The Model OSC-200 Omnidirectional Occupancy
Sensor 

automatically controls a HVAC ventilation system.

A spherical Fresnel lens provides a 360° detection zone
with the use of infrared technology. The integrated dual
delay processor saves energy by eliminating false
activation due to short-term occupancies. The Model
OSC-200 is designed to be ceiling mounted.

INSTALLATION

Do not install where the detector is exposed to direct
sunlight or directly above strong sources of heat.

Do not install in areas that have any obstruction
(plants, large pieces of furniture, curtains, etc.) which
may block the detection.

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A. 

Fax: 219/872-9057

e-mail: [email protected]

SPECIFICATIONS
Infrared Sensor:

Dual element.

Range: 

34.4 ft (10.5 m) Diameter at 13.8 ft (4.2 m) mount

height.

Detectable Speed: 

0.33 to 9.8 ft/sec (0.1 to 3.0 m/sec).

Control Output Rating:

SPDT, 0.2A at 30 VDC.

Ambient Operating Temperature:

-4 to 140°F (-20 to 60°C).

Power Consumption:

Standby: 5 mA, Operating: 18 mA. 

Mounting Height:

7.9 to 13.8 ft (2.4 to 4.2 m).

Power Requirements: 

22 to 26 VAC/DC.

Weight:

2.4 oz (68 g).

Agency Approvals:

CE.

Specifications - Installation and Operating Instructions

Model OSC-200 Omnidirectional Occupancy Sensor

Ø4-11/32

[Ø110.33]

1-47/64

[44.05]

H-21-OSC:TEMPLATE  2/5/10  11:12 AM  Page 1

Содержание OSC-200

Страница 1: ...ces of furniture curtains etc which may block the detection DWYER INSTRUMENTS INC Phone 219 879 8000 www dwyer inst com P O BOX 373 MICHIGAN CITY INDIANA 46361 U S A Fax 219 872 9057 e mail info dwyer inst com SPECIFICATIONS Infrared Sensor Dual element Range 34 4 ft 10 5 m Diameter at 13 8 ft 4 2 m mount height Detectable Speed 0 33 to 9 8 ft sec 0 1 to 3 0 m sec Control Output Rating SPDT 0 2A a...

Страница 2: ... LENS TAB KNOCKOUT HOLES FOR MOUNTING Step 2 Wiring Feed the cable through one of the corner knockout holes Figure 1b Reinsert the circuit board Turn the screw for each terminal counterclockwise Figure 1b Connect the cable to the corresponding terminals as shown in Figure 2 NC COM NO FAN COIL CONTROLLER 24 VAC DC 24V ON OFF INPUT Figure 2 Wiring the Sensor Step 3 Walk Test Before beginning test ma...

Страница 3: ...lay pins and jumpers on the circuit board 3 Gently remove the jumpers and reinsert into the desired pins according to the table below 4 Replace cover and screw NOTICE ON OFF A Walk Test 0 Sec 10 Sec B 10 Sec 1 Min C 30 Sec 5 Min D 1 Min 10 Min E 5 Min 20 Min F 10 Min 30 Min OPERATION MODES The OSC 200 Omnidirectional Occupancy Sensor utilizes several operation modes to eliminate false readings and...

Страница 4: ...description of the problem plus any relevant application notes Contact customer service to receive a return goods authorization number before shipping 1 Minute Warning Mode During this mode the sensor searches for any movement for one minute after the Relay On Delay Mode If occupancy is detected at any point within that one minute the output device is activated and the sensor enters Relay Off Dela...

Отзывы: