ELECTRICAL CONNECTIONS

Shielded cable is recommended for control loop wiring. Electrical connections to the 

Series 629C pressure transmitters are made to the terminal block located inside the 

housing. Remove the screws and lift off the cover. Wire as shown in Figure 3 or 4. Use 

Figure 3 for current output connection. Use Figure 4 for current output with optional 

LCD  display.  If  ordering  pre-wired  cable,  black  wire  is  negative  (-)  and  red  wire  is 

positive (+).

Wire Length – 

The maximum length of wire connecting transmitter and receiver is 

a function of wire size and receiver resistance. Wiring should not contribute to more 

than 10% of receiver resistance to total loop resistance. For extremely long runs (over 

1000 ft or 305 m), choose receivers with higher resistance to minimize size and cost 

of connecting leads. When wiring length is under 100 ft (30.5 m), lead wire as small 

as 22 AWG can be used.

Current (4 to 20 mA) Output Operation 

– An external power supply delivering 10 to 

35 VDC with minimum current capability of 40 mA DC (per transmitter) is required to 

power the control loop. See Figure 3 for connection of the power supply, transmitter, 

and receiver. The range of the appropriate receiver load resistance (RL) for the DC 

power supply voltage available is expressed by the formula

INSTALLATION

1.  Location: 

Select a location where the temperature of the unit will be between 

0 and 200°F (-18 to 93°C). Distance from the receiver is limited only by total loop 

resistance (see electrical connections). The tubing feeding pressure to the instrument 

can be practically any length required, but long lengths will increase the response 

time slightly. Mount the instrument in a location that will not be subject to excessive 

temperature, shock, or vibration.

2.  Position:

 A vertical position is recommended (pressure connections pointing 

horizontally) since that is how all standard models are spanned and zeroed at the 

factory.  They  can  be  used  at  other  angles,  but  may  require  final  zeroing.  Due  to 

potential condensation buildup that may travel down conduit or cable and into the 

housing, it is recommended to install with the electrical conduit or cable gland pointing 

downward.

3. Pressure Connection:

 Dual 1/4“ NPT pressure connections are provided. Use pipe 

thread sealant tape or other suitable pipe joint compound when making connection to 

the pressure source. Avoid excess sealant which could block the pressure passage. 

When monitoring liquid pressures, air trapped in the lines can cause incorrect readings. 

Bleed fittings or similar mechanisms should be used to bleed off any trapped air.

Optional 3-Way Valve

For applications where higher line pressures may be encountered at installation or 

when it is necessary to remove the transmitter for maintenance without interrupting the 

process, the optional three way valve is recommended. (See Figure 1)

Installation with 3-way valve option. Begin with valve V1 open and valves V2 and 

V3 closed. (See Figure 2) Slowly open valves V2 and V3. Once the pressure has 

stabilized and is equal on the high and low side of the transmitter, valve V1 can be 

closed and normal operation can proceed.

To  ensure  proper  pressures  will  be  detected  by  the  629C,  use  the  bleed  fittings 

provided with this package to free media of bubbles. Before applying pressure to the 

process connections, turn V1 to the open position and back off either the low or high 

side bleed hex nut. Next, apply pressure. After the flowing liquid is free of bubbles, 

retighten the bleed hex nut.

Before removing the transmitter from operation, open valve V1, then close valves V2 

and V3.

7-17/64 [184.66]

2-13/32

[60.96]

3-63/64

[101.02]

5-19/32

[142.11]

4-17/64

[108.33]

2-25/64

[60.84]

3 [76.19]

1-37/64

[40.14]

PRESSURE

TRANSMITTER

1

RECEIVER

2
3
4

SHIELD

COM

VIN

+

-

+

-

POWER

SUPPLY

10-35 VDC

WHITE

YELLOW

ORANGE

BLUE

BLACK

RED

SHIELD [TERM #4]

Com [TERM #2]

Vin [TERM #1]

POWER

SUPPLY

10-35 VDC

-

+

RECEIVER

-

+

LCD CONNECTOR

HI [+]

PRESSURE

CONNECTION

LOW [-]

PRESSURE

CONNECTION

UNIT BUTTON-PRESS TO TOGGLE THE

UNIT [PSID/BARD] ON THE LCD

ZERO BUTTON- PRESS AND

HOLD TO ZERO THE GAGE

TRANSMITTER CONNECTION INSTRUCTION:

- TURN OFF POWER SUPPLY.

- CONNECT THE POWER SUPPLY AND RECEIEVER TO Vin [TERM  #1] AND Com 

  [TERM #2] OF THE GAGE AS SHOWN.

- INSTALL THE LCD'S CONNECTOR TO THE GAGE AS SHOWN.

- TURN ON POWER.

CAUTION:  BE SURE TO TURN OFF POWER WHEN CONNECTING OR REMOVING

THE LCD CONNECTOR. FAILURE TO DO SO CAN RESULT IN GAGE DAMAGE.

Figure 1: 629C with Optional 3-Way Valve

Figure 2: Bleed Fitting Connections

Figure 3: Current Output Connection

Figure 4: Current Output with Optional LCD

BLEED FITTING

HIGH SIDE

BLEED FITTING

LOW SIDE

R

L

 max = 

vps - 10

20 mA DC

www.

GlobalTestSupply

.com