16
RMO100G Getting started
6.8 Deleting Results of Previous Tests
In the
Memory
menu, press
ENTER
.
Press
ENTER
once more to delete all saved measurements from the memory positions.
Press
STOP
to
leave the
Memory
menu without deleting any measurements.
6.9 Duty Cycles
During tests, RMO100G generates a high DC current that heats up the test set. To prevent RMO100G
from overheating, certain duty cycles apply depending on the used test current.
S i n g l e T e s t
Test current
(A)
Cooling time between
first 3 tests (sec)
Cooling time after
4 tests (sec)
5, 10, 20, 30,
40, 50, 60, 80,
100
0
0
C o n t i n u o u s T e s t
Test current
(A)
Maximal test
duration
time (sec)
Cooling time
(sec)
5, 10, 20, 30,
40, 50, 60, 80,
100
300
0
A built-in control prevents these cooling times from being skipped. If you try to start a test within the
cooling period, the display shows "Wait" and a timer counting down. After the cooling period has
elapsed, start the test using the set test parameters by pressing the
START
button. Cooling of RMO100G
is supported by a built-in fan that is automatically activated every time a test is started from the
Ready
state. It continues running 5 minutes after the test is finished.
Table 6-16:
Cooling time
between
single
tests
Figure 6-15: The
Memory
menu showing an option to
delete all saved
measurements from the
memory positions
Table 6-17:
Cooling time
between
continuous
tests