3 Product Introduction 

 

3.1 System architecture 

 
The POWER CENTER HUB is the communication gateway for the line of Duracell Power Center 
microinverters.  The gateway collects microinverter data via Wi-Fi and reports this data to the Power 
Center’s server via a customer supplied internet connection, either via hard-wired ethernet (recommended) 
or Wi-Fi.  Local monitoring applications include PC-based web-browser and IOS / Android apps. 
 
3.1.1 System Capacity 
  
A single POWER CENTER HUB can monitor up to a total of 99 PV panels (PV port inputs).  Mutiple gateways 
can be provisioned where PV arrays exceed this limit. 
 

 

 
 
 

3.1.2: Basic requirements & prerequisites 

 

 

120VAC power outlet required for the POWER CENTER HUB power adapter. 

 

Indoor installation only.  Outdoor installation requires a non-metallic, NEMA type 4  rated enclosure 
(not included).  Operating temperature range is -20°C to +55°

C.

 

 

Internet service required.  Router with dedicated Ethernet port recommended. 

 

Wall-mounting bracket requires two #8 screws.  Use anchors appropriate for wall material. 

 

Completed serial number map from the Duracell Power Center Microinverter Installation Manual. 

 

Installer must have a registered Installer APP account 

(Contact dealer/reseller for details)

Server 

PC-

Содержание PC-PRO-WIFI

Страница 1: ...POWER CENTER USER MANUAL Model PC PRO WIFI For use with Duracell Power Center Microinverters...

Страница 2: ...4 Locating the Power Center Hub 4 4 1 Installing the antennas 4 4 2 Proximity to the PV array 4 4 3 Proximity to the customer supplied internet router 4 4 4 Mapping the Power Center Hub to the PV arra...

Страница 3: ...ent damage Do not install the equipment in adverse environment conditions such as flammable explosive corrosive extreme high or low temperature and humidity Do not use the equipment when the safety de...

Страница 4: ...V panels PV port inputs Mutiple gateways can be provisioned where PV arrays exceed this limit 3 1 2 Basic requirements prerequisites 120VAC power outlet required for the POWER CENTER HUB power adapter...

Страница 5: ...ons Indicators B Power C Server communication D Microinverter communication E System alarm Other Features A SD card slot N Antenna screw type O Wall bracket P Serial number label Ports F Wi Fi antenna...

Страница 6: ...NTER HUB can communicate with the router via hard wired ethernet or Wi Fi The ideal location for microinverter communication may conflict with router communication In the case that the resulting Wi Fi...

Страница 7: ...t Modes LED State Description Firmware update Initializing Power ON Server online Internet offline Internet online server offline Local APP connected Microinverter communication OK Microinverter IDs i...

Страница 8: ...it s being installed Select Next when completed 5 Select Add DTU ID then scan or manually input the DTU ID Select Next when completed 6 Select Start binding then choose the angle tilt for the PV array...

Страница 9: ...etary RF Nordic Maximum distance open space 200m Maximum PV panels 99 Server communication Type WIFI 802 11b g n 1 Ethernet Sample rate 15 minute Mechanical Data Ambient temperature range C 20 C 65 C...

Страница 10: ...8 Appendix A Installation Map Template...

Страница 11: ...Doc 97016...

Отзывы: