Dwyer Instruments ADPS-08-2-N Скачать руководство пользователя страница 2

electrical connection

Work  on  electrical  installations  must  only  be  carried  out  by  electricians  who  are
specifically trained for this purpose. 

First make sure that there is no voltage on the connecting cable
while you are working on the electrical connections. Otherwise,

a  possible  electric  shock  may  result  and  the  connected  equipment  may  be
damaged.  The  connecting  cable  can  be  run  to  the  pressure  switch  from  three
sides, according to choice. The screw cable connection has a plug-in design for
this purpose. Rotate protective cover accordingly.

For  cable  gland  models,  the  seal  in  the  screw  cable  connection  is  designed  for
cables with alternative sheath diameters of 0.275˝ (7 mm) or 0.393˝ (10 mm). Only
use these sizes – otherwise the screw cable connection cannot seal adequately.

1. If using a 0.275˝ (7 mm) connecting cable, you can line up the press nut, the 
plain washer and the sealing ring directly on the cable.

2. If using a 0.393˝ (10 mm) connecting cable, you must first break the inner 
rubber ring out of the sealing ring directly on the cable. Then line up the press 
nut, the plain washer and the sealing ring on the cable.

Wiring

The switching device in this pressure switch is designed as a change-over contact
as can be seen from the wiring diagram (Figure 1). The rest position is shown in
Figure 1 (pressure below the activation switch point on dial).

1. In the instance where pole 3 (COM) closes to Pole 2, the pressure is 
increasing (NO).

2. In the instance where pole 3 (COM) closes to Pole 1, the pressure is 
decreasing (NC).

Protect the feed line (to pole 3) by fuse, either in control system or along the line,
and do so with: 

1. Max. 1.5 A / 250 VAC, if you are loading the contact with an resistive load;

2. Max 0.4 A / 250 VAC, if you are loading the contact with an inductive load 
(such as relay);

3. Max. 0.1 A / 24 VDC, if you are using the pressure switch in the weak current 
version with gold-plated contacts.

The connections are intended for crimp-type sockets, 0.25 in (6.3 mm).

1. Make sure the crimp connection is perfect, and that the cable lugs fit properly 
on to the connections.

2. If you do not have any crimp-type sockets available, you can also use the 
cable lugs which are supplied with mounted screw terminals. However, these 
are only intended for rigid copper wire.

3. On flex, it is either necessary to crimp on strand end sleeves – and then you 
can also screw the strands on – or to crimp cable lugs on directly as previously 
described.

©Copyright 2014 Dwyer Instruments, Inc.

Printed in U.S.A. 6/14

FR# R1-443602-00 Rev. 2

Setting the pressure Range

Make  absolutely  certain  that  there  is  no  voltage  on  the  electrical  connections
before you carry out any setting on the pressure switch. Otherwise, it could be fatal
if  you  accidentally  touch  the  electrical  connections  or  the  metal  adjusting  screw
while you are performing the settings.

a) Use the adjustment dial to set the pressure which should trip the switch on an
increase of pressure.

1. The indications on the dial are only correct for the vertical mounting position.

2. When the pressure falls, the switch returns to its resting position as soon as 
the pressure falls below the dead band.

attaching cover

a) Insert the screw cable connection into the recess provided for this purpose on
the housing.

b) Then place the housing cover in position and screw it down evenly on to the
pressure switch.

testing the Setting

Do  not  operate  the  system  until  the  housing  is  closed.  Otherwise  there  is  the
possibility of an electric shock if you accidentally touch live parts.
Check  the  trip  and  reset  pressures  by  slowly  increasing  the  pressure  and  then
allowing it to fall again.

iMpoRtant:

Observe  the  maximum  permissible  operating  pressure  of  40˝  w.c.

(10 kPa) which is indicated in the data sheet. Otherwise the pressure switch may
be damaged.

Maintenance

Upon final installation of the Series ADPS Adjustable Differential Pressure Switch,
no  routine  maintenance  is  required.  A  periodic  check  of  system  operation  is
recommended. The Series ADPS is not field serviceable and should be returned if
repair is needed (field repair should not be attempted and may void warranty). Be
sure  to  include  a  brief  description  of  the  problem  plus  any  relevant  application
notes. Contact customer service to receive a return goods authorization number
before shipping.

DWYeR inStRUMentS, inc. 

phone: 219/879-8000

www.dwyer-inst.com

p.o. BoX 373 • MicHiGan citY, inDiana 46360, U.S.a. 

fax: 219/872-9057

e-mail: [email protected]

caUtion

1

2

3

2 NO

1 NC

P

3 COM

figure 1

1. Break Contact
2. Operating Contact
3. Power Supply Line

1.800.868.7495

QualityInstruments-Direct

.ca

Отзывы: