Dwyer Instruments ADPS-08-2-N Скачать руководство пользователя страница 1

Series aDpS Differential pressure Switch

Specifications - installation and operating instructions

Bulletin e-80-aDpS

the  Series  aDpS  adjustable  Differential  pressure  Switch 

is  designed  for

overpressure,  vacuum,  and  differential  pressure  applications.  The  scaled
adjustment knob allows changes to the switching pressure to be made without a
pressure gage. The ADPS is available with settings from 0.08˝ w.c. (20 Pa) to 20˝
w.c. (5000 Pa). The silicone diaphragm and PA 6.6 body make the Series ADPS
perfect for use with air and other noncombustible gases. The Series ADPS can be
used  in  monitoring  air  filters,  ventilators,  and  industrial  cooling-air  circuits  along
with controlling air and fire-protection flaps and many other applications.

Use  only  with  mediums  such  as  air,  or  other  noncombustible  or  non-aggressive
gases. Otherwise operating faults or accidents may occur.

Mounting Switch

First check the pressure switch to ascertain whether any damage is visible on the
housing. If the housing is leaky because of damage, the pressure switch must not
be used.
Switching  pressure  specifications  apply  to  vertical  installation  which  is  also  the
recommended position with pressure connections pointing downwards. 
Only if there is no potential for condensate forming can you mount the pressure
switch horizontally. In this case, however, the switching values are approximately
0.08 in w.c. (20 Pa) higher as indicated on the scale. In the horizontal position, the
pressure  switch  should  be  mounted  ‘lying  down’  only  (that  is  to  say  with  the
electrical  connections  pointing  upwards).  Do  not  mount  the  pressure  switch  in  a
hanging  position  (that  is  to  say,  not  ‘overhead’  with  the  electrical  connections
pointing downwards). Otherwise the device will function inaccurately. 

a) Mounting with screws or brackets 

1. To mount the pressure switch, L-shaped A-288 and S-shaped A-289 
mounting brackets can be ordered separately. To secure the device on the rear 
side of the housing, only use the sheet metal screws (3.5 x 8 mm) which are 
supplied together with the mounting brackets. Under no circumstances must 
you use longer screws. Otherwise, the base of the housing could be punctured 
resulting in the pressure switch leaking.

2. You can also mount the pressure switch directly on a wall. To do this use 
screws with a maximum diameter of 0.315˝ (8.0 mm), if you use the outer 
mounting lugs to screw the device in place. Do not tighten the screws so much 
that the base of the device is deformed. Otherwise, the pressure switch can be 
shifted out of position, or leak.

installing Hoses
important:

Pressure tubing cannot be kinked. Pay particular attention to this point

if you run hoses over an edge. It is better to form a loop. If the hoses are kinked,
the device cannot function accurately.

a) For connection to the pressure switch two fittings inherent in the housing are
provided for hoses with an internal diameter of 1/4˝ (6.0 mm).

1. Connect a hose with the higher pressure to socket P1 which is located on the 
lower section of the housing.

2. Connect a hose with the lower pressure to socket P2 which is located on the 
middle section of the housing.

After  you  have  installed  the  hoses,  it  is  absolutely  essential  to  check  them  for
tightness of fit at the connection points and to make sure that they run without any
kinks. 

DWYeR inStRUMentS, inc. 

phone: 219/879-8000

www.dwyer-inst.com

p.o. BoX 373 • MicHiGan citY, inDiana 46360, U.S.a. 

fax: 219/872-9057

e-mail: [email protected]

SpecificationS
Service: 

Air and noncombustible, compatible gases.

Wetted Materials: 

Diaphragm material: Silicone; Housing material & switch body:

POM and PA 6.6; Cover: Polystyrene.

temperature Limits: 

Process ambient temperature from -4 to 185˚F 

(-20 to 85˚C). 

pressure Limits: 

Max. Operating Pressure: 40” W.C. (10 kPa) for all pressure

ranges.

Switch type: 

Single-pole double-throw (SPDT).

Repeatability: 

±15% FS.

electrical Rating: 

Standard: Max., 1.5A/250 VAC, max. switching rate: 6

cycles/min.; Gold Contact Option: 0.1 A/ 24 VDC.

electrical connections: 

Push-on screw terminals. M20x1.5 with cable strain

relief or optional 1/2˝ NPT connection.

process connections: 

5/16˝ (7.94 mm) outside diameter tubing, 1/4˝ (6.0 mm)

inside diameter tubing. 

Mounting orientation: 

Vertically, with pressure connections pointing downwards.

Mechanical Working Life: 

Over 10

6

switching operations. 

Weight: 

5.6 oz (160 g).

enclosure Rating: 

IP54.

agency approvals: 

CE, RoHS.

Ø11/64

[Ø4.5]

21/64

[8.5]

2-17/64

[57.5]

7/8

[22]

2-21/64

[59]

19/64

[7.5]

51/64

[18]

-

(P2)

+

(P1)

Ø15/64

[Ø6]

2-9/16

[65]

1-31/32

[50]

1.800.868.7495

QualityInstruments-Direct

.ca

Отзывы: