OUTPUT CALIBRATION

1. Adjust the input frequency at least 15% below the maximum desired
input value, then adjust the input frequency for the desired MAXIMUM
output value.
2. Press the CAL switch.  The red IN LED will turn off, and the yellow OUT
LED will stop flashing and stay on.
3. Adjust the input frequency at least 15% above the minimum desired
input value, and then adjust the input frequency for the desired MINIMUM
output value.
4. Press the CAL switch.  The yellow OUT LED will turn off and the cali-
bration values will be stored in nonvolatile memory.

If the red and yellow LEDs flash after calibration, an error condition exits,
i.e. the input or output span was set too small, or the minimum/maximum
values were reversed.
If it is desired to retain the previous calibration values and exit calibration,
simply remove power to the unit before pressing the CAL switch at the
minimum input or output step.

Содержание LOVE Iso Verter II SC478

Страница 1: ...Dwyer Instruments Incorporated PO Box 338 Michigan City IN 46361 0338 800 828 4588 219 879 8000 FAX 219 872 9057 www love controls com LOVE CONTROLS LOVE 1 Delta Park Blvd 12 Brampton ON L6T 5G1 Tel...

Страница 2: ...INSTRUMENTS INC ALL RIGHTS RESERVED PRINTED IN U S A Contents DESCRIPTION 3 OUTPUT PROGRAMMING HARDWARE 3 MODE SELECTION SWITCH BANK SW 3 3 RANGE SELECTION SWITCH BANK SW 4 4 MOUNTING 4 WIRING 4 CALIB...

Страница 3: ...uencies between 1000 Hz to 10 000 Hz the minimum span is 2 Hz This allows the input to be pro grammed for almost any desired span i e 10 to 15 Hz 3456 to 5678 Hz or 9998 to 10 000 Hz Output Selection...

Страница 4: ...tional surface mounting kit is available from the factory P N 35DINADPTR To install hold the SC478 so that the front is higher than the rear Place the upper slot on the rear of the SC478 on the top ed...

Страница 5: ...LED will light Note if the LEDs were flashing due to a previous error condition they will stop and allow calibration to continue 3 Input the MINIMUM desired frequency 4 Press the CAL switch the yellow...

Страница 6: ...desired input value and then adjust the input frequency for the desired MINIMUM output value 4 Press the CAL switch The yellow OUT LED will turn off and the cali bration values will be stored in nonv...

Страница 7: ...1 Drift 0 02 per C typical 0 05 maximum Maximum current output load 600 ohms Maximum voltage output load 20mA 500 ohms Input Type Frequency Full scale range 1 to 10 000 Hz Input impedence 50 Kohms Inp...

Страница 8: ...rated PO Box 338 Michigan City IN 46361 0338 800 828 4588 219 879 8000 FAX 219 872 9057 www love controls com LOVE CONTROLS LOVE 1 Delta Park Blvd 12 Brampton ON L6T 5G1 Tel 905 457 6322 or 1 800 794...

Отзывы: