ITVC Series – Intelligent Total Valve Controller IOM-ITVC-LB-04
DVG AUTOMATION S.p.A.
Legal & Operative HQ: 29016 Cortemaggiore (Piacenza) Italy, Via G. Rossetti n° 2
Tel. (+39) 0523 255811; Fax (+39) 0523 255890;
Fully Paid In Capital: Euro 1.000.000,00=
ISO
9001,
ISO
14001,
OHSAS
18001
CERTIFIED
REA 167410 - VAT 01494460338
COMPANY SUBJECT TO MANAGEMENT AND COORDINATION BY G.I.V.A. S.P.A. W ITH HEADQUARTERS IN RHO (MILAN), RECORDED UNDER NUMBER 02917180172 IN
MILAN'S REGISTER OF COMPANIES
[email protected]
www.dvgautomation.it
SHEET 23 DI 28
4.8
LB-d parameters
By this option the following parameters can be set:
Condition to start
: type of test to decide if the safe action should start. Two options are available: The “read
differential pressure is higher than a configured limit” or “the read differential pressure is less than a
configured limit”. One only test at a time can be set
Max differential pressure
: limit of pressure if the “condition to start” is “differential pressure is higher than a
configured limit”
Min differential pressure
: limit of pressure if the “condition to start” is “differential pressure is less than a
configured limit”
Safe action
: action to perform if the configured test is true. Three options are available, stayput, open, close.
One option at a time can be set.