background image

PRESSURE RE-RANGING PROCEDURE

1

. With the transmitter correctly connected to the com-

panion receiver, an accurate milliameter with a full scale

reading of approximately 30 mA should be inserted in

series with the current loop.  A controllable pressure

source capable of achieving the desired range should be

connected to the pressure port of the transmitter and teed

into an accurate reference pressure gauge or manometer.

The instrument must be ranged in the same position in

which it will be used.  Vertical mounting is recommended.

2

.  Apply electrical power to the system and allow it to

stabilize for 10 minutes.

3

.  With no pressure applied to the transmitter, adjust

“zero” control so that loop current is 4 mA.

4

.  Apply full range pressure and adjust loop current to 20

mA using “span” control.

5

.  Relieve pressure and allow transmitter to stabilize for

two minutes.

6

.  Zero and span adjustments may be interactive, so

repeat steps 3 through 5 until zero and full range pres-

sures consistently produce loop currents of 4 and 20 mA

respectively.

7

.  Remove the milliameter from the current loop and pro-

ceed with final installation of the transmitter and receiver.  

MULTIPLE RECEIVER INSTALLATION

An advantage of the standard 4-20 mA output signal pro-
vided by the Series 634ES Pressure Transmitter is that
any number of receivers can be connected in series in the
current loop.  Thus, an A-701 Digital Readout Accessory,
an analog panel meter, a chart recorder, process control-
ling equipment, or any combination of these devices can
be operated simultaneously.  It is only necessary that
these devices all be equipped with a standard 4-20 mA
input and that proper polarity of the input connections be
observed when inserting the device in the current loop.  If
any of the receiving devices displays a negative or down-
scale reading, this indicates that the signal input leads are
reversed.

MAINTENANCE

Upon final installation of the Series 634ES Transmitter and
the companion receiver, including the A-701 Digital
Readout, no routine maintenance is required.  A periodic
check of system calibration is recommended.  The Series
634ES Pressure Transmitter is not field serviceable and
should be returned, freight prepaid, to the factory if repair
is required.  The A-701 Digital Readout should be
returned to the manufacturer if service is needed.  Refer
to the A-701 instruction sheet.

©Copyright 2002 Dwyer Instruments, Inc.

Printed in U.S.A. 6/02

FR# 01-440577-04, Rev. 3

Series 634ES Pressure Transmitter

Specifications - Installation and Operating Instructions

Bulletin E-69ES

Page 4

DWYER INSTRUMENTS, INC.

Phone: 219/879-8000

www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, INDIANA 46361, U.S.A.

Fax: 219/872-9057  

e-mail: [email protected]

Lit-By Fax: 888/891-4963

E-69ES (634ES)-4.0  6/26/02  11:05 AM  Page 4

Содержание 634ES Series

Страница 1: ...2 oz 8 kg Span and Zero Adjustments Protected potentiome ters located in auxiliary housing Pressure Connection 1 4 female NPT x 1 2 male NPT PERFORMANCE AT 70 F 21 1 C Zero Output 4 mA DC Full Span 16 mA DC Accuracy 0 5 of span Warm up Time 10 minutes STABILITY ENVIRONMENTAL Operating Temperature 20 to 120 F 6 7 to 48 9 C Thermal Errors 0 02 F typical Stability 1 F S yr STANDARD ACCESSORIES 3 Z mo...

Страница 2: ...CAUTION DO NOT EXCEED SPECIFIED SUPPLY VOLT AGE RATINGS PERMANENT DAMAGE NOT COVERED BY WARRANTY WILL RESULT THIS UNIT IS NOT DESIGNED FOR AC VOLTAGE OPERATION Electrical connections to the Series 634ES Transmitter are made inside the enclosure Remove the cover feed stripped and tinned leads through the conduit opening and connect to terminal block screws marked and See Figure A for locations of t...

Страница 3: ...letin E 69ES Page 3 OPERATING REGION MAXIMUM VALUE 1100 TOTAL RECEIVER RESISTANCE Vps 12 3 20mA DC WIRE LENGTH The maximum length of wire connect ing transmitter and receiver is a function of wire size and receiver resistance Wiring should not contribute more than 10 of receiver resistance to total loop resistance For extremely long runs over 1000 feet choose receivers with higher resistances to m...

Страница 4: ...ter is that any number of receivers can be connected in series in the current loop Thus an A 701 Digital Readout Accessory an analog panel meter a chart recorder process control ling equipment or any combination of these devices can be operated simultaneously It is only necessary that these devices all be equipped with a standard 4 20 mA input and that proper polarity of the input connections be o...

Отзывы: