Dwyer Instruments DS-300 Series Скачать руководство пользователя страница 2

LP

HP

1-7/16 (36.53)

SENSOR

FLOW

PIPE

1/16 (1.59)

CLEARANCE

HP

LP

LP DRAIN

HP DRAIN

0

.20

.40

.60

.80

1.0

INCHES OF WATER

CAPSUHELIC

®

MAX. OPERATING PRESS. 500 PSIG

ZERO SET

D W Y E R   I N S T R U M E N T S ,   I N C .   M I C H I G A N   C I T Y,   I N D I A N A   4 6 3 6 0   U . S . A .

UPPER PIPE

QUADRANT

LOWER PIPE

QUADRANT

For Air or Gas Flow

Install in upper
quadrant of pipe

Condensate drains

back to pipe

For Liquid or Steam Flow

Install in lower
quadrant of pipe

Air bleeds

back to pipe

LP BLEED

HP BLEED

PIPE

1/16 (1.59)

CLEARANCE

FLOW

SENSOR

1-7/16 (36.53)

LP

HP

HP

LP

INCHES OF WATER

CAPSUHELIC

®

ZERO SET

MAX. OPERATING PRESS. 500 PSIG

.60

.80

1.0

.40

.20

0

DWYER INSTRUMENTS, INC MICHIGAN CITY, INDIANA 46360 U.S.A.

Water Flow

Air or Gas Flow

INSTALLATION

1. When using an A-160 thred-o-let, weld it to the pipe wall.
If replacing a DS-200 unit, an A-161 bushing (1/4˝ x 3/8˝) will
be needed. 

2. Drill through center of the thred-o-let into the pipe with a
drill that is slightly larger than the flow sensor diameter. 

3. Install the packing gland using proper pipe sealant. If the
packing gland is disassembled, note that the tapered end of
the ferrule goes into the fitting body.

4. Insert sensor until it bottoms against opposite wall of the
pipe, then withdraw 1/16˝ to allow for thermal expansion.

5. Tighten packing gland nut finger tight. Then tighten 
nut with a wrench an additional 1-1/4 turns. Be sure to hold
the sensor body with a second wrench to prevent the
sensor from turning.

INSTRUMENT CONNECTION

Connect the slide pressure tap to the high pressure port of
the Magnehelic

®

(air only) or Capsuhelic

®

gage or

transmitting instrument and the top connection to the low
pressure port.

See the connection schematics below.

Bleed air from instrument piping on liquid flows. Drain any
condensate from the instrument piping on air and gas flows. 

Open valves to instrument to place flow meter into service.
For permanent installations, a 3-valve manifold is
recommended to allow the gage to be zero checked
without interrupting the flow. The Dwyer A-471 Portable
Test Kit includes such a device. 

POSITION

Be certain there is sufficient clearance between the
mounting position and other pipes, walls, structures, etc, so
that the sensor can be inserted through the mounting unit
once the mounting unit has been installed onto the pipe.

Flow sensors should be positioned to keep air out of the
instrument connecting lines on liquid flows and condensate
out of the lines on gas flows. The easiest way to assure this
is to install the sensor into the pipe so that air will bleed into,
or condensate will drain back to, the pipe.

REVISEDBulletin F-50  7/8/04  8:04 AM  Page 2

1.800.868.7495

QualityInstruments-Direct

.ca

Содержание DS-300 Series

Страница 1: ... pointed upstream The top connection is for static or low pressure Location The sensor should be installed in the flowing line with as much straight run of pipe upstream as possible A rule of thumb is to allow 10 15 pipe diameters upstream and 5 downstream The table below lists recommended up and down piping PRESSURE AND TEMPERATURE Maximum 200 psig 13 78 bar at 200 F 93 3 C Series DS 300 Flow Sen...

Страница 2: ...6 to allow for thermal expansion 5 Tighten packing gland nut finger tight Then tighten nut with a wrench an additional 1 1 4 turns Be sure to hold the sensor body with a second wrench to prevent the sensor from turning INSTRUMENT CONNECTION Connect the slide pressure tap to the high pressure port of the Magnehelic air only or Capsuhelic gage or transmitting instrument and the top connection to the...

Страница 3: ...e the differential pressure readings being sensed into the equivalent flow rate When direct readout of flow is required use this information to calculate the full flow differential pressure in order to specify the exact range of Dwyer Magnehelic or Capsuhelic gage required Special ranges and calculations are available for these gages at minimal extra cost See bulletins A 30 and F 41 for additional...

Страница 4: ...ssure expressed in inches of water column Q Flow expressed in GPM SCFM or PPH as shown in equation K Flow coefficient See values tabulated on Pg 3 D Inside diameter of line size expressed in inches For square or rectangular ducts use D 4 x Height x Width π P Static Line pressure psia T Temperature in degrees Fahrenheit plus 460 Rankine p Density of medium in pounds per square foot Sf Sp Gr at flow...

Отзывы: