SONDELTOX

4-20mA detectors for toxic gases 

&

 O2

DURAN ELECTRONICA CALIBRATES ONE BY ONE ALL DETECTORS USING CALIBRATION GAS

VERIFY THE ZEROING AT LEAST ONCE IN A YEAR

SONDELTOX 

are

 

4-20mA

 

detectors using electrochemical sensors for the detection of toxic 

gases & O2. They are compatible with 

EUROSONDELCO and SIEMENS CC62P 

(using interface) 

and with any other system provided of 4-20mA standard input.

Sondeltox for oxygen provided of backlit LCD display is available.

Available for these gases; Carbon monoxide (CO), Nitrogen dioxide (NO2), Sulphur dioxide 
(SO2), Nitrogen monoxide (NO), Clorhydric acid (HCl), Hydrogen sulphide (H2S), Chlorine (CL2), 

Oxygen (O2).

TECHNICAL CHARACTERISTICS (under 20ºC / 50% RH / 1013 mBar conditions)

* Bottom of scale for 

EUROSONDELCO 

and 

SIEMENS CC62P

.

MEASUREMENT RANGE (in ppm)

MODEL WITH DISPLAY

CO

0-50, 0-100, 0-200, 

0-300*

, 0-500, 0-1000, 0-2000

-

NO

2

0-5, 0-10, 

0-20

*, 0-30, 0-50, 0-100, 0-200, 0-300

-

SO

2

0-10, 0-20, 0-30, 0-50, 0-100, 

0-200*

-

NO

0-20, 0-30, 0-50, 0-100, 

0-200*

, 0-300

-

HCl

0-10, 0-20, 0-50, 0-100, 

0-200*

-

H

2

S

0-5, 0-10, 0-20, 0-30, 0-50, 0-100, 

0-200*

, 0-300

-

Cl

2

0-5, 0-10, 0-20, 0-30, 0-50, 0-100, 

0-200*

-

O

2

0-25 (in %)

Yes

H

2

0-200, 0-300, 0-500, 0-1000, 0-2000, 0-20.000, 0-50.000

-

CO

NO

2

SO

2

NO

HCl

H

2

S

O

2

Cl

2

H

2

Power supply / Consumption

From

 1

0 to 35V DC / 21mA max.

Resolution

0,5 ppm

0.1 ppm

0.1 ppm

0.5 ppm

0.5 ppm

0.25 ppm

0.1%

0.1 ppm

2 ppm

Measurement Range   

0-2000ppm 

0-300ppm 

0-200ppm 

0-300pmm 

0-200ppm 

0-300ppm 

0-25%

0-200ppm 

0-200 ppm

Repeatability

1% F.S.

2% F.S.

2% F.S.

2% F.S.

2% F.S.

1% F.S.

1% F.S.

2% F.S.

2% F.S.

Time of response 

T90<30 s

T90<35 s

T90<15 s

T90<10 s

T90<120 s 

(typical 100)

T90<35 s

T90<15 s

T90<60 s

T90<30 s

Temperature range

–20ºC to +50ºC

Pressure range

Atmospheric ± 10%

Pressure coefficient 

0,020 ± 
0,008% 

signal/mBar

without data  without data 

0.016%

 signal/mBar

without data 

0,008 ± 
0.002% 

signal/mBar

0.02% 

signal/mBar

without data 

0,009 ± 
0.003% 

signal/mBar

Enclosure

IP65

Relative humidity range

From 15 to 90% without condensation

Maximum zero change

(+20 ºC to +40 ºC) 

9ppm

0.2ppm

0.1ppm

9ppm

1,5 ppm

2ppm

9ppm

0.2ppm

10ppm

Output linearity

Linear in full range

Output drift

<5% / year

<2% / month

<2% / month <2% / month

<2% / month

<2%/ month

<5% / year

<2% / month

<2% / month

Output impedance

4M

Ω

4M

Ω

4M

Ω

4M

Ω

4M

Ω

4M

Ω

15M

Ω

4M

Ω

4M

Ω

Expected operation life

3 years on air

2 years on air

2 years on air

3 years on air

2 years on air

2 years on air

2 years at 20% O2 2 years on air

2 years on air

Backlit LCD Display

Optional

Storage time (months)

6

Storage temperature

0-20ºC

Coverage area (m

2

) Approx

300

200

200

150

200

150

200

100

100

Installation height

-from floor- (cm)

170-200

100

30/40

100

100

100

170-200

100

30/40 cm 

from ceiling

Measurements (mm)  Weight 

(gr) Approx

125 x 150 x 63   -   300