OPERATION

The device operates continuously. It is recom-
mended that the device be interlocked with a
power disconnect to prevent inadvertent UV-C
exposure when access panels are removed.

CONNECTING THE HARNESS 

(Fig.8 )

After lamp has been installed, attach electrical
harness. The harness connector is asymmetri-
cal and can only be attached one way. If the
harness does not attach easily, rotate 90
degrees and try again.

Fig. 8

Attach electrical harness to lamp.

STRAIGHT-LAMP INSTALLATION 

(Fig.7 )

To maximize the efficiency and life of the UV-C
lamp, clean each lamp prior to installation.
Use isopropyl alcohol and cotton cloth to wipe
dust and fingerprints from the lamp.

To install the lamp in its straight-lamp con-
figuration the lower slide bracket must be
removed.

After the lower slide bracket has

been removed gently insert lamp into lamp hole
and push upper slide bracket over the retaining
lip of the lamp and tighten the two knurled nuts
until the lamp is securely fastened.

Fig. 7

After lower slide clip is removed, slip upper slide bracket

over retaining lip of lamp and tighten two knurled nuts.

FINISH INSTALLATION

Close the cover, reinstall the cover retaining
screws, and turn on the electrical service.
Apply included warning label on nearby main-
tenance access panel.

Note:

This device uses a cover safety inter-

lock. The cover must be closed for the device
to operate.

Electrical disconnect required.

Areas where UV fixtures are installed must
have access panel/door disconnect
switches installed. Never view UV-C light
without protective eyewear.

WARNING

Lamp retaining lip

Remove lower slide bracket.

Upper slide bracket

Содержание BIO-FIGHTER 4Xtreme

Страница 1: ...owth on HVAC coils allowing them to operate at peak efficiency where the light shines Also significantly reduces bacteria viruses fungi and yeasts on surfaces exposed to the UV C energy NEMA 4X weatherproof enclosure High output long life UV C lamps Multi voltage electronic ballast Low maintenance and reduced costs INCLUDED INSIDE BOX Bio Fighter 4Xtreme ultraviolet light system UV C lamp shipped ...

Страница 2: ... 347 5 817 276 6 245 293 6 267 924 6 280 686 6 313 470 6 627 000 6 539 727 6 932 494 6 550 257 Specifications subject to change without notice 4Xtreme 21 20 4Xtreme 33 32 4Xtreme 45 44 4 25 8 11 56 SPECIFICATIONS EPA Device Manufacturer Establishment No 73316 TX 1 The product and technologies described are not medical devices and are not intended to diagnose treat cure or prevent any disease or il...

Страница 3: ...rradiate an air filter to neutralize the microbiological matter on the air filter surface such as would be found in the return air drop of a basement application or in the return plenum of a horizontal system in an attic take precautions as described in note above and make sure the UV fixture is placed on the return side of the filter DO NOT INSTALL THE UV FIXTURE ON EITHER SIDE OF THE FILTER IN H...

Страница 4: ...allation WARNING Fig 2 For vertical installations use either the straight lamp or tilt lamp configuration Note Removal of lower slide clip is required for straight lamp configuration Fig 1 For horizontal installations use the tilt lamp configuration for greater UV C exposure into the drain pan ENCLOSURE MOUNTING Fig 3 Tape the provided mounting template at the desired installation location Use thi...

Страница 5: ...iance with all national and local electrical and mechanical codes Failure to do so will void Dust Free warranty CONDUIT INSTALLATION Fig 4 Remove the two cover retaining screws and swing open the cover to access ballast and wiring Install an appropriate weatherproof conduit on the side of the enclosure Drill points are marked on two sides of the enclo sure where it is safe for conduit installation...

Страница 6: ...in its straight lamp con figuration the lower slide bracket must be removed After the lower slide bracket has been removed gently insert lamp into lamp hole and push upper slide bracket over the retaining lip of the lamp and tighten the two knurled nuts until the lamp is securely fastened Fig 7 After lower slide clip is removed slip upper slide bracket over retaining lip of lamp and tighten two kn...

Страница 7: ...ner Do not incinerate LAMP DISPOSAL Dispose of your spent UV C lamps at your local recycling center You may also send your spent lamps in the same container you received your replacement lamps to Dust Free Lamp Reclamation 1112 Industrial Drive Royse City TX 75189 IF THE LAMP DOES NOT ILLUMINATE Check that the lamp connector is securely attached to lamp Check that the fuse is in good working order...

Страница 8: ...UST FREE EXPRESSLY DISCLAIMS ALL OTHER WARRANTIES WHETHER WRITTEN OR ORAL IMPLIED OR STATUTORY INCLUDING BUT NOT LIMITED TO ANY WARRANTIES OF MERCHANTABILITY WORKMAN SHIP OR FITNESS FOR A PARTICULAR USE If the limited warranty is void due to failure to use a quali fied contractor all disclaimers of implied warranties shall be effective upon installation How to make a warranty claim or have questio...