The individual user should take care to determine, prior to use or installation, whether this device is suitable, adequate or safe 

for the use intended.  Since individual applications are subject to great variation, DuraComm makers no representation or warranty as 
to the merchantability, suitability or fitness of these units for any specific application. 

The precision regulated power supplies operate internally from voltages in excess of 300 volts.  In rare cases, voltage spikes 

or transients on the AC power line, or overheating, may cause a component failure in the power supply. Overloading the output will 
cause the over current feature to operate.  In either case, the cause must be determined and corrected.   Failures require investigation 
as to cause and/or repair of the unit.

  

THERE ARE NO USER SERVICEABLE PARTS INSIDE.  HAZARDOUS VOLTAGES EXIST INSIDE THE UNIT.  SERVICE AND 
REPAIR MUST BE REFERRED TO QUALIFIED FACTORY PERSONNEL.

 

 

INSTALLER NOTES 
 

The outputs are

 NOT

 referenced to the chassis.  The Modular System can be used either positive or negative ground.   

 

DO NOT

 block any of the cooling vents on the sides and always allow adequate ventilation by not installing the unit inside 

tightly closed spaces.  Physical mounting position is not critical but the cooling vents and the load controlled cooling fan must not be 
blocked. 

AC MAIN OPERATING INPUT VOLTAGE 
 

The AC input is auto-ranging and will operate without adjustment from 85 VAC to 264 VAC.  Maximum efficiency is realized 

with input voltages above 180 VAC.   Linear de-rating to ~85% @ 90 VAC is recommended for AC inputs less than 180 VAC. 

 

CONDUCTOR ATTACHMENT 
 

The DC output terminals are 6mm diameter and a ¼ inch ring terminal will fit exactly.  The ¼ inch ring terminal may be 

crimped or soldered to the conductors before attaching to the DC output terminals.  

DO NOT

 solder the ring terminals while on the DC 

output studs.   Use a 10 mm wrench to securely tighten the hex nut on the stud.

 

 

RECOMMENDED COPPER WIRE SIZE FOR CURRENT CAPACITY 

 

(Insulated Wire, Single Conductor in free air) 

 

Current Level in Amperes 

<7 AMPERES 

Wire Size 

20 AWG Up to 5 feet 

18 AWG Up to 10 feet 

14  AMPERES 

18 AWG Up to 5 feet 

16 AWG Up to 10 feet 

20  AMPERES 

16 AWG Up to 5 feet 

14 AWG Up to 10 feet 

30  AMPERES 

14 AWG Up to 5 feet 

12 AWG Up to 10 feet 

40  AMPERES 

12 AWG Up to 5 feet 

10 AWG Up to 10 feet 

50  AMPERES 

10 AWG Up to 5 feet 

8  AWG Up to 10 feet 

70  AMPERES 

8 AWG Up to 5 feet 

6 AWG Up to 10 feet 

100 AMPERES 

6 AWG Up to 5 feet 

4 AWG Up to 10 feet 

 
 

 