The Series 605 Magnehelic

®

Indicating Transmitter 

simultaneously

provides local indication on a large, easily read analog scale while also
converting that pressure into a standard two-wire, 4-20 mA signal for
ranges from 0-0.5 to 0-50˝ w.c.  Positive, negative or differential air and
compatible gas pressure can be measured with accuracies as low as
±.5% of full scale. The basic mechanical components of the Series 605
Magnehelic

®

indicating transmitter are similar to those used in the pop-

ular, time-proven Magnehelic

®

differential pressure gage. 

STANDARD ACCESSORIES

Mounting ring
Snap ring
(4) 6-32 x 1-1/4 screws (panel mtg.)
(3) 6-32 x 5/16 screws (surface mtg.)
(2) Tubing to 1/8˝ NPT adapters
(2) 1/8˝ NPT plugs
Adjustment key

Series 605 Magnehelic

® 

Differential Pressure Indicating Transmitter

Specifications - Installation and Operating Instructions

Bulletin E-68

DWYER INSTRUMENTS, INC. 

Phone: 219/879-8000 www.dwyer-inst.com

P.O. BOX 373 • MICHIGAN CITY, IN 46361, U.S.A. 

Fax: 219/872-9057

e-mail: [email protected]

23/32

[18.26]

1

[25.40]

30

°

1-1/8

[28.58]

(3) #6-32 x 3/16 [4.76]

DP HOLES EQUALLY SPACED

ON A Ø4-1/8 [104.78] B.C.

FOR PANEL MOUNTING

11/16

[17.46]

1/8 FEMALE NPT

LOW PRESSURE 

CONNECTION

1/2 [12.70]

1-3/4

[44.45]

1/8 FEMALE

NPT HIGH

PRESSURE

CONNECTION

2-1/16

[52.39]

2

[50.80]

1-1/4

[31.75]

2-1/2

[63.50]

3/16

[4.76]

5/8 [15.88] 

PANEL MAX

Ø5

[127.00]

Ø4-47/64

[ 120.25]

(4) 6-32 HOLES

EQUALLY SPACED ON 

A 5-1/8 [130.18] B.C.

FOR FLUSH MOUNTING

Ø4 [101.60] 

FACE

5-1/2 [139.70]

O.D. MOUNTING 

RING

SPECIFICATIONS
GAGE SPECIFICATIONS
Service: 

Air and non-combustible, compatible gases.

Wetted Materials: 

Consult factory.

Accuracy:  

See chart.

Stability:

±1% F.S./yr.

Pressure Limits: 

See chart.

Temperature Limits: 

20 to 120°F (-6.67 to 48.9°C).  

Process Connections: 

1/8˝ female NPT.

Size: 

4˝ (101.6 mm) dial face, 5˝ (127 mm) O.D. x 2-11/16˝ (68.3 mm).

Weight: 

1 lb, 12.6 oz (811 g).

Agency Approvals: 

CE.

TRANSMITTER SPECIFICATIONS
Accuracy: 

See chart (includes linearity, hysteresis, repeatability).   

Temperature Limits: 

20 to 120°F (-6.67 to 48.9°C).

Compensated Temperature Range: 

32 to 120°F (0 to 48.9°C).

Thermal Effect: 

±0.025% F.S./°F (0.045% F.S./°C).

Power Requirements: 

10-35 VDC (2-wire).

Output Signal:

4 to 20 mA.

Zero and Span Adjustments: 

Protected potentiometers.

Loop Resistance: 

DC; 0-1250 ohms maximum. 

Current Consumption: 

DC; 38 mA maximum.

Electrical Connections: 

Screw terminal block.

Mounting Orientation: 

Diaphragm in vertical position. Consult factory for

other position orientations.

Patent No. 4,890,497

Model

605-00N
605-11
605-0
605-1
605-2
605-3
605-6
605-10

Range 
in w.c.

.05-0-.20
.25-0-.25
0-.50
0-1.0
0-2.0
0-3.0
0-6.0                                                 
0-10

Maximum
Pressure

25 psi (1.7 bar)
25 psi (1.7 bar)
25 psi (1.7 bar)
25 psi (1.7 bar)
2 psi (13.79 kPa)
2 psi (13.79 kPa)
2 psi (13.79 kPa)
2 psi (13.79 kPa)

Electrical
Ac/-%

2
2
2
2
0.5
0.5
0.5
0.5

Model

Range 
in w.c.

605-20
605-30
605-50

605-60PA
605-125PA
605-250PA
605-500PA

0-20.0
0-30
0-50

Range in Pa

0-60
0-125
0-250
0-500

Maximum
Pressure

20 psi (1.4 bar)
20 psi (1.4 bar)
20 psi (1.4 bar)

25 psi (1.7 bar)
25 psi (1.7 bar)
25 psi (1.7 bar)
2 psi (13.79 kPa)

Electrical
Ac/-%

0.5
0.5
0.5

2
2
2
0.5

Mechanical
Ac/-%

4
3
3
2
2
2
2
2

Mechanical
Ac/-%

2
2
2

4
3
2
2

E-68:E-68  2/24/10  10:21 AM  Page 1

Содержание 605-00N

Страница 1: ...TING RING SPECIFICATIONS GAGE SPECIFICATIONS Service Air and non combustible compatible gases Wetted Materials Consult factory Accuracy See chart Stability 1 F S yr Pressure Limits See chart Temperature Limits 20 to 120 F 6 67 to 48 9 C Process Connections 1 8 female NPT Size 4 101 6 mm dial face 5 127 mm O D x 2 11 16 68 3 mm Weight 1 lb 12 6 oz 811 g Agency Approvals CE TRANSMITTER SPECIFICATION...

Страница 2: ... 4 MOUNTING The Series 605 Transmitter may be either panel mounted or surface mounted A PANEL MOUNTING Cut a 4 3 4 or 120mm dia hole in panel and insert the complete unit from the front Slip on the mounting ring and install the split snap ring in the groove on the bezel Seat the mounting ring against the snap ring and thread the four screws through the tapped holes Tighten screws against rear of p...

Страница 3: ...t Referring to Figure B RL becomes the 250 ohm resistor and point X and Y are connected to the receiver input point X being positive and point Y negative or ground The resistor should be connected at the panel end of the transmitter current loop close to the receiver input to take advantage of the immunity of the cur rent loop to electrical noise pickup Most electronic component distribu tors stoc...

Страница 4: ...e number of units x 20 mA In the example shown this would be 4 x 20 or 80 mA minimum MAINTENANCE Upon final installation of the Series 605 Transmitter and the companion receiver including the A 701 Digital Readout no routine maintenance is required A periodic check of system calibration is recommended The Series 605 Differential Pressure Transmitter is not field repairable and should be returned f...

Отзывы: