INSTALLATION BLOCK DIAGRAM
(Shown with factory jumper for PS U ON)
HE1U-1248-BBLVD Remote Control and DC-OK
Between RC- and RC+
Output Status
Switch Closed
PSU ON
Switch Open
PSU OFF
Between DC-OK and GND
Output Status
0 to 1 V
PSU ON
3.3 to 5.6 V
PSU OFF
May Also be used Open-Collector
10 mA max, 5.6 V max
HE1U-1248-BBLVD Wiring Layout
This system setup will provide continuous power to the load and maintain the battery bank with smart charger while AC power
is on. There is a seamless transfer of the load to the battery when the AC power goes off. The LVD will disconnect the battery if the
voltage drops below 42 VDC. The battery reconnects once AC power is restored and voltage reaches 50 VDC.
HE1U-1248-BBLVD
+
-
-
+
Battery
+
-
Load
+
-
AC
DC-OK GND
20.84mm
RC+ RC-