Inductive Loads

Possible causes

-

An  electromagnetic  relay,  electromagnetic
solenoid, electromagnetic counter with inductive
component as circuit load.

Capacitive Loads

Possible causes 

-

A capacitor connected in series or parallel with
Reed Switch control. In a closed circuit, a cable
length  (usually  greater  than  50m  [162.5  ft.])
used to connect reed switch may also introduce
static capacitance.

Lamp Loads

Possible causes

A tungsten filament lamp load.

©Copyright 2014 Dwyer Instruments, Inc.

Printed in U.S.A.  7/14

FR# 82-440677-00 Rev. 5

Installation  Notes

-  Do  not  subject

reed  switch  controls  to  excessive
shock  or  vibration  or  any  of  the
following: 
• Bending or placing force loads on 

reed switch housing.

• Over-torquing fittings on reed 

switch housing.

• Placing pull-out force on lead wires.

CIRCUIT INFORMATION FOR REED SWITCH PROTECTION
Read information below before installing your new reed switch control!

Exceeding the current capacity of this Reed Switch control may cause FAULTY OPERATION! Be aware of the inductive and capacitive or lamp loads you may be placing on
you Reed Switch Control. The circuits below outline possible solutions to preventing overloads due to inrush or surge currents exceeding maximum or when the switch current
and product of the inductive back EMF exceed the switch’s power rating. Also the circuit for prevention of overload when switching filament lamps (low “cold” resistance) is
outlined below. Failure to follow these measures to protect Reed Switch Contacts may cause the contacts to weld together or result in premature wear.

Indicating arrows are 
provided on the stem
ends to confirm float 
alignment.

Do not exceed 1.5 pounds/
foot (2 n/m) tightening
torque. Excessive torque
may cause premature switch
element or housing failure.

Avoid installations where
wiring entering the device is 
submerged or exposed to
excessive amounts of liquid 
or humidity condensate.

Gasket seal for internal
mounting units should be pre-
assembled before insertion 
through tank wall. Wall thick-
ness should not exceed 1/8"
(3 mm).

When preparing wires for
termination, avoid pulling
against the resin seal or 
end plug of the float switch.

Units with tapered pipe 
threads should be treated 
with Teflon based thread 
compound or tape before
insertion in fitting. Sufficient 
torque is achieved at hand-
tight plus one half turn.

Possible Circuit Solutions Indicated by Dashed Lines

DIODE SUPPRESSION

DIODE

INDUCTIVE

LOAD

PIV DIODE > V

REED

SWITCH

REED

SWITCH

USED IN

AC CIRCUITS

VARISTER

VARISTER PROTECTION

INDUCTIVE

LOAD

RC SUPPRESSION

R

C

INDUCTIVE PROTECTION FOR

CABLE LENGTH CAPACITANCE

LOAD

REED

SWITCH

Cable Length

over 50 meters

[162.5 ft.]

REED

SWITCH

RESISTOR PROTECTION

FOR CAPACITIVE LOAD

SURGE LIMITER FOR

CAPACITANCE IN SERIES

REED

SWITCH

CURRENT LIMITING RESISTOR

IN SERIES

CURRENT LIMITING RESISTOR

IN PARALLEL

REED

SWITCH

REED

SWITCH

INDUCTIVE

LOAD

REED

SWITCH

SWITCH

[uf]

10

C

R

10*I

(1+50/E)

SWITCH

2

C

LOAD

SWITCH

SWITCH

LOAD

C

R

L  =0.5

~

5 mH

P

+V

R

A

P

L

R

A

+V

R = 50~500 Ohms

R

B

P

L

L  = 0.5~5 mH

P

+V

R

L

R

R

V-0.12 R

L

2

+V

R

L

5R  >  R

L

R

DWYER INSTRUMENTS, INC.   

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46360, U.S.A.     Fax: 219/872-9057

e-mail: [email protected]

1.800.868.7495

QualityInstruments-Direct

.ca