  Input Voltage 90 to 264 VAC 

  13.8 VDC Output @ 54 Amps Max 

  Remote Monitoring of Power supply Voltage and 

Current, and an External Alarm. 

  Remote control of power supply ON/OFF and External 

Alarm output ON/OFF via Web Interface 

  Short Circuit / Overload / Over Voltage / Over 

Temperature Protection  

  Output Power Led 

  3 year warranty

 

 

 

 

SPECIFICATIONS 

 

Output Voltage ....................................................................................................................................................................... 13.8 VDC 

Output Voltage Tolerance .......................................................................................................................................................... +/- 1 % 

Output Amperage ........................................................................................................................................................... 54 Amps max. 

Maximum Power, continuous ................................................................................................................................................ 750 Watts 

Maximum Ripple and Noise ........................................................................................................................................ 150 mV p-p max 

Input Voltage, Switch Selectable ................................................................................................................................. 110-or 220 VAC 

Input Frequency Range ........................................................................................................................................................... 47-63 Hz 

Maximum AC Current ............................................................................................................. 8.2 Amps/115 VAC; 3.9 Amps/230 VAC 

Typical Efficiency .......................................................................................................................................................................... 89 % 

Max Inrush Current, single cycle ........................................................................................... 25 Amps / 115 VAC, 40 Amps / 230VAC 

Short Circuit Protection ................................................................................................................................. Constant Current Limiting 

Overload Protection (operates) ................................................................................................................................. typical 105-125 % 

Line Regulation ....................................................................................................................................................................... +/- 0.5 % 

Load Regulation ...................................................................................................................................................................... +/- 0.5 % 

Fan Control ................................................................................................................................... Heat sink temp >140 F (60 C) = ON 

Over Temperature ........................................................................................................................ >195 F (90 C) auto output shutdown 

Rise Time following ON ............................................................................................................................................................... 50 mS 

Hold Time following OFF ............................................................................................................................................................. 10 mS 

Working Temperature Range ............................................................................................................. -22 F to +158 F (-30 C to +70 C)  

Storage Temperature ......................................................................................................................... -40 F to +185 F (-40 C to +85 C) 

Withstand Voltage .................. 3 KVAC @ 10 ma (I/P-O/P)/1 min, 2 KVAC @ 10 ma (I/P-FG)/1 min, 500 V @ 10 ma (O/P-FG)/1 min 

Dimensions ...................................................................................................................................................... 1.75” H x 19” W x 13” D 

Weight ......................................................................................................................................................................................... 8.

0

 lbs 

 

 

Содержание HE1U-5012-MU

Страница 1: ...um Power continuous 750 Watts Maximum Ripple and Noise 150 mV p p max Input Voltage Switch Selectable 110 or 220 VAC Input Frequency Range 47 63 Hz Maximum AC Current 8 2 Amps 115 VAC 3 9 Amps 230 VAC...

Страница 2: ...d or SNMP Logging Rate 1 minute resolution 1 minute to 1 hour Log Download Format Comma Separated Values CSV File SNMP MIB File Download from Device Setup Page 5V Supply Maximum Current 300 mAmps INST...

Страница 3: ...oltage of 60 VDC for the revision 2 monitoring hardware included with the HE1U 5012 MU The Alarm Input Ain is referenced to G and is a LED in series with a 220 Ohm resistor internally and can withstan...

Страница 4: ...dress of 70 B3 D5 6B 3 Write down the IP address of the HE1U 5012 MU then proceed to the section in this manual named Open a Web Connection to the HE1U 5012 MU Using Static HE1U 5012 MU IP and Network...

Страница 5: ...fox internet Explorer etc and enter the IP address of the power supply on your network into the URL box on the browser see the screenshot below If you are unable to connect to the device with the brow...

Страница 6: ...ogin Enter the user name and password Factory default username and password are as follows Admin Users have full control of the device Username admin cannot be changed Password admin Control users hav...

Страница 7: ...7 of 20 December 18 2015 NETWORK SETUP...

Страница 8: ...arch for training material online under SNMP Traps MIB Browsers and SNMP Monitoring The MIB file for the HE1U 5012 MU can be downloaded from the HE1U 5012 MU after you connect to it with your browser...

Страница 9: ...9 of 20 December 18 2015 EMAIL SETUP Email Setup Enter the required email setup parameters given to you by your System Administrator You can also send a test email from this screen...

Страница 10: ...10 of 20 December 18 2015 DEVICE SETUP...

Страница 11: ...d data so that the source of the card can be identified after it removed from the HE1U 5012 MU SNMP MIB File Download The SNMP MIB File can be downloaded from this page Date and Time Settings Configur...

Страница 12: ...12 of 20 December 18 2015 SENSOR SETUP...

Страница 13: ...g alarms are set up in the Alarm Setup screen See the Alarm Setup section for more information In the HE1U 5012 MU the Digital Output 1 is an alarm output and Digital Output 2 controls the ON OFF stat...

Страница 14: ...14 of 20 December 18 2015 ALARM SETUP...

Страница 15: ...screen above Firmware 2 0 includes additional settings for alarms This screen is where thresholds are set to define alarm conditions for the analog channels You can choose to set an email notificatio...

Страница 16: ...ld be taken when changing any of these settings NOTE To hard reset your device back to factory settings press the red button on the HE1U 5012 MU PCB and hold it for more than 30 seconds You will need...

Страница 17: ...cember 18 2015 REMOTE MONITORING AND CONTROL STATUS PAGE Status screen This screen shows the status of all analog and digital inputs A user can also download the Log file from this page AC Voltage is...

Страница 18: ...ile devices Just use the same IP address and add m for example 192 168 100 220 m HE1U 5012 MU MAINTENANCE Battery The battery on the HE1U 5012 MU is used to back up the real time clock for logging pur...

Страница 19: ...Copper ferrules prevent the current transfer from being influenced by dissimilar metals and remove the risk of corrosion Always use the correct tool to crimp the ferrule RECOMMENDED COPPER WIRE SIZE...

Страница 20: ...d prior to inclusion of such changes DuraComm requires any product needing in or out of warranty service to be returned to DuraComm All requests for warranty service must be accompanied by proof of pu...

Отзывы: