allows for energy conservation
by bypassing short-term or faulty occupancies. It is
followed by a secondary one minute warning delay.

H-21-OSC:TEMPLATE  2/5/10  11:12 AM  Page 3

Содержание OSC-200

Страница 1: ...ces of furniture curtains etc which may block the detection DWYER INSTRUMENTS INC Phone 219 879 8000 www dwyer inst com P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Fax 219 872 9057 e mail info dwyer inst com SPECIFICATIONS Infrared Sensor Dual element Range 34 4 ft 10 5 m Diameter at 13 8 ft 4 2 m mount height Detectable Speed 0 33 to 9 8 ft sec 0 1 to 3 0 m sec Control Output Rating SPDT 0 2A a...

Страница 2: ... LENS TAB KNOCKOUT HOLES FOR MOUNTING Step 2 Wiring Feed the cable through one of the corner knockout holes Figure 1b Reinsert the circuit board Turn the screw for each terminal counterclockwise Figure 1b Connect the cable to the corresponding terminals as shown in Figure 2 NC COM NO FAN COIL CONTROLLER 24 VAC DC 24V ON OFF INPUT Figure 2 Wiring the Sensor Step 3 Walk Test Before beginning test ma...

Страница 3: ...lay pins and jumpers on the circuit board 3 Gently remove the jumpers and reinsert into the desired pins according to the table below 4 Replace cover and screw NOTICE ON OFF A Walk Test 0 Sec 10 Sec B 10 Sec 1 Min C 30 Sec 5 Min D 1 Min 10 Min E 5 Min 20 Min F 10 Min 30 Min OPERATION MODES The OSC 200 Omnidirectional Occupancy Sensor utilizes several operation modes to eliminate false readings and...

Страница 4: ...description of the problem plus any relevant application notes Contact customer service to receive a return goods authorization number before shipping 1 Minute Warning Mode During this mode the sensor searches for any movement for one minute after the Relay On Delay Mode If occupancy is detected at any point within that one minute the output device is activated and the sensor enters Relay Off Dela...

Отзывы: