![DURAG D-R 290 Скачать руководство пользователя страница 149](http://html.mh-extra.com/html/durag/d-r-290/d-r-290_operating-manual_2541137149.webp)
7 | Checking / setting parameters with D‑ESI 100
D-R 290
149
Temperature compensation
Temperature and pressure compensation using the device
parameters
The Dust and Opacity Monitor D‑R 290 can covert a calculated dust concentration into
a dust concentration per standard cubic metre.
For this the dust concentration determined in mg/m
3
is converted to the standard sta
tus at 0°C according to the following formula:
C
(standard)
=
Temperature of the gas being me 273.15°C
Standard tempe 273.15°C
×
Media pressure
1013.25 hPa
(measurement)
C
The display of the calculated value based on a standard cubic metre is performed by
selecting the type code 0x0052 for one of the four output channels. (see also section
The determination of the media conditions is performed either
●
by describing the media conditions by D−ESI 100, D−ISC 100 or Modbus.
Setting path:
Device (D‑R 290 ) > >
Common parameters
>
D‑R 290
Setting variables
>
Media conditions
●
by using a D−ISC 100 analogue input module and the "Media conditions" software
module in the D−ISC 100.
●
in a special variant of the D‑R 290 via the optional 4−20 mA temperature input
(see section
7.7.10.2 Temperature compensation via an external temperature trans
Temperature compensation via an external temperature
transmitter (special variant)
The necessary determination of the temperature of the gas being measured is per
formed by means of an additional temperature measurement input (4-pin plug connec
tion) at the measuring head (
The parameter
Common Parameters > Setting variables > Media conditions >
Media temperature
for the standardisation described above is meaningless for this device variant.
This input is arranged as a 4..20 mA interface. Suitable temperature transmitters
(transducers) with 4..20 mA output are available as accessories.
The temperature measurement range be selected as any of
●
0..200°C (32..392°F),
●
0..400°C (32..752°F) and
●
0..1000°C (32..1832°F)
and should correspond to the temperature of the gas being measured.
7.7.10
7.7.10.1
7.7.10.2
Fig. 7.23: Temperature
transmitter
Содержание D-R 290
Страница 12: ...12 D R 290 ...
Страница 18: ...1 General 18 D R 290 ...
Страница 20: ...20 D R 290 ...
Страница 28: ...2 Safety 28 D R 290 ...
Страница 30: ...30 D R 290 ...
Страница 38: ...3 Delivery 38 D R 290 ...
Страница 40: ...40 D R 290 ...
Страница 60: ...4 Product description 60 D R 290 ...
Страница 106: ...106 D R 290 ...
Страница 152: ...152 D R 290 ...
Страница 174: ...8 Maintenance 174 D R 290 ...
Страница 176: ...176 D R 290 ...
Страница 177: ...9 Appendix D R 290 177 Appendix Measurement point questionnaire Fig 9 1 Measurement point questionnaire 1 9 9 1 ...
Страница 178: ...9 Appendix 178 D R 290 Fig 9 2 Measurement point questionnaire 2 ...
Страница 188: ...9 Appendix 188 D R 290 Fig 9 11 Dimensional diagram D TB 100 supply unit Dimensional diagram purge air unit D BL 9 3 7 ...
Страница 193: ...9 Appendix D R 290 193 Fig 9 18 Dimensional diagram weather protection cover control electronics protective device ...
Страница 194: ...9 Appendix 194 D R 290 ...
Страница 200: ...11 Index 200 D R 290 ...
Страница 202: ...GmbH Kollaustraße 105 22453 Hamburg Germany www durag com ...