PAIRING WIRELESS PROBES
1. Turn on Model UHH Universal Handheld by pressing the button.
2. Press the and buttons to scroll through the menu headings at the top of the
display.
3. When
PROBE
is highlighted, hit the button to access the probe menu.
4. Press the to scroll through the sub-menu headings. The current selected
parameter will be highlighted in yellow.
5. When
PAIRING MODE
is highlighted, hit the button to access the pairing mode.
6. Turn on the wireless probe(s) to be paired. After a period of up to 15 to 20 seconds,
the UHH screen will update with the information about the wireless probe(s) just
turned on.
7. Press the button to scroll through the available probes. The current selected
probe will be highlighted in yellow.
8. When desired probe to be paired is highlighted, hit the button to pair the probe.
Once it is paired, it will be removed from the list automatically.
9. Once all the desired probes are paired, press button.
10. Repeat step 9 to go back to the home screen and begin readings.
SELECTING A PROBE
In order to cycle through the probes that are paired to the Model UHH Universal
Handheld, press the or button while in the view data mode.
SETTINGS
When using the Model VP2 Wireless 100 mm Thermo-Anemometer Probe, the base
unit can display velocity or air flow along with temperature and humidity. The settings
allow users to select velocity or air flow, engineering units, measurement range, and
which parameters to show on the display. To access the setting menus:
1. Press the or arrows to scroll through the menu headings at the top of the
display.
2. When
PROBE
is highlighted, hit the button to access the probe menu.
3. Press the arrow to scroll through the sub-menu headings. The currently selected
parameter will be highlighted in yellow.
Flow / Velocity Selection
1. When sub-menu
TYPE
(next to Anemometer) is highlighted, hit the button to
access the settings for the sub-menu.
2. Press the arrow to scroll through the parameters. The currently selected
parameter will be highlighted in yellow.
3. When
DISPLAY
is highlighted, press the button and velocity or vol. flow will be
highlighted.
4. Pressing the or buttons will alternate between velocity and vol. flow.
5. Once the desired selection is made, press button.
Units Selection
1. When sub-menu
TYPE
(next to Anemometer, Humidity or Temperature) is
highlighted, hit the button to access the settings sub-menu.
2. Press the arrow to scroll through the parameter headings. The currently selected
parameter will be highlighted in yellow.
3. When
UNITS
is highlighted, press the button and the current units will be
highlighted.
4. Pressing the or buttons will cycle through the available units.
5. Once the desired selection is made, press button.
Area Adjustment (Only when Display is set to Volumetric Flow)
1. When sub-menu
TYPE
(next to Anemometer) is highlighted, hit the button to
access the settings sub-menu.
2. Press the arrow to scroll through the parameter headings. The currently selected
parameter will be highlighted in yellow.
3. When
AREA
is highlighted, press the button to enter a new submenu that allows
selection of the shape of the duct, engineering units in which the duct is measured,
and the dimensions of the duct.
4. Press the arrow to scroll through the parameter headings. The currently selected
parameter will be highlighted in yellow.
5. When the desired menu is highlighted, press the button and the current value
of the parameter will be highlighted.
6. Pressing the or buttons will cycle through the available options for each
parameter.
7. Once the desired selection is made, press button.
8. After all of the area parameters are entered, press button.
Display Measurements
1. When
SOURCE
is highlighted, press the button and the measurement type
selected will be highlighted.
2. Pressing the or buttons will cycle through the available parameters.
3. Once the desired selection is made, press button.
4. In order to turn off the secondary displays, use the and to select the
measurement type that is not selected for the
SOURCE
.
5. When the desired
TYPE
is highlighted, hit the button to access the settings
sub-menu.
6. Press the arrow to scroll through the parameter headings. The currently selected
parameter will be highlighted in yellow.
7. When
VISIBLE
is highlighted, press the button and either ON or OFF will be
highlighted. The measurement will be displayed when set to ON and not displayed
when set to OFF.
8. Pressing the or buttons will alternate between ON and OFF.
9. Once the desired selection is made, press button.
The measurements on the
MAJOR
display will always be
displayed, but the measurements on the secondary displays
can be turned off.
NOTICE
If a probe does not appear, power the probe down, then power
it back on.
NOTICE